Part Number or the Week S3EP-V-VAD-HPR-R

Gent S4 Dual Optical Heat Sensor High Power red VAD

Part no.S4-711-VAD-HPR
BrandGent
RangeS4 Detectors
Sub-rangeDetectors with VAD
Gent by Honeywell S4-711-VAD-HPR S4 Dual Optical Heat Sensor High Power red VAD — circular white detector with central lens

Image for illustration; item supplied may differ

At a glance

  • Dual optical detection and heatForward and backward optical sensing combine with heat detection in one head.
  • High Power red visual alarmHigh, Medium and Low ceiling coverage: C-3-14, C-3-13 and C-3-10.
  • Loop powered with isolatorThe loop supplies the device, which includes a short-circuit isolator.
  • Low setting on NanoNano operates this VAD at Low, with C-3-10 ceiling coverage.
  • Synchronisation within one panelVisual alarm outputs synchronise across all loops of one panel; synchronisation does not cross a panel network.
  • IP21C mountingUse the S4-701 base and IP seal plate for IP21C.

Description

The Gent S4-711-VAD-HPR is an S-Quad dual optical and heat sensor with a red High Power VAD for Vigilon Plus, Compact Plus and Nano. At High, its light covers C-3-14; on Nano it runs at Low with C-3-10 coverage. It takes power from the loop and has a built-in short-circuit isolator. This version has no sounder or voice output; the S4-711-V-VAD-HPR adds voice. Use the S4-701 base and IP seal plate for IP21C. By default, the light flashes once every two seconds. Across the S-Quad range, the head is 117 mm in diameter and 49.6 mm high. A red LED gives a fire indication at the device. The enclosure is ABS.

S4-711-VAD-HPR combines forward and backward optical smoke sensing with heat. The panel selects the detection state. States 2, 6, 11 and 12 do not meet EN 54-7; the selected state must match the required smoke and heat response.

Read the full technical description

S4-711-VAD-HPR combines forward and backward optical smoke sensing with heat. The panel selects the detection state. States 2, 6, 11 and 12 do not meet EN 54-7; the selected state must match the required smoke and heat response.

The alarm output is a red visual warning. This model has no sounder or speech function. S4-711-V-VAD-HPR combines dual optical and heat detection with a red High Power VAD and a voice sounder.

The red High Power VAD offers High, Medium and Low settings. Ceiling coverage is C-3-14, C-3-13 and C-3-10 respectively. High also supports O-4.5-14 and Medium supports O-4-13. On Nano the light is fixed at Low, giving C-3-10 coverage. Use the two-second flash interval for EN 54-23 operation.

Supplied with one sensor head and one blue protective dust cover. The mounting base and IP21 mounting plate are not included. Fit the S4-701 base with its IP seal plate to achieve IP21C. S-Quad VAD installations require an IP21 mounting plate for EN 54-23 operation. The visual alarm synchronises across all loops of the same panel. Synchronisation does not extend across a network of panels.

For Vigilon Plus and Compact Plus VAD coverage, use MCC/MCB software v4.52 or later and LPC software v4.48 or later. Use Vigilon Commissioning Tool v1.32 or later for device setting changes. Nano configuration uses Nano Commissioning Tool v3.0 or later. Verify the system design with the Gent Battery Standby and Loop Load calculator.

Specifications

Sensor typeDual optical and heat
Power sourceLoop powered
Loop isolatorBuilt-in short-circuit isolator
Panel families (S-Quad)Vigilon Plus, Compact Plus and Nano
Operating voltage (S-Quad)35-48 V
Enclosure (S-Quad)ABS
Body colour (S-Quad white models)White, RAL 9010
Head dimensions (S-Quad)117 mm diameter × 49.6 mm height
Operating temperature (S-Quad)-10°C to +50°C
Storage temperature (S-Quad)-20°C to +70°C
Relative humidity (S-Quad)95%, non-condensing, at +5°C to +45°C
Mounting baseS4-701 with IP seal plate
Voice outputNone
VAD light colourRed
VAD power classHigh Power
IP ratingIP21C with S4-701 base and IP seal plate
VAD flash interval2 seconds (0.5 Hz), EN 54-23 setting
VAD ceiling coverage: HighC-3-14; 461.8 m³
VAD ceiling coverage: MediumC-3-13; 398.1 m³
VAD ceiling coverage: LowC-3-10; 235.6 m³
VAD open coverage: MediumO-4-13; 530.9 m³
VAD open coverage: HighO-4.5-14; 692.7 m³
VAD-only current maxima (HPR class)High 16 mA; Medium 11.5 mA; Low 6 mA
Sounder outputNone
Programmable I/O (S-Quad)Monitored input or unmonitored output
External I/O cable limit (S-Quad)15 m from base to external I/O unit

Specifications per manufacturer documentation, subject to change. E&OE.

Standards and approvals

StandardWhat it covers
LPCB approvedApproved by the Loss Prevention Certification Board for fire detection and alarm system products.
EN 54-5:2000 + A1:2002
EN 54-7:2000 + A1:2002 + A2:2006
EN 54-17:2005 + AC:2007
EN 54-18:2005 + AC:2007
EN 54-23:2010
LPCB ref 042bw/01

Approval body: Loss Prevention Certification Board (BRE Global Limited).

Documents

DocumentTypeSizeDownload
s quad sensor and sensor sounder vad brochure data sheetDatasheet453 KBDownload PDF
Gent 4188-1073 issue 7 - S-Quad data and installation (white and black)Installation7.2 MBDownload PDF

Optional accessories

FAQs

What visual alarm coverage does S4-711-VAD-HPR provide?

At High, the S4-711-VAD-HPR gives C-3-14 ceiling coverage, equal to 461.8 m³. Medium gives C-3-13 and Low gives C-3-10. The open categories are O-4.5-14 at High and O-4-13 at Medium. In a C rating, the two numbers give the maximum ceiling height and coverage diameter, both in metres; the covered space is cylindrical. Use a two-second flash interval and the S4-701 base with its IP seal plate. Coverage changes with the selected power setting.

Does S4-711-VAD-HPR include a voice sounder?

The S4-711-VAD-HPR combines dual optical and heat sensing with a red High Power visual alarm. It has no sounder or speech output. Its optical channels use forward and backward scatter, while the heat channel provides temperature sensing. The red VAD provides the visual warning and flashes every two seconds in its EN 54-23 setting. S4-711-V-VAD-HPR adds a voice sounder to dual optical and heat detection with a red High Power VAD. Both models have a built-in loop isolator.

How does S4-711-VAD-HPR operate on Nano?

The S4-711-VAD-HPR works on a Nano loop, where its VAD is fixed at Low. Its ceiling coverage on Nano is C-3-10. The High and Medium visual alarm settings are therefore unavailable on Nano. Its dual optical and heat sensing remain part of the device. Configure the Nano system with Nano Commissioning Tool v3.0 or later. Use the S4-701 base and IP seal plate, and keep the visual alarm flash interval at two seconds.

Which mounting parts does S4-711-VAD-HPR use?

Use the S4-701 base and its IP seal plate with the S4-711-VAD-HPR to achieve IP21C. The S4-701 is the IP21 base kit and includes the plate. S-Quad VAD installations require an IP21 mounting plate for EN 54-23 operation. The S-Quad range also includes the S4-705 plate pack, containing five plates. The detector uses a ceiling position for its red visual alarm; the selected power setting determines its coverage height and diameter. Its loop connection supplies power to the head.

How are S4-711-VAD-HPR alarm outputs set up and synchronised?

The S4-711-VAD-HPR visual alarm synchronises with compatible devices across all loops belonging to the same panel. Synchronisation does not extend across a network of panels. The red VAD uses a two-second flash interval for EN 54-23 operation. This model provides a visual warning without a sounder or spoken message. On Nano, this VAD operates at Low with C-3-10 ceiling coverage. Fit the S4-701 base and IP seal plate for IP21C.