Gent S4 Dual Optical Heat Sensor Voice Sounder

Part no.S4-711-V
BrandGent
RangeS4 Detectors
Sub-rangeDetectors with Voice Sounder
Gent by Honeywell S4-711-V S4 Dual Optical Heat Sensor Voice Sounder — white circular device with central clear lens

Image for illustration; item supplied may differ

At a glance

  • Dual optical detection and heatForward and backward optical sensing combine with heat detection in one head.
  • Spoken alarm messagesFour English speech messages and a bell tone support alarm, alert and test signals.
  • Loop powered with isolatorThe loop supplies the device, which includes a short-circuit isolator.
  • S4-700 mounting baseFits the standard base and supports the optional S4-FLUSH semi-flush kit.
  • Synchronisation within one panelSound outputs synchronise across its loops; synchronisation does not cross a panel network.
  • Three Gent panel familiesThe S-Quad range works with Vigilon Plus, Compact Plus and Nano panels.

Description

The Gent S4-711-V is an S-Quad dual optical and heat sensor with a voice sounder for Vigilon Plus, Compact Plus and Nano. It combines smoke and heat detection with spoken fire warnings in one head. Four stored English messages and a bell tone provide alarm, alert and test signals. Each speech signal starts with an attention tone, then plays its message. The device takes power from the loop and has a built-in short-circuit isolator. It fits the S4-700 base, with an optional S4-FLUSH kit for semi-flush mounting. This model has no VAD. Its sound outputs synchronise across all loops of one panel.

S4-711-V combines forward and backward optical smoke sensing with heat. The panel selects the detection state. States 2, 6, 11 and 12 do not meet EN 54-7; the selected state must match the required smoke and heat response.

Read the full technical description

S4-711-V combines forward and backward optical smoke sensing with heat. The panel selects the detection state. States 2, 6, 11 and 12 do not meet EN 54-7; the selected state must match the required smoke and heat response.

Four English speech messages cover emergency evacuation, an incident alert, a system test and fire evacuation, with a bell tone available as well. Audio storage is up to 20 seconds, with additional local attention tones. Speech follows an attention tone, and pauses before and after the message can be programmed. Fault monitoring checks the speech circuit without playing a test sound.

The sounder provides intermittent, alternating and continuous tone signals. Sound outputs synchronise across all loops of one panel; that timing does not extend across a network of panels. This model provides an audible warning without a visual alarm.

Supplied with one sensor head and one blue protective dust cover. The mounting base is not included. The S4-700 standard base supports this detector, with the S4-FLUSH kit available for semi-flush installation. Across the S-Quad range, the head is 117 mm in diameter and 49.6 mm high, increasing to 63.8 mm high on the standard base. The range uses an ABS enclosure and a 35-48 V loop supply.

Use Vigilon Commissioning Tool v1.32 or later for device setting changes, or Nano Commissioning Tool v3.0 or later for Nano configuration. Verify the system design with the Gent Battery Standby and Loop Load calculator. The S-Quad programmable connection can operate as a monitored input or an unmonitored output, with a maximum 15 m run to the external I/O unit.

Specifications

Sensor typeDual optical and heat
Power sourceLoop powered
Loop isolatorBuilt-in short-circuit isolator
Panel families (S-Quad)Vigilon Plus, Compact Plus and Nano
Operating voltage (S-Quad)35-48 V
Enclosure (S-Quad)ABS
Body colour (S-Quad white models)White, RAL 9010
Head dimensions (S-Quad)117 mm diameter × 49.6 mm height
Operating temperature (S-Quad)-10°C to +50°C
Storage temperature (S-Quad)-20°C to +70°C
Relative humidity (S-Quad)95%, non-condensing, at +5°C to +45°C
Mounting baseS4-700
Voice outputStored speech and attention tones
Audio storageUp to 20 seconds; additional local attention tones
Factory audioFour English speech messages and a bell tone
Visual alarmNone
Semi-flush mounting kitS4-FLUSH
Height on standard base (S-Quad)63.8 mm
Programmable I/O (S-Quad)Monitored input or unmonitored output
External I/O cable limit (S-Quad)15 m from base to external I/O unit
Fire indication (S-Quad)Red LED
Speech monitoringSilent fault monitoring

Specifications per manufacturer documentation, subject to change. E&OE.

Standards and approvals

StandardWhat it covers
LPCB approvedApproved by the Loss Prevention Certification Board for fire detection and alarm system products.
EN 54-5:2000 + A1:2002
EN 54-7:2000 + A1:2002 + A2:2006
EN 54-17:2005 + AC:2007
EN 54-18:2005 + AC:2007
LPCB ref 042ca/01

Approval body: Loss Prevention Certification Board (BRE Global Limited).

Documents

DocumentTypeSizeDownload
Gent 4188-1073 issue 7 - S-Quad data and installation (white and black)Installation7.2 MBDownload PDF

Optional accessories

FAQs

Does S4-711-V have a visual alarm?

The S4-711-V combines dual optical smoke and heat sensing with a voice sounder. It has no visual alarm device. Its audible warning can use stored speech preceded by an attention tone, with four English messages and a bell tone supplied as the factory audio set. The detector takes its power from the loop and includes a short-circuit isolator. It fits the S4-700 standard base, and the optional S4-FLUSH kit provides a semi-flush mounting arrangement for this model.

Which messages does S4-711-V provide?

The S4-711-V provides four English speech messages plus a bell tone. The messages cover emergency evacuation, an incident alert asking people to wait, a test requiring no action, and fire evacuation. An attention tone plays before the message. Audio storage is up to 20 seconds, with additional local attention tones. The factory speech can be changed to custom messages, and pauses can be set before and after speech. Silent monitoring checks for failure of the speech function.

Which base fits S4-711-V?

The S4-711-V fits the S4-700 standard base. It can also use the S4-FLUSH semi-flush mounting kit with that base. Across the S-Quad range, the head measures 117 mm in diameter and 49.6 mm high, with the standard base increasing the height to 63.8 mm. The range uses an ABS enclosure, and this model has a white body. Power comes from the loop at 35-48 V. Its integrated short-circuit isolator forms part of the detector assembly.

Which sensing options does S4-711-V offer?

The S4-711-V uses forward and backward optical smoke sensing together with a heat channel. The panel selects the sensor state to set the detection response. The available states are 0, 2, 3, 4, 5, 6, 7, 8, 11 and 12, with state 0 as the default. States 2, 6, 11 and 12 do not meet EN 54-7. This model also provides spoken alarm messages and tone signals from its integral voice sounder, with a red LED for fire indication.

Does S4-711-V synchronise across different loops?

The S4-711-V sound outputs synchronise with compatible devices across all loops of the same panel. That synchronisation does not extend across a network of panels. The device works with Vigilon Plus, Compact Plus and Nano systems, combining dual optical and heat detection with stored speech and attention tones. Use Vigilon Commissioning Tool v1.32 or later when changing its settings on a Vigilon system, or Nano Commissioning Tool v3.0 or later for Nano configuration. Verify the design with the Gent loop load calculator.