We supply Gent VAD and S4M sounder devices for ceiling mounting. We offer three S-Quad S4M alarm options for specifiers and installers.
The Gent S4M sounder, S4M-S, provides audible warning. S4M-VAD-LPR provides a Standard Power red visual alarm. S4M-V-VAD-LPR combines a voice sounder with a Standard Power red VAD. Each device has a white housing. All three take power from the panel loop. Each fits the S4-700 mounting base. Choose the alarm function to match the warning needed at each ceiling position.
We supply Vigilon Plus, Compact Plus and Nano fire alarm panels from Gent by Honeywell. S4M support on Vigilon and Vigilon Compact requires EN 54 loop cards. Legacy loop cards do not support these devices. Controller software must be version 4.64 or later. Loop card software must be version 4.58 or later. Commissioning uses the Vigilon tool at version 1.40 or later. All three S4M devices operate from a 35–48V loop supply. Each head measures 117mm in diameter and 63mm high. The voice model plays an attention tone before its spoken message. Its red VAD provides visual warning at the same position. We supply this combined device as S4M-V-VAD-LPR.
For a Gent visual alarm device alongside separate audible warning, choose the visual-only model. S4M-S suits a position requiring sound alone. Choose S4M-V-VAD-LPR when the specification needs speech and visual warning together. Custom messages on the voice model use the S4T-BASE-PROGRAM programmer. We supply this programmer through S4 Bases & Accessories. We also supply the S4-700 mounting base through that range. The 805576 label plate carries device location details. For detection devices, browse S4 Detectors. Our S3 Sounders & VADs range contains S-Cubed alarm devices.
Related products
Frequently asked questions
- Which Gent addressable VAD in this range provides visual warning only?
- S4M-VAD-LPR provides visual warning only. Its Standard Power VAD emits red light from a white housing. It fits the S4-700 mounting base. The device takes power from a 35–48V panel loop. Choose it for ceiling positions where the specification calls for visual warning alongside a separate audible alarm. We supply this Gent addressable VAD as the visual-only option in our S4M range.
- Which model combines spoken messages with a red VAD?
- S4M-V-VAD-LPR combines a voice sounder with a Standard Power red VAD. It plays an attention tone before each spoken message. The same ceiling-mounted head provides both alarm functions. It takes its power from a 35–48V panel loop. It fits the S4-700 mounting base. Custom messages use the S4T-BASE-PROGRAM programmer. We supply S4M-V-VAD-LPR for positions requiring speech and visual warning together.
- What does the S4M-S sounder provide?
- S4M-S is a ceiling-mounted sounder for audible fire alarm signals. The head measures 117mm in diameter and 63mm high. It has a white RAL 9010 housing. Its operating voltage is 35–48V from the panel loop. The head fits the S4-700 mounting base. Choose it where the specification calls for sound alone. We supply S4M-S as the sounder-only option in this range.
- Which base fits the S4M alarm devices?
- The S4-700 mounting base fits all three S4M devices on this page. This includes S4M-S and both VAD models. It provides the panel loop connection for the alarm head. The optional 805576 label plate carries device location details at the base. These label plates come in packs of ten. We supply the base and label plates through S4 Bases & Accessories.
- Can the voice model use custom messages?
- Yes, S4M-V-VAD-LPR supports custom messages through the S4T-BASE-PROGRAM programmer. This allows its factory speech messages to be replaced. The voice sounder plays an attention tone before the spoken message. Its Standard Power red VAD provides visual warning at the same position. The head uses the S4-700 mounting base. We supply the S4T-BASE-PROGRAM as a separate item in S4 Bases & Accessories.