Gent S4M Sounder only
| Part no. | S4M-S |
|---|---|
| Brand | Gent |
| Range | S4 Audio & Visual Only |
| Sub-range | Sounder Only |

Image for illustration; item supplied may differ
At a glance
- Sounder-only alarm headThe S4M-S provides audible warning within the S-Quad S4M AV range.
- S4-700 base fitThe head fits the S4-700 mounting base.
- Loop powered S4M rangeS4M heads receive power through their connection to the fire alarm loop.
- S4M sounder controlsThe S4M sounder range provides adjustable volume and soft start.
- Current commissioning requirementsUse MCC/MCB 4.64 or later, LPC 4.58 or later and commissioning tool 1.40 or later.
- S4M AV head sizeThe AV range head measures 117mm in diameter and 63mm in height.
Description
The Gent S4M-S is a sounder-only head for ceiling mounted fire alarm warning where detection is provided separately. It fits the S4-700 base and takes power from the loop. The S-Quad S4M AV range works with Vigilon and Vigilon Compact systems fitted with current EN54 loop cards. The S4M sounder range provides adjustable volume and a gradual start to the alarm sound. The white head is supplied with an orange dust cover. It needs controller software 4.64 or later, loop software 4.58 or later and commissioning tool 1.40 or later. The AV range head measures 117mm across and 63mm high.
The S4M-S provides sounder output as the sounder-only member of the S-Quad S4M AV range. The AV range provides fire alarm warning without smoke or heat detection. S4M-S carries the S function marking. The white head is supplied with an orange dust cover.
Read the full technical description
The S4M-S provides sounder output as the sounder-only member of the S-Quad S4M AV range. The AV range provides fire alarm warning without smoke or heat detection. S4M-S carries the S function marking. The white head is supplied with an orange dust cover.
The S4M sounder range has an average output of 85dBA at 1m, or 75dBA at 3m at a bedhead. Volume can be adjusted at the device, and soft start increases the sound gradually to its set level. The range monitors its sounder function for failure.
The S4M range plugs into the S4-700 base, mounted on a metal back box with earth continuity maintained around the loop. Loop wiring uses screened two-core fire-rated cable with conductors from 1.5mm² to 2.5mm². The base provides the connection between the head and the panel loop.
The S4M range works with Vigilon and Vigilon Compact systems fitted with current EN54 loop cards. These AV-only models need MCC/MCB software 4.64 or later, LPC software 4.58 or later and commissioning tool 1.40 or later. S4M outputs need a sector assignment and their output functions configured during commissioning.
The S4M AV range has a white RAL 9010 housing, a head diameter of 117mm and a head height of 63mm. S4M environmental limits are IP21C, -10°C to +50°C in operation and -20°C to +70°C in storage, with up to 95% non-condensing relative humidity at +5°C to +45°C. The Battery Standby and Loop Load calculator is used to establish loop loading, cable length and standby requirements.
Specifications
| Alarm function | Sounder only |
|---|---|
| Function marking | S |
| Power source | Loop powered |
| Product range | Gent S-Quad S4M AV |
| Mounting | Ceiling, in an S4-700 base |
| Mounting base | S4-700 |
| S4M AV range head diameter | 117mm |
| S4M AV range head height | 63mm |
| S4M range operating voltage | 35-48V |
| S4M range outer housing | Terluran GP-35 ABS |
| S4M AV range finish | White, RAL 9010 |
| S4M range ingress protection | IP21C |
| S4M range operating temperature | -10°C to +50°C |
|---|---|
| S4M range storage temperature | -20°C to +70°C |
| S4M range relative humidity | Up to 95%, non-condensing at +5°C to +45°C |
| S4M range panel families | Vigilon and Vigilon Compact with current EN54 loop cards |
| Minimum MCC/MCB software | 4.64 |
| Minimum LPC software | 4.58 |
| Minimum commissioning tool | 1.40 |
| S4M range base support | Metal back box |
| S4M range loop cable | Screened two-core fire-rated cable, 1.5-2.5mm² |
| S4M sounder range average output | 85dBA at 1m; 75dBA at 3m at a bedhead |
| Supplied items | White sounder head and orange dust cover |
Specifications per manufacturer documentation, subject to change. E&OE.
Optional accessories
- S4-705IP21 base covers (pack 5)S4-705 White IP21C Plate£11.37ex VAT£13.64 inc VATIn stock
- 805580S-Quad Removal Tool Kit805580 Removal tool kit (supplied with Dust Cover Remover part)£327.18ex VAT£392.62 inc VATIn stock
- 805576S-Quad Base Label Plate (pack of 10)805576 Label plate (10 pack)£8.28ex VAT£9.94 inc VATIn stock
- S4T-BASE-PROGRAMProgrammer Base for S4/T/M and S3 Voice Sounderscompatible / works with: Programmer Base for S4/T/M and S3 Voice Sounders£230.83ex VAT£277.00 inc VATIn stock
FAQs
What does the S4M-S do?
The S4M-S is the sounder-only member of the S-Quad S4M AV range. It provides audible fire alarm warning and fits the S4-700 base at the ceiling. The AV range has no smoke or heat detection function. Within the same family, S4M-VAD-LPR is the Standard Power red visual alarm model, while S4M-V-VAD-LPR combines voice sounder output with a Standard Power red visual alarm. S4M-S is identified by the S marking for its sounder function.
How is the S4M sounder output controlled?
Within the S4M sounder range, volume can be set at each device and soft start raises the sound gradually to the chosen level. The range has an average output of 85dBA at 1m, or 75dBA at 3m at a bedhead. Its sounder function is monitored for failure. The S4M-S supplies the sounder-only alarm function in this family, with the output configured during commissioning and the device assigned to a sector in the fire alarm system.
What is supplied, and how is the S4M-S mounted?
The S4M-S is supplied as a white sounder head with an orange dust cover and fits the S4-700 base for ceiling mounting. Across the S4M range, the base is mounted on a metal back box with earth continuity maintained around the loop. The loop uses screened two-core fire-rated cable with conductors between 1.5mm² and 2.5mm². The base connects the head to the panel loop. The optional 805576 label plate carries location information at the base.
What software is needed to commission the S4M-S?
The S4M-S needs controller software 4.64 or later on the MCC or MCB, loop software 4.58 or later on the LPC and commissioning tool 1.40 or later. The S4M range operates with Vigilon and Vigilon Compact systems fitted with current EN54 loop cards. During setup, S4M output devices need a sector assignment and their output functions configured. For the S4M-S, the alarm function is sounder output. Loop loading and battery standby are calculated as part of the system design.
How is the S4M-S included in loop design?
Include the S4M-S in the Battery Standby and Loop Load calculator with the other devices on its loop. S4M loop design covers loading, cable length and the control panel's standby requirement. The range takes power from a 35-48V loop through its mounting bases. Its operating environment is -10°C to +50°C, with up to 95% non-condensing relative humidity over +5°C to +45°C. The S4M AV head is 117mm in diameter and 63mm high.