Skip to content

Trade prices shown ex VAT. Order by 3pm for same-day dispatch on stocked lines, UK mainland. Free UK delivery on orders over £250 ex VAT.

Part Number or the Week S3EP-V-VAD-HPR-R

Gent S4M Voice Sounder Low Power C Class VAD Red.

Part no.S4M-V-VAD-LPR
BrandGent
RangeS4 Audio & Visual Only
Sub-rangeVoice Sounder & VAD
Gent S4M-V-VAD-LPR Voice Sounder + Low Power Red VAD — white ceiling unit with clear lens and red LED

Image for illustration; item supplied may differ

At a glance

  • Voice sounder and red VADThe S4M-V-VAD-LPR combines voice sounder output with a Standard Power red visual alarm.
  • S4-700 base fitThe combined AV head fits the S4-700 mounting base.
  • S4M speech sequenceThe S4M speech range pairs an attention tone with a voice message.
  • S4M Standard Power VAD coverageThe Standard Power VAD range provides C-3-10 coverage with a two-second flash interval.
  • Loop powered S4M rangeThe range receives power through the bases connected to the fire alarm loop.
  • Current commissioning requirementsUse MCC/MCB 4.64 or later, LPC 4.58 or later and commissioning tool 1.40 or later.

Description

The Gent S4M-V-VAD-LPR combines a voice sounder and a Standard Power red visual alarm in one ceiling mounted head. It fits the S4-700 base and takes power from the loop. The S-Quad S4M AV range provides alarm warning without smoke or heat detection and works with Vigilon and Vigilon Compact systems fitted with current EN54 loop cards. In the S4M speech range, an attention tone precedes a voice message. The white head is supplied with an orange dust cover. It needs controller software 4.64 or later, loop software 4.58 or later and commissioning tool 1.40 or later. Its marking is V/RVAD/LP.

The S4M-V-VAD-LPR combines voice sounder output with a Standard Power red VAD. It carries the V/RVAD/LP function marking and belongs to the S-Quad S4M AV range, which provides alarm warning without smoke or heat detection. The white head is supplied with an orange dust cover.

Read the full technical description

The S4M-V-VAD-LPR combines voice sounder output with a Standard Power red VAD. It carries the V/RVAD/LP function marking and belongs to the S-Quad S4M AV range, which provides alarm warning without smoke or heat detection. The white head is supplied with an orange dust cover.

In the S4M speech range, an attention tone precedes the voice message. Speech messages can be reprogrammed. The sounder range provides adjustable volume and soft start, with an average output of 85dBA at 1m or 75dBA at 3m at a bedhead. The S4M speech and sounder functions are monitored for failure.

The S4M Standard Power VAD range covers a C-3-10 cylinder: up to 3m mounting height, 10m diameter and 235.6m³ volume. A two-second flash interval is used for EN54-23 coverage in the S4M VAD range.

The S4M range plugs into the S4-700 base, mounted on a metal back box with earth continuity maintained around the loop. Loop wiring uses screened two-core fire-rated cable with conductors from 1.5mm² to 2.5mm². The base provides the connection between the head and the panel loop.

The S4M range works with Vigilon and Vigilon Compact systems fitted with current EN54 loop cards. These AV-only models need MCC/MCB software 4.64 or later, LPC software 4.58 or later and commissioning tool 1.40 or later. S4M outputs need a sector assignment and their output functions configured during commissioning. Use the Battery Standby and Loop Load calculator for loop loading, cable length and standby requirements.

The S4M AV range has a white RAL 9010 housing, a head diameter of 117mm and a head height of 63mm. S4M environmental limits are IP21C, -10°C to +50°C in operation and -20°C to +70°C in storage, with up to 95% non-condensing relative humidity at +5°C to +45°C.

Specifications

Alarm functionVoice sounder and Standard Power red VAD
Function markingV/RVAD/LP
Power sourceLoop powered
Product rangeGent S-Quad S4M AV
MountingCeiling, in an S4-700 base
Mounting baseS4-700
S4M AV range head diameter117mm
S4M AV range head height63mm
S4M range operating voltage35-48V
S4M range outer housingTerluran GP-35 ABS
S4M AV range finishWhite, RAL 9010
S4M range ingress protectionIP21C
S4M range operating temperature-10°C to +50°C
S4M range storage temperature-20°C to +70°C
S4M range relative humidityUp to 95%, non-condensing at +5°C to +45°C
S4M range panel familiesVigilon and Vigilon Compact with current EN54 loop cards
Minimum MCC/MCB software4.64
Minimum LPC software4.58
Minimum commissioning tool1.40
S4M range base supportMetal back box
S4M range loop cableScreened two-core fire-rated cable, 1.5-2.5mm²
S4M sounder range average output85dBA at 1m; 75dBA at 3m at a bedhead
S4M Standard Power VAD range coverageC-3-10 at a two-second flash interval
S4M Standard Power VAD range volume235.6m³ cylindrical volume
S4M Standard Power VAD range geometryMaximum 3m mounting height; 10m diameter
Supplied itemsWhite voice sounder and red VAD head; orange dust cover

Specifications per manufacturer documentation, subject to change. E&OE.

Optional accessories

FAQs

What functions does the S4M-V-VAD-LPR combine?

The S4M-V-VAD-LPR combines a voice sounder with a Standard Power red VAD in one ceiling mounted head. Its function marking is V/RVAD/LP. It belongs to the S-Quad S4M AV range, which provides fire alarm warning without smoke or heat detection. Within this family, S4M-S is sounder only and S4M-VAD-LPR is VAD only. The combined model fits the S4-700 base and takes power from the loop, with its alarm output functions configured during commissioning.

Can the voice messages be changed?

The S4M speech range supports replacement of its factory messages, and each speech output pairs an attention tone with a message. Custom recordings are loaded into S4M voice sounders using the S4T-BASE-PROGRAM programmer base. This is an accessory for custom-message programming. The S4M-V-VAD-LPR combines that voice sounder identity with a Standard Power red visual alarm and uses the S4-700 as its installed mounting base. Commissioning requires tool 1.40 or later, alongside the required controller and loop software.

What visual coverage does the Standard Power S4M range provide?

The S4M Standard Power VAD range has C-3-10 coverage, describing a cylinder up to 3m high and 10m in diameter, with a volume of 235.6m³. The S4M VAD range uses a two-second flash interval for EN54-23 coverage. The S4M-V-VAD-LPR combines its Standard Power red VAD with voice sounder output in the same ceiling head. Its required software is MCC/MCB 4.64 or later, LPC 4.58 or later and commissioning tool 1.40 or later.

What is supplied, and how is the S4M-V-VAD-LPR mounted?

The S4M-V-VAD-LPR is supplied as a white voice sounder and red VAD head with an orange dust cover. It fits the S4-700 base for ceiling mounting. Across the S4M range, the base is mounted on a metal back box with earth continuity maintained around the loop. The loop uses screened two-core fire-rated cable with conductors between 1.5mm² and 2.5mm². The base connects the head to the panel loop. The optional 805576 label plate carries location information at the base.

How is the combined S4M voice and VAD head commissioned?

The S4M-V-VAD-LPR needs controller software 4.64 or later on the MCC or MCB, LPC software 4.58 or later and commissioning tool 1.40 or later. The S4M range operates with Vigilon and Vigilon Compact systems fitted with current EN54 loop cards. S4M output devices need a sector assignment and their output functions set during commissioning. This model has both voice sounder and Standard Power red visual alarm functions. Use the Battery Standby and Loop Load calculator to establish loop loading and battery standby.