Gent Remote LED for ES Detect
| Part no. | 781814 |
|---|---|
| Brand | Gent |
| Range | Conventional Audio Visual Devices |
| Sub-range | Remote LED Indicator |

Image for illustration; item supplied may differ
At a glance
- Remote alarm indicationRepeats an ES Detect detector alarm at a separate position.
- Three red LEDsA red lens is illuminated by three red LEDs.
- 180-degree viewThe illuminated indicator has a viewing angle of 180 degrees.
- Two-wire base connectionWith the 805590-D, X1 positive connects to LED EP6 and X1 negative to EM2.
- Compact rectangular bodyThe enclosure measures 85mm wide × 82mm high × 27mm deep.
- IP42 enclosureWhite ABS enclosure with an ambient temperature range of -25°C to +70°C.
Description
The Gent 781814 is a remote LED indicator that repeats an ES Detect detector alarm at a separate position. Its red lens is lit by three red LEDs and has a viewing angle of 180 degrees. On ES Detect circuits the light flashes when activated. The flash rate is about 1Hz. It connects to the detector base with two separate wires; with the 805590-D, these run to the LED EP6 and EM2 terminals. The white ABS housing is 85mm wide, 82mm high and 27mm deep. It operates from 1.8 to 3V DC and draws about 9mA. The ambient temperature range is -25°C to +70°C, with IP42 protection for the indicator.
The 781814 repeats the alarm from an ES Detect detector through three red LEDs behind a red lens. Its viewing angle is 180 degrees. On an ES Detect circuit, the indicator flashes at approximately 1Hz when activated.
Read the full technical description
The 781814 repeats the alarm from an ES Detect detector through three red LEDs behind a red lens. Its viewing angle is 180 degrees. On an ES Detect circuit, the indicator flashes at approximately 1Hz when activated.
Two wires connect the indicator to the detector base. With an 805590-D, X1 positive connects to LED EP6 and X1 negative connects to EM2. The base carries the conventional zone connections for the detector. The indicator operates from 1.8 to 3V DC and its current consumption is approximately 9mA.
The enclosure is white ABS plastic, similar to RAL 9010, and measures 85mm wide by 82mm high by 27mm deep. It is rated IP42, with an ambient temperature range of -25°C to +70°C and a storage range of -35°C to +85°C.
The 805590-D installation supports the 800171 fixed heat detector, 800177 Class B fixed heat detector, 800271 rate-of-rise heat detector and 800371 optical smoke detector with remote alarm indication. The 781814 is an optional indicator connected through the base.
Specifications
| Device type | Remote alarm LED indicator |
|---|---|
| Alarm display | Three red LEDs behind a red lens |
| Viewing angle | 180° |
| Connection | Two wires to detector base |
| Operating voltage | 1.8-3V DC |
| Current consumption | Approximately 9mA |
| Ambient temperature | -25°C to +70°C |
| Storage temperature | -35°C to +85°C |
|---|---|
| Housing | ABS plastic |
| Colour | White, similar to RAL 9010 |
| Dimensions | 85mm wide × 82mm high × 27mm deep |
| Ingress protection | IP42 |
| Diode base connection | 805590-D: X1 positive to LED EP6; X1 negative to EM2 |
| Supply contents | One remote indicator with red lens |
Specifications per manufacturer documentation, subject to change. E&OE.
Documents
| Document | Type | Size | Download |
|---|---|---|---|
| Installation manual (781814, 805590-D) | Installation | 863 KB | Download PDF |
Optional accessories
- 805590-DDetector Base With DiodeUsed with the Base (805590-D) for the ES Detect range of conventional fire detectors£6.16ex VAT£7.39 inc VATIn stock
- 805590Detector Base. Can be used for ES Conventional and Intrinsically safe detection.Used with the Base (805590-D) for the ES Detect range of conventional fire detectors£5.98ex VAT£7.18 inc VATIn stock
- 13270-08LBGent 8 Zone conventional panel, EN54 less batteriesES Detect range is only approved to be installed with Xenex Control Panels - 13270-02LB, 1£339.66ex VAT£407.59 inc VATIn stock
- 13270-02LB2 Zone conventional panel, EN54 less batteriesES Detect range is only approved to be installed with Xenex Control Panels - 13270-02LB, 1£196.14ex VAT£235.37 inc VATIn stock
- 13270-04LBGent 4 Zone conventional panel, EN54 less batteriesES Detect range is only approved to be installed with Xenex Control Panels - 13270-02LB, 1£263.72ex VAT£316.46 inc VATIn stock
- S4-34440-02Mains Powered Interface - max o/p power 1.5A. Batteries not included - requires 2 x 4015-502-YFR (Power Sonic Flame Retardant 12V 2.1Ah) to meet compliance regulations.Can be wired to a Mains interface unit installed in a Vigilon or SENTRI fire panel based s£461.66ex VAT£553.99 inc VATIn stock
- S4-34440-12Mains Powered Interface - max o/p power 2.5A. Batteries not included - requires 2 x 4015-514-YFR (Power Sonic Flame Retardant 12V 12Ah) to meet compliance regulations.Can be wired to a Mains interface unit installed in a Vigilon or SENTRI fire panel based s£577.67ex VAT£693.20 inc VATIn stock
- S4-344504 Channel Interface (input/output) (no enclosure)Can be wired to an LV interface unit installed in a Vigilon or SENTRI fire panel based sys£163.85ex VAT£196.62 inc VATIn stock
+ 5 moreShow fewer
- S4-34410Single Channel Interface, LV Input only (no enclosure)Can be wired to an LV interface unit installed in a Vigilon or SENTRI fire panel based sys£58.01ex VAT£69.61 inc VATIn stock
- 800171Fixed Heat DetectorCompatible fire detectors (ES Detect range): 800171 Fixed Heat detector, 800177 Fixed Heat£20.46ex VAT£24.55 inc VATIn stock
- 800177Fixed Heat Detector Class BCompatible fire detectors (ES Detect range): 800171 Fixed Heat detector, 800177 Fixed Heat£31.70ex VAT£38.04 inc VATIn stock
- 800271Rate of Rise Heat DetectorCompatible fire detectors (ES Detect range): 800171 Fixed Heat detector, 800177 Fixed Heat£21.05ex VAT£25.26 inc VATIn stock
- 800371Optical Smoke DetectorCompatible fire detectors (ES Detect range): 800171 Fixed Heat detector, 800177 Fixed Heat£20.99ex VAT£25.19 inc VATIn stock
FAQs
What does the 781814 show on an ES Detect installation?
The 781814 repeats the connected detector alarm at a separate position. It has three red LEDs behind a red lens, with a viewing angle of 180 degrees. On an ES Detect circuit, the indicator flashes at approximately 1Hz when activated. Two wires link it to the detector base. With the 805590-D base, the detector can be an 800171 fixed heat, 800177 Class B fixed heat, 800271 rate-of-rise heat or 800371 optical smoke head.
How does the 781814 connect to the 805590-D base?
The connection uses two wires between the 781814 and the 805590-D base. The indicator X1 positive terminal connects to LED EP6 on the base, and X1 negative connects to EM2. The base carries the detector on the conventional zone circuit, while the indicator repeats its alarm at another position. The 781814 operates from 1.8 to 3V DC and consumes approximately 9mA. Its red lens contains three red LEDs, which flash when activated on an ES Detect circuit.
What are the dimensions and environmental ratings of the 781814?
The 781814 has a rectangular ABS enclosure measuring 85mm wide, 82mm high and 27mm deep. The housing is white, similar to RAL 9010, with a red indicator lens. Its ingress protection is IP42 and its ambient operating range is -25°C to +70°C. Storage temperature is -35°C to +85°C. The illuminated lens has a viewing angle of 180 degrees. A pair of wires connects the unit to the detector base so that it can repeat the alarm at a separate position.
Which ES Detect heads can use the 781814 through a diode base?
The 805590-D base supports remote indication with the 781814 for the 800171, 800177, 800271 and 800371 heads. These are the fixed heat, Class B fixed heat, rate-of-rise heat and optical smoke models respectively. The indicator connects to the base through two wires and repeats the alarm using three red LEDs. On this ES Detect application the light flashes when activated. The head fits into the base on the conventional zone circuit, with the remote indicator connected at the base.
What voltage and current apply to the 781814?
The 781814 operates from 1.8 to 3V DC and consumes approximately 9mA. Its electrical connection is through two wires to the detector base. With the 805590-D, the positive indicator connection is LED EP6 and the negative connection is EM2. The red lens contains three red LEDs and flashes at approximately 1Hz on an ES Detect installation. The indicator itself has an IP42 ABS housing and an ambient operating temperature range extending from -25°C to +70°C.