Part Number or the Week S3EP-V-VAD-HPR-R

Gent Single Channel Interface, LV Input Only (No Enclosure)

Part no.S4-34410
BrandGent
RangeS4 Interfaces & Accessories
Sub-rangeLow Voltage Interfaces
Replaces34410, VSINTZM-PCB
Gent by Honeywell S4-34410 Single Channel Interface, LV Input only — beige plastic device with green terminal block

Image for illustration; item supplied may differ

£58.01 ex VAT
£69.61 inc VAT
Available to order, ships 14th October
Dates are based on our supplier's lead times and may change.
Free UK delivery over £250 ex VAT, otherwise £9.95 ex VAT (£11.94 inc VAT).

Volume pricing

Bulk discount, applied automatically at checkout.

QuantityUnit price ex VAT
1+£58.01
5+£56.27
10+£55.40
20+£54.53

Don't forget

At a glance

  • Monitored fire, fault or supervisory inputThe input on terminals 6 and 5 works on either normally open or normally closed contacts and can be programmed as a fire, fault or supervisory (non fire) input. It is wired with a 10K resistor in series with the contacts plus a 10K end-of-line resistor over a run of up to 300 metres, and short and open circuit faults are detected in every input mode.
  • Acceptance delay to ride out contact bounceThe input can be set to accept a signal only once it has stayed active for a set period, up to 10 seconds on a fire input and up to 300 seconds on a fault or supervisory input. The delay is set during commissioning and is the usual answer to a contact that chatters.
  • Conventional zone on the same inputThe same input can be configured as a zone input for conventional detectors and manual call points, every call point carrying a 470 Ohm resistor or a 3V9 zener diode in series with its normally open contacts, the zone taking up to 2mA quiescent and 9mA in alarm at 24V nominal over a run of up to 100 metres and terminating in the supplied end-of-line capacitor unit.
  • Input only, with no outputThis interface has no relay or LED output and no confirmation function. It monitors clean contacts or a conventional zone. Where an output or confirmation function is needed, the S4-34420 provides one input and one relay output, and the S4-34450 provides four configurable channels.
  • Loop powered, for Vigilon and 34000 panelsIt takes its power and its communications from the loop, includes a loop isolator for device isolation, uses one of the 207 device addresses available on a loop and counts a load factor of 1 as a switch input. Vigilon and 34000 systems need compatible MCC/MCB and LPC firmware, and the interface is commissioned with the Commissioning Tool software version 1.21 or greater.
  • Supplied without an enclosureSupplied with the standard S4 interface spares pack. The interface is about 92g and 93 x 90 x 23mm; the M200E-SMB surface box, S4-34492 metal box, S4-34496 six-way enclosure, S4-34490 plastic box and S4-34491 DIN rail brackets are separate order codes.

Description

The Gent S4-34410 is the single input low voltage interface for Vigilon and 34000 fire alarm systems. Its one monitored input can be programmed as a fire, fault or supervisory input on either normally open or normally closed contacts, letting the fire alarm system take a signal from plant or another system through a clean pair of contacts, or set as a zone input for conventional detectors and manual call points. Short and open circuit faults are detected in every input mode. The interface takes its power and its address from the loop and includes a loop isolator. It has no output. Supplied with the standard S4 interface spares pack, without an enclosure.

The S4-34410 monitors one input circuit on terminals 6 and 5. It accepts normally open or normally closed clean contacts with a 10K series resistor and a 10K end-of-line resistor over up to 300 metres. The channel can be configured as fire, fault or supervisory. Acceptance delays allow the input to remain active for a chosen period before it is accepted: up to 10 seconds for fire, or up to 300 seconds for fault and supervisory inputs. The interface detects open and short circuit faults in every input mode.

Read the full technical description

The input can also connect a zone of conventional detectors and manual call points to the addressable loop. Every manual call point on that zone needs a 470 Ohm resistor or a 3V9 zener diode in series with its normally open contacts. The zone carries a load of up to 2mA quiescent and 9mA in alarm at 24V nominal, with a minimum operating voltage of 18V, over a run of up to 100 metres, and the circuit is terminated with the supplied end-of-line capacitor unit. The S4 LV range has a load factor of 26 for a zone-input configuration, with a maximum of 30 per loop. Zone input is supported on all compatible Gent addressable panels, Nano included.

The S4-34410 has no relay or LED output and no confirmation function. It monitors a contact or a conventional zone. Where a relay output is needed, the S4-34420 combines one input with a single-pole changeover relay rated 1A at 30V ac/dc into a resistive load. The S4-34450 provides any combination of up to four inputs or outputs.

Within the S4 LV trio, interfaces configured as switch inputs have a load factor of 1, with a maximum of 200 per loop. Like every interface in the S4 low voltage range it is loop powered, includes a loop isolator for device isolation, and uses one of the 207 device addresses available on a loop, responding to regular polls from the control panel with its device type and the status, open, normal or short, of its supervised input circuit. The loop connects at terminals 4 to 1. The loop cable screen must be carried through each interface, and the loop and switch input cable screens, where used, must connect to an earth terminal.

For Vigilon and 34000 systems, compatible firmware pairs are LPC V3.93 with MCC/MCB V3.94, or LPC V4.35 with MCC/MCB V4.37. Configuration is done with the Commissioning Tool software, version 1.21 or greater, where the channel is set to unused, to a fire, fault or supervisory input, or to a zone input, along with any acceptance delay.

The interface comes with its plug-in terminal blocks and the standard S4 interface spares pack. The white interface measures 93 x 90 x 23mm and weighs about 92g without an enclosure. The M200E-SMB surface mounting box, formerly S4-34493, suits a single interface. The S4-34492 small metal box has 20mm and 25mm knockouts, and the S4-34496 houses six interfaces together. S4-34491 DIN rail brackets come in packs of five for mounting inside other equipment. The interface assembly has IP31 protection in the S4-34490 plastic box. The S4 low voltage trio operates from -10°C to +60°C, with storage from -30°C to +70°C and up to 95% non-condensing relative humidity at +5°C to +45°C.

Specifications

EN 54 part / classEN 54-17:2005 + AC:2007 and EN 54-18:2005 + AC:2007
ApprovalsLPCB approved
InputFire, fault or supervisory, normally open or normally closed contacts
Input acceptance delayUp to 10s (fire); up to 300s (fault or supervisory)
Input termination10K series resistor plus 10K end-of-line resistor, supplied in the standard S4 interface spares pack
Zone inputConventional detectors and manual call points; every call point needs a 470 Ohm resistor or a 3V9 zener diode in series with its normally open contacts
Zone input load2mA quiescent; 9mA in alarm; at 24V nominal (18V minimum)
Zone terminationOne end-of-line capacitor unit supplied
Zone cable limit100m
OutputNone - input-only module
Load factor per deviceSwitch input 1; zone input 26
Loop limits (S4 LV trio)Switch input interfaces: 200 per loop; zone input configurations: 30
Weight92g interface; 1047g in plastic box; 782g in metal box
Cable limitsClean-contact input 300m
Power sourceLoop powered
Device addresses used1 of 207 per loop
Loop operating voltage (S4 LV trio)35V to 48V
Dimensions (interface)93 × 90 × 23mm
Operating temperature (S4 LV trio)−10°C to +60°C (storage −30°C to +70°C)
Relative humidity (S4 LV trio)Up to 95%, +5°C to +45°C non-condensing
Ingress protectionIP31 with plastic box S4-34490
EMC / safety (S4 LV trio)BS EN 61000-6-3:2001; BS EN 50130-4:1996 Pt 4; BS EN 60950-2002
EN 54-17 electrical (S4 LV trio)Vmax 48V; Vnom 40V; Vmin 24V; VSOmax 16V; VSOmin 8V; ICmax 0.8A; ISmax 1.25A; ILmax 50µA; ZCmax 0.2Ω
Panel compatibility (S4 LV trio)Loop card V3.93 / V4.35; main control card V3.94 / V4.37

Specifications per manufacturer documentation, subject to change. E&OE.

Standards and approvals

StandardWhat it covers
LPCB approvedApproved by the Loss Prevention Certification Board for fire detection and alarm system products.
EN 54-17:2005 + AC:2007
EN 54-18:2005 + AC:2007

Approval body: LPCB (notified body 2831).

Documents

DocumentTypeSizeDownload
Data & Installation - S4 LV Interface Modules (4188-873 issue 9)Installation4.2 MBDownload PDF
S-Quad Loop Powered Interfaces - range datasheetDatasheet200 KBDownload PDF
Declaration of Performance DoP 022 rev 2 - S4 LV interface modules (EN 54-17, EN 54-18)Certificate312 KBDownload PDF

Guides

Optional accessories

FAQs

How do you configure a Gent S4-34410?

Use the Gent Commissioning Tool, version 1.21 or later; the S4 range cannot be set up from the panel. Declare it an interface unit, choose the loop powered variant and confirm yes at the low voltage prompt. On the S4-LV page channel 1 carries the input, set as fire, fault or supervisory on normally open or normally closed contacts. Channels 2, 3 and 4 do nothing on this model and are left unused. Then save the configuration and reallocate the loop at the panel so the change takes effect.

Does the S4-34410 come with an enclosure, and which box do I need?

The interface comes with the standard S4 interface spares pack; the enclosure is separate. For a single interface the M200E-SMB surface mounting box, previously listed as S4-34493, is the cost-effective choice, while the small metal S4-34492, with 20mm and 25mm knockouts, is the one we recommend. Where several interfaces sit together the S4-34496 holds six. The large plastic S4-34490 will take one interface and gives seven usable cable entry points, and S4-34491 DIN rail brackets come in packs of five.

Does the S4-34410 need a separate power supply?

No. It is loop powered, taking both its power and its communications from the Gent loop, so there is no separate PSU, mains feed or standby battery to house. It includes a loop isolator, uses one of the 207 device addresses on a loop and, as a switch input, counts a load factor of one within a maximum of 200 devices per loop. In switch-input mode, the field wiring is the monitored contact pair, up to 300 metres, with a 10K series resistor and a 10K end-of-line resistor.

Can the S4-34410 input be set to normally closed?

Yes. The input works on either normally open or normally closed contacts, and the sense is chosen in the Commissioning Tool when the channel is set as a fire, fault or supervisory input. You cannot read it back at the panel: the Device Status view under the Info menu gives a letter per channel, I for the input and U or a dot for the unused ones, but never the contact sense. Only a configuration download shows that. Short and open circuit faults are detected in every input mode.

Can I connect a conventional zone to an S4-34410?

Yes. The input can be configured for a zone of conventional detectors and manual call points. Each call point needs a 470 ohm resistor or a 3V9 zener diode in series with its normally open contacts. The zone accepts up to 2mA quiescent and 9mA in alarm at 24V nominal, with an 18V minimum, over up to 100 metres. Terminate it with the supplied end-of-line capacitor unit. Zone input is supported on all compatible Gent addressable panels, Nano included.