Part Number or the Week S3EP-V-VAD-HPR-R

VESDA 4 Pipe VEP with 3.5" Touchscreen Display - Black Plastic

Part no.VEP-A10-P
BrandVESDA
RangeVESDA VEP
Xtralis VEP-A10-P 4 Pipe VEP with 3.5" Touchscreen Display — Black plastic housing, two silver pipes, touchscreen display

Image for illustration; item supplied may differ

At a glance

  • Four Pipe Display ModelVEP-A10-P is the 4 pipe VESDA-E VEP with a 3.5” Display in a plastic enclosure.
  • Seven Programmable RelaysSeven relays are programmable to latching or non-latching states.
  • Pipe Length And CoverageFour pipes reach 280 m (919 ft) linear or 560 m (1,837 ft) branched over 2,000 m2 (21,520 sq. ft).
  • EN 54-20 ClassificationClassification runs Class A (40 holes / Fire 1 = 0.028% obs/m), Class B (80 holes / Fire 1 = 0.027% obs/m) and Class C (100 holes / Fire 1 = 0.056% obs/m).
  • CMOS Particle ImagingDirect imaging of the sampled particles using a CMOS imager combined with multiple photo-diodes allows better detection and fewer nuisance alarms.
  • USB Configuration PortUSB is present for PC configuration, and firmware upgrade using a memory stick.
  • Weight And Cable AccessIt weighs 4.5 kg (9.9 lbs) and takes 4 x 26 mm (1.02 in) cable entries.

Description

VEP-A10-P carries the 3.5” Display. It weighs 4.5 kg (9.9 lbs) and takes 4 x 26 mm (1.02 in) cable entries.

Multi stage filtration and optical protection with clean air barriers ensures lifetime detection performance, and the detector holds consistent performance over its lifetime via absolute calibration.

VEP-A10-P is the four pipe VESDA-E VEP aspirating smoke detector with a 3.5” Display in a plastic enclosure, an Aspirating Smoke Detection product built on Flair detection technology, which delivers reliable very early warning in a wide range of environments with minimal nuisance alarms.

Four pipes reach 280 m (919 ft) laid linear or 560 m (1,837 ft) branched, covering 2,000 m2 (21,520 sq. ft); A/B/C hole counts are 40/80/100 and each pipe needs a minimum of 15 l/m airflow. Classification runs Class A (40 holes / Fire 1 = 0.028% obs/m), Class B (80 holes / Fire 1 = 0.027% obs/m) and Class C (100 holes / Fire 1 = 0.056% obs/m); classification of any configuration is determined using ASPIRE.

Read the full technical description

Seven relays are programmable to latching or non-latching states, and the enclosure is rated IP40. The detector works with existing VESDAnet installations, so both VESDA-E and legacy detectors can be watched through the latest VSC and VSM4 applications.

VEP-A10-P is the four pipe VESDA-E VEP aspirating smoke detector with a 3.5” Display in a plastic enclosure, an Aspirating Smoke Detection product built on Flair detection technology, which delivers reliable very early warning in a wide range of environments with minimal nuisance alarms.

Four pipes reach 280 m (919 ft) laid linear or 560 m (1,837 ft) branched, covering 2,000 m2 (21,520 sq. ft); A/B/C hole counts are 40/80/100 and each pipe needs a minimum of 15 l/m airflow. Classification runs Class A (40 holes / Fire 1 = 0.028% obs/m), Class B (80 holes / Fire 1 = 0.027% obs/m) and Class C (100 holes / Fire 1 = 0.056% obs/m); classification of any configuration is determined using ASPIRE.

Direct imaging of the sampled particles using a CMOS imager combined with multiple photo-diodes allows better detection and fewer nuisance alarms. USB is present for PC configuration and firmware upgrade using a memory stick. The model carries CE and UKCA marking with FM, VdS, CSFM, ActivFire and CCC approval, against EN 54-20 and ISO 7240-20, though approvals and regulatory compliance vary by region and between product models.

Specifications

Product TypeAspirating Smoke Detector (ASD); short-wavelength laser-based detection chamber; four sampling pipe inlets
User interface / displayLED status indicators plus a 3.5" colour touchscreen (the A10 / LCD build); configurable buzzer
Supply voltage range18 to 30 VDC (nominal 24 VDC)
Nominal power consumption @ 24VDC (quiescent / alarm)VEP-A10-P-UL: 0.57 A (quiescent), 0.59 A (alarm)
Maximum power consumption (quiescent / alarm, aspirator settings 1 and 5)VEP-A10-P-UL: 0.33 A / 0.41 A / 0.36 A / 0.44 A across the listed quiescent and alarm columns at aspirator settings 1 and 5; max current is taken from the supply voltage producing the highest current
Dimensions (WHD)13.8 in x 8.9 in x 5.3 in (350 mm x 225 mm x 135 mm)
Weight10.0 lb (4.5 kg)
IP RatingIP40 (enclosure not UL tested)
MountingUpright or inverted, via a steel support bracket or direct mounting
Measurement range0.0000% to 11.09% obs/ft (0.000 to 32% obs/m)
Sensitivity range0.0015 to 6.575% obs/ft (0.005 to 20% obs/m)
Alarm thresholds (default, % obs/m)Alert 0.08, Action 0.14, Fire 1 0.20, Fire 2 2.0 % obs/m (four alarm levels: Alert, Action, Fire1, Fire2)
Threshold setting range (% obs/m, Min-Max)Alert 0.005-2.0, Action 0.005-2.0, Fire 1 0.010-2.0, Fire 2 0.020-20.0 % obs/m
Sampling pipe networkUp to four inlet pipes; max length per pipe (four straight pipes) 230 ft (70 m); maximum total pipe length with branches 1,542 ft (470 m); inlet pipe external diameter 1.05 in (3/4" IPS) or 25 mm
Coverage area (four pipe)Up to 21,520 ft2 (2,000 m2) for the four-pipe VEP-A10-P build
Relays7 programmable relays; contacts rated 2A @ 30 VDC (resistive); default assignments Disable, Minor Fault, Urgent Fault, Alert, Action, Fire 1, Fire 2 (Relay 3 fixed normally energized)
General Purpose InputsTwo GPIs - one monitored, one unmonitored; 5-30 VDC triggers the configured action
InterfacesUSB (local host mode), Ethernet 100base-T (RJ45), VESDAnet networking
Cable termination / accessScrew terminal blocks 0.2-2.5 sq mm (24-14 AWG); cable access 4 x 26 mm ports
Operating conditionsAmbient 32F to 100F (0C to 38C); sampled air -4F to 140F (-20C to 60C); humidity 5-95% RH non-condensing
Event logUp to 20,000 events stored on a FIFO basis
Laser classificationClass 1 laser product complying with FDA 21 CFR 1040.10; laser housed in a sealed, non-serviceable detector chamber
Pipe modeling / design toolASPIRE (pipe network design); standards compliance of a pipe network must be determined using ASPIRE
Configuration variant (identity)VEP-A10-P-GW = VESDA-E VEP with LEDs and 3.5" LCD, four-pipe, coverage area 2,000 sq.m. (21,520 sq.ft); part of the VESDA-E VEP single-pipe/four-pipe family

Specifications per manufacturer documentation, subject to change. E&OE.

Documents

DocumentTypeSizeDownload
Datasheet (VEP-A10-P)Datasheet283 KBDownload PDF