Gent 1 to 4 Loop Vigilon Plus Control Panel without printer c/w 1 loop card & supplied in black. Recommend the use of fixed CLSS Gateway HON-CGW-MBB as a digital printer. Batteries not included - requires 2 x 4015-602-YFR (Power Sonic Flame Retardant 12V 21Ah) to meet compliance regulations.

Part no.VIGPLUS-24-NP
BrandGent
RangeVigilon Plus
Sub-rangeVigilon Plus Panels
Gent by Honeywell 1 to 4 loop Vigilon Plus control panel without printer — product photo

Image for illustration; item supplied may differ

At a glance

  • One to 4 loopsThe VIGPLUS-24-NP supports one to four loops.
  • Supplied without a printerThe NP version is supplied without an integral printer; the fixed CLSS Gateway HON-CGW-MBB is recommended as a digital printer.
  • One loop card suppliedOne loop card is included with the panel.
  • 2 specified batteries requiredOrder 2 x 4015-602-YFR Power Sonic Flame Retardant 12V 21Ah batteries separately; batteries are not included.
  • Black panel finishThe VIGPLUS-24-NP is supplied in black.
  • LPCB approvedVIGPLUS-24-NP is LPCB approved to EN 54-2 and EN 54-4.

Description

The Gent VIGPLUS-24-NP is the black Vigilon Plus control panel for one to four loops, supplied with one loop card and without a printer. It is the option for a system where the panel does not need an integral paper printer. The fixed CLSS Gateway HON-CGW-MBB is recommended as a digital printer. Order two 4015-602-YFR Power Sonic Flame Retardant 12V 21Ah batteries separately. For the Vigilon Plus range, the loop load and cable design set the usable device count, within the stated limits. Use Gent's Battery Standby and Loop Load Calculator to check the proposed system and its standby load.

The VIGPLUS-24-NP is the black Gent Vigilon Plus control panel for one to four loops. It is supplied with one loop card and an integral mains power supply, without a printer. The fixed CLSS Gateway HON-CGW-MBB is recommended as a separate digital printer. This no-printer model is LPCB approved to EN 54-2 and EN 54-4.

Read the full technical description

The VIGPLUS-24-NP is the black Gent Vigilon Plus control panel for one to four loops. It is supplied with one loop card and an integral mains power supply, without a printer. The fixed CLSS Gateway HON-CGW-MBB is recommended as a separate digital printer. This no-printer model is LPCB approved to EN 54-2 and EN 54-4.

The Vigilon Plus range supports up to 200 devices per loop, subject to available addresses, electrical load, cable length and geographical layout. Fire detectors and manual call points together are limited to 512 per control panel. The Battery Standby and Loop Load Calculator assesses the proposed loop and alarm loads.

The panel requires two 4015-602-YFR Power Sonic Flame Retardant 12V 21Ah batteries. Batteries are not included. The Vigilon Plus range uses an integral mains-derived PSU with standby batteries. Standby duration depends on the connected loop and alarm loads.

The Vigilon Plus range has a backlit display with eight lines of 40 characters, 32 integral zone LEDs and four programmable buttons, U1 to U4. USB connects the commissioning tool, while an SD card stores configuration and event logs.

Vigilon Plus networks support up to 31 control panels and network nodes, each fitted with a network card. Maximum cable distances between panels or nodes are 1.2km with copper cards or 2km with fibre cards. Card selection and cable routes form part of the network design alongside loop layout and cause-and-effect configuration.

The Vigilon Plus range supports surface and semi-flush mounting, rear and top cable entry, and separate mounting arrangements for 19-inch racks. A battery box fitted closely below a control panel requires surface mounting.

Specifications

ManufacturerGent
Product rangeVigilon Plus
Panel typeControl panel without printer
Loop range1 to 4 loops
Supplied equipmentBlack panel with one loop card and an integral mains power supply; no integral printer.
FinishBlack
Required batteries2 x 4015-602-YFR
Specified battery typePower Sonic Flame Retardant 12V 21Ah
Battery supplyBatteries not included
Digital printer recommendationFixed CLSS Gateway HON-CGW-MBB, ordered separately
Power source, Vigilon Plus rangeIntegral mains-derived power supply with standby batteries
Device limit, Vigilon Plus rangeMaximum 200 devices per loop; actual count depends on addresses, load, cable length and layout
Detector and call-point limit, Vigilon Plus rangeMaximum 512 fire detectors and/or manual call points per control panel
Display, Vigilon Plus rangeBacklit LCD, 8 lines of 40 characters
Zone indicators, Vigilon Plus range32 integral zone LEDs
User controls, Vigilon Plus rangeFour programmable buttons, U1 to U4
Commissioning connection, Vigilon Plus rangeUSB connection for the commissioning tool
SD functions, Vigilon Plus rangeConfiguration and event logging
Network size, Vigilon Plus rangeUp to 31 control panels and network nodes, each fitted with a network card
Copper distance, Vigilon Plus rangeUp to 1.2km between panels/nodes with copper network cards
Fibre distance, Vigilon Plus rangeUp to 2km between panels/nodes with fibre network cards
Standby design, Vigilon Plus rangeCheck the proposed load with Gent's Battery Standby and Loop Load Calculator

Specifications per manufacturer documentation, subject to change. E&OE.

Standards and approvals

StandardWhat it covers
LPCB approvedApproved by the Loss Prevention Certification Board for fire detection and alarm system products.
LPCB listing 042cc/02
EN 54-2:1997 + A1:2006
EN 54-4:1997 + A2:2006

Approval body: BRE Global Limited (Loss Prevention Certification Board).

Documents

DocumentTypeSizeDownload
Vigilon Plus 4-6 loop panel, data and installation (4188-1100 issue 4)Installation9.6 MBDownload PDF

Optional accessories

FAQs

How many loops and loop cards does the VIGPLUS-24-NP provide?

The VIGPLUS-24-NP supports one to four loops and comes with one loop card. The Vigilon Plus range supports up to 200 devices on each loop, subject to available addresses, electrical load, cable length and layout. Fire detectors and manual call points together are limited to 512 per control panel. Loop count and the connected device mix form part of the system design. The Battery Standby and Loop Load Calculator assesses the proposed loop and alarm loads.

Which batteries must I order for the VIGPLUS-24-NP?

The VIGPLUS-24-NP requires two 4015-602-YFR Power Sonic Flame Retardant 12V 21Ah batteries. Batteries are not included with the panel. The Vigilon Plus range uses an integral mains-derived PSU with standby batteries. Standby duration depends on the connected loop devices and their alarm loads. The Battery Standby and Loop Load Calculator assesses these loads together, allowing the standby requirement to be considered alongside the proposed fire alarm circuit design and device mix.

What does the NP option mean on the VIGPLUS-24-NP?

NP identifies the version supplied without an integral printer. The VIGPLUS-24-NP comes with one loop card and supports one to four loops. The fixed CLSS Gateway HON-CGW-MBB is recommended as a separate digital printer. The Vigilon Plus range also provides SD storage for configuration and event logs, plus a USB connection for the commissioning tool. Its backlit display has eight lines of 40 characters, alongside 32 integral zone LEDs and four programmable user buttons, U1 to U4.

What network limits should I consider when specifying the VIGPLUS-24-NP?

A Vigilon Plus network supports up to 31 control panels and network nodes, each fitted with a network card. Maximum cable distances between panels or nodes are 1.2km with copper cards or 2km with fibre cards. The selected network hardware determines the applicable cable limit. Network design includes the card and cable arrangement, loop layout and cause-and-effect configuration. The Vigilon Plus range provides USB access for the commissioning tool and SD storage for configuration and event logs.

Which approvals apply to VIGPLUS-24-NP?

VIGPLUS-24-NP is LPCB approved to EN 54-2:1997 with A1:2006 for control and indicating equipment, and EN 54-4:1997 with A2:2006 for its power supply. It is a fire alarm control panel for buildings, supplied in black without an integral printer. The panel supports one to four loops and comes with one loop card. It requires two separately supplied 4015-602-YFR batteries for standby power; the connected loop and alarm loads determine the standby duration.