VESDA VEU
Xtralis VEU-A10 VEU with 3
- Product type / detection principle
- Aspirating Smoke Detector (ASD); short-wavelength laser light source with photodiodes and imaging technology measuring smoke obscuration
- Area coverage (single detector)
- Up to 69,965 sq ft (6,500 sq m), subject to system design and local regulatory requirements
- Sampling pipe inlets
- Up to four inlet pipes, each with an ultrasonic flow sensor
- Supply voltage range
- 18 to 30 VDC (nominal 24 VDC)
- Maximum power consumption (VEU-A10-UL)
- 0.84 A quiescent / 0.88 A alarm (maximum current measured from the supply voltage that generates the highest current)
- IP Rating
- IP 40 enclosure (not evaluated by UL)
- Standards / listings (VEU-A10-UL variant, from engineering spec)
- UL268 and UL268A (UL, USA); UL268 (ULC, Canada); CSFM category 7259 (California State Fire Marshal)
You will also need
Needed to install, power or certify this product.
In-Line Filter Grey
Approved Xtralis in-line filter (grey) for the VEU-A10 detector; non-approved third-party in-line filters must not be used.
In-Line Filter Red
Approved Xtralis in-line filter (red) for the VEU-A10 detector; non-approved third-party in-line filters must not be used.
Specifications
Full technical data for this part.
| Product type / detection principle | Aspirating Smoke Detector (ASD); short-wavelength laser light source with photodiodes and imaging technology measuring smoke obscuration |
|---|---|
| Area coverage (single detector) | Up to 69,965 sq ft (6,500 sq m), subject to system design and local regulatory requirements |
| Sampling pipe inlets | Up to four inlet pipes, each with an ultrasonic flow sensor |
| Supply voltage range | 18 to 30 VDC (nominal 24 VDC) |
| Maximum power consumption (VEU-A10-UL) | 0.84 A quiescent / 0.88 A alarm (maximum current measured from the supply voltage that generates the highest current) |
| Nominal power consumption @ 24 VDC by aspirator setting (VEU-A10-UL) | Quiescent: 0.32 A (setting 1) / 0.41 A (5) / 0.64 A (10); Alarm: 0.35 A (1) / 0.44 A (5) / 0.67 A (10) |
| Dimensions (W x H x D) | 13.8 in x 8.9 in x 5.3 in (350 mm x 225 mm x 135 mm) |
| Weight | 11.7 lbs (5.3 kg) |
| Operating conditions | Ambient 32 F to 100 F (0 C to 38 C); sampled air -4 F to 140 F (-20 C to 60 C); humidity 5-95% RH non-condensing |
| Sampling pipe network limits | Max length per pipe with four straight pipes: 328 ft (100 m); max total pipe length with branches: 2,624 ft (800 m); minimum airflow per pipe: 20 l/min; design tool: ASPIRE |
| Inlet / exhaust pipe size | External diameter 1.05 in (3/4" IPS) or 25 mm (exhaust via adaptor) |
| Relays | 7 programmable relays; contacts rated 2 A @ 30 VDC (resistive); programmable to latch or not latch alarm/fault states |
| General Purpose Inputs | Two GPIs (one monitored, one unmonitored) |
| IP Rating | IP 40 enclosure (not evaluated by UL) |
| Cable access / termination | 4 x 26 mm cable ports; screw terminal blocks (0.2-2.5 sq mm, 24-14 AWG) |
| Interfaces | USB (Type 2); Ethernet (RJ45, 100 base T); VESDAnet |
| Measurement range | 0.0000% to 11.09% obs/ft (0.000 to 32% obs/m) |
| Sensitivity range | 0.0003 to 6.575% obs/ft (0.001 to 20% obs/m) |
| Alarm levels | Four configurable alarm levels: Alert, Action, Fire 1, Fire 2 |
| Event log | Up to 20,000 events stored on a FIFO basis |
| Mounting orientation | Upright or inverted |
| Standards / listings (VEU-A10-UL variant, from engineering spec) | UL268 and UL268A (UL, USA); UL268 (ULC, Canada); CSFM category 7259 (California State Fire Marshal) |
| Family designator (engineering spec) | VEU-A10-GW: VESDA-E VEU with LEDs and 3.5" LCD, coverage up to 6,500 sq m (69,965 sq ft); sibling VEU-A00-GW is the LED-only version |
Specifications sourced from manufacturer documentation.
Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know
Optional accessories
Optional additions — this product works without them.
ASD ENCL IP66 VESDA-E
compatible / works with: ASD ENCL IP66 VESDA-E
PC Link HLI Access Protocol
compatible / works with: PC Link HLI Access Protocol
PC Link HLI Modbus MK3
compatible / works with: PC Link HLI Modbus MK3
Metal Box HLI - Access Protocol
compatible / works with: Metal Box HLI - Access Protocol
Metal box HLI - Modbus Type 3
compatible / works with: Metal box HLI - Modbus Type 3
VESDA-E STX PSU 0.5A (7-14AH) - BLACK
compatible / works with: VESDA-E STX PSU 0.5A (7-14AH) - BLACK
VESDA-E STX PSU 3A (7-24AH) - BLACK
compatible / works with: VESDA-E STX PSU 3A (7-24AH) - BLACK
VEU with LEDs
Alternative — same VESDA-E VEU aspirating smoke detector; VEU-A00 variant has LEDs instead of a 3.5" display.
Datasheets & documents
Reference downloads.
- Datasheet (VEU-A10, VSP-966)datasheet282 KB