VESDA-E VE Scanner detector with LED's

Part no.VES-A00-P
BrandVESDA
RangeVESDA VES
Xtralis VES-A00-P VESDA-E detector — black housing with vertical LED display and four antennas

Image for illustration; item supplied may differ

At a glance

  • Four Sector AddressabilitySector addressability covers up to four sectors, so one zone can be divided into four separately reported sectors.
  • Inlet Manifold Valve MechanismA valve mechanism in the inlet manifold and software control the airflow from the four Sectors (pipes).
  • First Alarm Sector ScanningWhen smoke reaches the Adaptive Scan Threshold the VES scans each sector and designates the First Alarm Sector (FAS).
  • Twelve Programmable RelaysTwelve programmable relays are fitted, latching or non-latching, with contacts rated 2 A @ 30 VDC (Resistive).
  • Power Per Aspirator SettingQuiescent consumption is 7.5 W on setting 1, 9.8 W on setting 5 and 15.4 W on setting 10, with alarm figures of 8.4 W, 10.8 W and 15.8 W.
  • Coverage And AirflowCoverage reaches 2,000 m2 (21,520 sq. ft) with a minimum airflow per pipe of 20 l/m.
  • Backward Compatible With VLSThe detector is backward compatible with VLS and VESDAnet.
  • Pipe Length CapacityPipe length reaches 560 m (1,837 ft) branched or 280 m (919 ft) linear, each subject to agency confirmation.

Description

Sector addressability reaches up to four sectors, and VES-A00-P is the build that indicates on LEDs. An adaptive scan threshold governs when the scan begins.

Quiescent consumption at 24 VDC is 7.5 W with the aspirator on setting 1, 9.8 W on setting 5 and 15.4 W on setting 10; in alarm the same three settings give 8.4 W, 10.8 W and 15.8 W. It weighs 4.7 kg (10.4 lbs) and needs a minimum airflow per pipe of 20 l/m across 2,000 m2 (21,520 sq. ft) of coverage.

VES-A00-P is the LED build of the VESDA-E VES, a four-sector aspirating smoke detector in a plastic enclosure. It includes a valve mechanism in the inlet manifold and software to control the airflow from the four Sectors (pipes), so one zone can be split across four separately reported sectors.

Air is drawn from all sectors in use. If the smoke level reaches the Adaptive Scan Threshold, the VES quickly scans each sector to identify which sector is carrying smoke; the first sector to reach the Alert level becomes the First Alarm Sector (FAS) and is signalled to the user, and where two or more sectors reach Alert, the sector with the highest smoke concentration takes that designation.

Read the full technical description

The classes are A with 40 holes at Fire 1 = 0.067% obs/m, B with 80 holes at 0.085% obs/m and C with 100 holes at 0.251% obs/m; ASPIRE determines the classification of any configuration. The detector is backward compatible with VLS and VESDAnet.

VES-A00-P is the LED build of the VESDA-E VES, a four-sector aspirating smoke detector in a plastic enclosure. It includes a valve mechanism in the inlet manifold and software to control the airflow from the four Sectors (pipes), so one zone can be split across four separately reported sectors.

Air is drawn from all sectors in use. If the smoke level reaches the Adaptive Scan Threshold, the VES quickly scans each sector to identify which sector is carrying smoke; the first sector to reach the Alert level becomes the First Alarm Sector (FAS) and is signalled to the user, and where two or more sectors reach Alert, the sector with the highest smoke concentration takes that designation.

Four individually configurable alarm levels (Alert, Action, Fire 1 and Fire 2) are available for each sector. The measurement range is 0.000 to 32% obs/m (0.0000 to 11.09% obs/ft). Twelve programmable relays are fitted, latching or non-latching, with contacts rated 2 A @ 30 VDC (Resistive). Ethernet is present for connectivity with Xtralis software for configuration, secondary monitoring and maintenance.

Specifications

Ip ratingIP 40
Supply voltage18 to 30 VDC (24 VDC Nominal)
Dimensions (whd)350 mm x 225 mm x 135 mm
Weight4.7 kg (10.4 lbs)
Sensitivity range0.005 to 20% obs/m (0.0015 to 6.575% obs/ft)
Relays12 programmable relays
Contacts rated2A @ 30 VDC (Resistive)
Power (in alarm)10.8 W
Power (quiescent)9.8 W
Humidity5% to 95% RH, non-condensing
Inlet pipe size (external diameter)25 mm or 1.05 in (3/4" IPS)
Area coverageup to 2,000 m² (21,520 ft²)
Number of inlet pipesUp to four inlet pipes
Sector addressabilityup to four sectors or zones

Specifications per manufacturer documentation, subject to change. E&OE.