Gent Vigilon Compact Plus 1-2 Loop Control Panel c/w 1 Loop Card & Supplied in Black.
| Part no. | COMPACT-PLUS |
|---|---|
| Brand | Gent |
| Range | Compact Plus |
| Sub-range | Compact Plus Panels |

Image for illustration; item supplied may differ
At a glance
- One loop supplied, two supportedSupplied with one COMPACT-LPC-EN loop card; add another for a second detection loop.
- Up to 200 devices per loopThe usable device count and cable length depend on the compatible device mix, alarm load and device positions.
- Optional copper networkingCOMPACT-NC connects the panel to a secure loop of up to 31 panels and network nodes.
- Second loop retained when networkedWith COMPACT-NC in CARD 2, the second loop card fits the socket on the network card.
- Local alarm and plant connectionsTwo master alarm circuits, configurable auxiliary relays, clean contacts and a monitored input support site connections.
- LCD and 32 zone LEDsAn eight-line backlit display and integral zone indicators present local system events.
Description
The Gent COMPACT-PLUS is a one to two loop fire alarm control panel, supplied in black with one loop card. Each loop can take up to 200 compatible devices, with the usable count and cable length set by the device mix, alarm load and layout. A second COMPACT-LPC-EN adds the second loop, while the optional COMPACT-NC links the panel to a copper network. The panel has a backlit LCD, 32 zone LEDs and two master alarm circuits. It runs from a mains supply with battery standby. Batteries are not included: order two 4015-514-YFR 12V 12Ah units and check the standby time against the system load.
COMPACT-PLUS controls up to two addressable detection loops and is supplied with one COMPACT-LPC-EN loop card. Each loop can serve up to 200 compatible devices, including fire sensors, manual call points and interfaces. This card supports up to 2 km of loop cable in the Compact Plus panel, with the actual device count and cable length governed by the compatible device mix, alarm load and whether alarm devices are spread out or grouped together. Use the Battery Standby and Loop Load calculator for the proposed device mix.
Read the full technical description
COMPACT-PLUS controls up to two addressable detection loops and is supplied with one COMPACT-LPC-EN loop card. Each loop can serve up to 200 compatible devices, including fire sensors, manual call points and interfaces. This card supports up to 2 km of loop cable in the Compact Plus panel, with the actual device count and cable length governed by the compatible device mix, alarm load and whether alarm devices are spread out or grouped together. Use the Battery Standby and Loop Load calculator for the proposed device mix.
For a second loop, fit another COMPACT-LPC-EN. The first loop card goes in CARD 1 on the master control board. The second goes in CARD 2 unless a COMPACT-NC network card is fitted there; in that arrangement the second loop card plugs into the socket on the network card. The optional COMPACT-NC connects the panel to a secure copper loop network of up to 31 panels and network nodes. The distance between adjacent units can reach 1.2 km with a suitable approved cable; the permitted distance depends on the cable type.
Two master alarm circuits each provide 24 V nominal at up to 250 mA. Auxiliary relay 1 has two changeover contact sets and relay 2 has one, rated 1 A at 24 V DC. They can be configured for fire, fault or disablement, with an optional delay of up to ten minutes. A separate voltage-free changeover contact set operates with the master alarms. The normally open monitored input checks for open and short circuit faults and triggers command build 250, whose action is selected during commissioning.
The backlit LCD displays eight lines of 40 characters, alongside 32 integral zone LEDs. RS485 Port 0 connects repeat indicators, RS232 Ports 1 and 2 provide serial connections, and USB Port 3 at P16 connects the commissioning tool. An SD card can hold configuration data and extended event logs when that function is enabled.
The integral power supply takes 230 V mains at 50/60 Hz. Order two 4015-514-YFR Power Sonic Flame Retardant 12 V 12 Ah batteries separately: batteries are not included. The 24-hour standby and 30-minute alarm target must be checked against the installed load. The black IP31 panel measures 403 x 338 x 140 mm, height x width x depth, and weighs approximately 8.6 kg without batteries. It has top and rear cable entries and can be surface mounted or semi-flush mounted with the optional COMPACT-FLUSH surround.
Specifications
| Product type | Vigilon Compact Plus fire alarm control panel |
|---|---|
| Supplied detection loops | 1, with one COMPACT-LPC-EN card |
| Maximum detection loops | 2, with a second loop card |
| Devices per loop | Up to 200; subject to compatible device mix and loading |
| Loop cable length | Up to 2 km; subject to compatible device mix, alarm load, device positions and cable selection |
| Additional loop card | COMPACT-LPC-EN |
| Optional network card | COMPACT-NC |
| Network capacity | Up to 31 panels and network nodes in a secure copper loop |
| Network link distance | Up to 1.2 km between units, dependent on approved cable type |
| Mains supply | 230 V, -15%/+10%, 50/60 Hz |
| Mains input current | 0.6 A |
| Batteries required | 2 x 4015-514-YFR, Power Sonic Flame Retardant 12 V 12 Ah; ordered separately |
| Batteries included | No |
| Standby target | 24 hours plus 30 minutes alarm; check with the Battery Standby and Loop Load calculator |
| Dimensions | 403 H x 338 W x 140 D mm |
| Weight | Approximately 8.6 kg without batteries |
|---|---|
| Ingress protection | IP31 |
| Operating temperature | 0 to +45 C |
| Storage temperature | -10 to +55 C |
| Relative humidity | Up to 90%, non-condensing, at +5 to +45 C |
| Master alarm circuits | 2, 24 V nominal, 250 mA maximum per circuit |
| Auxiliary relay 1 | Two changeover contact sets; factory set for fire |
| Auxiliary relay 2 | One changeover contact set; factory set for fault |
| Auxiliary relay contact rating | 1 A at 24 V DC |
| Clean contacts | One voltage-free changeover set, 1 A at 24 V DC, active with master alarms |
| Monitored input | Normally open; open/short circuit monitoring; triggers command build 250 |
| Display | Backlit LCD, 8 lines x 40 characters |
| Zone indication | 32 integral zone LEDs |
| Ports | RS485 Port 0; RS232 Ports 1 and 2; USB Port 3 at P16 |
| Mounting and cable entry | Surface or semi-flush with optional surround; top and rear cable entries |
Specifications per manufacturer documentation, subject to change. E&OE.
Standards and approvals
| Standard | What it covers |
|---|---|
| LPCB approved | Approved by the Loss Prevention Certification Board for fire detection and alarm system products. |
| LPCB certificate 042cb, listing 042cb/01 | |
| EN 54-2:1997 + A1:2006 | |
| EN 54-4:1997 + A2:2006 |
Approval body: BRE Global Limited (Loss Prevention Certification Board).
Guides
Optional accessories
- COMPACT-LPC-ENAdditional Loop Card (2km) for COMPACT-24-NAdd when a second detection loop is required.£460.58ex VAT£552.70 inc VATIn stock
- COMPACT-NCNetwork Card for Vigilon Compact (EN Networks Only)Add when copper networking is required.£742.33ex VAT£890.80 inc VATIn stock
- COMPACT-FLUSHControl Panel Flush Surround (Supplied in Black)For semi-flush mounting.£142.32ex VAT£170.78 inc VATIn stock
Spares & replacement parts
- VCS-PSU-NReplacement PSU for Compact Control PanelListed replacement power supply for Compact Plus.£344.43ex VAT£413.32 inc VATIn stock
- VCS-MCB-PLUSReplacement Main Control PCB for Compact Plus Control PanelListed replacement master control board for Compact Plus.£650.90ex VAT£781.08 inc VATIn stock
FAQs
How many loops are supplied with COMPACT-PLUS?
COMPACT-PLUS is supplied with one COMPACT-LPC-EN loop card, giving one detection loop. Add a second card of the same order code when two loops are required. Each loop can carry up to 200 compatible devices, but that ceiling must be checked against the device mix, alarm load and device positions. This panel and card combination supports up to 2 km of loop cable, with the actual cable length and device count established for the proposed system using the loop load calculator.
Which batteries do I need to order for COMPACT-PLUS?
Order two 4015-514-YFR Power Sonic Flame Retardant 12 V 12 Ah batteries. They are separate items and are not included with COMPACT-PLUS. The pair provides the battery arrangement specified for this panel, whose standby target is 24 hours followed by 30 minutes in alarm. Check that target against the connected equipment using the Battery Standby and Loop Load calculator. The panel weight of approximately 8.6 kg excludes the batteries, so it is not the complete installed weight.
Can COMPACT-PLUS have two detection loops and a network card?
Yes. Fit the first loop card in CARD 1 on the master control board. The COMPACT-NC network card fits CARD 2, and the second COMPACT-LPC-EN loop card then plugs into the socket on that network card. This arrangement retains both detection loops on a networked Compact Plus panel. Without a network card, the second loop card fits CARD 2 directly. The copper network supports up to 31 panels and network nodes in a loop.
What outputs does COMPACT-PLUS provide for sounders and plant?
There are two master alarm circuits, each rated at 24 V nominal and 250 mA maximum. Auxiliary relay 1 provides two changeover contact sets, while relay 2 provides one; their contacts are rated 1 A at 24 V DC. The relays can respond to fire, fault or disablement and can have a delay of up to ten minutes. A separate clean-contact changeover set operates with the master alarms. Those contact ratings govern equipment connected directly to the relays.
What are the enclosure size and mounting options for COMPACT-PLUS?
The Compact Plus panel measures 403 mm high, 338 mm wide and 140 mm deep. The panel is black, is rated IP31 and weighs approximately 8.6 kg without batteries. It can be surface mounted, or semi-flush mounted using the separately ordered COMPACT-FLUSH surround. Cable entries are provided at the top and rear. The front carries a backlit display with eight lines of 40 characters and 32 zone LEDs, giving local information about events on the connected fire alarm system.