Detector
Gent 803371.EX IS Optical Smoke Detector
- Operating voltage
- 8 V DC to 42 V DC
- Sensor type
- Smoke (Optical)
- Ambient temperature
- -20 °C to +70 °C * 3
- Alarm indicator
- red LED, flashing
- IP rating
- IP 43 (with base + optional base gasket)
- EN54 standard
- EN 54-7 : 2006
- VdS approval
- G 204060
You will also need
Needed to install, power or certify this product.
Detector Base. Can be used for ES Conventional and Intrinsically safe detection.
Detector base associated in the IS products listing
Z-System Zener barrier for intrinsically safe detectors
Intrinsically safe optical smoke detector requires the safety barrier for its ATEX II 2G category.
Overview
What it is and how it fits the system.
The Gent 803371.EX is an optical smoke detector listed among the Intrinsically Safe and relay products used with the S4 Mains Powered Interface Unit, connected via Zener barriers for intrinsically safe detection. It is specified for IS smoke detection circuits served by that interface.
Technical overview
803371.EX is an intrinsically safe optical smoke detector designed for fire detection systems requiring explosion protection. It operates across an 8 V DC to 42 V DC range and uses an optical sensing method to detect smoke particles. The device features a red flashing LED as its alarm indicator and is constructed from white ABS housing with a colour similar to RAL 9010.
It is rated IP 43 when installed with the base and optional base gasket, providing protection against solid objects over 1 mm and spraying water. The detector functions in ambient temperatures from -20 °C to +70 °C and tolerates up to 95% non-condensing relative humidity. Storage conditions extend from -25 °C to +75 °C. It carries EN 54-7 : 2006 certification for smoke detection performance, VdS approval G 204060, CE certification 0786 - CPD - 20104, and Ex-protection classification Ex ib IIC T4 Gb for use in intrinsically safe circuits.
Physical dimensions with base are Ø 117 mm and height 62 mm, with a weight of approximately 110 g. The detector requires the base (SKU 805590) for installation and must be used with a Z-System Zener barrier (SKU 764744 or 804744) to maintain its intrinsically safe status in ATEX II 2G environments. It is compatible with esserbus transponders and can be connected as a spur of the esserbus/esserbus-Plus loop. Testing should only be performed using a dedicated smoke detector device and test gas. Commissioning, testing and maintenance are supported by the 8000 service and programming software.
Specifications
Full technical data for this part.
| Operating voltage | 8 V DC to 42 V DC |
|---|---|
| Sensor type | Smoke (Optical) |
| Ambient temperature | -20 °C to +70 °C * 3 |
| Alarm indicator | red LED, flashing |
| IP rating | IP 43 (with base + optional base gasket) |
| Housing | ABS |
| Colour | White (similar to RAL 9010) |
| Weight | approx. 110 g |
| Dimensions (with base) | Ø 117 mm, H = 62 mm |
| Ambient humidity | ≤ 95% relative, (non-condensing) % |
| Storage temperature | -25 °C to +75 °C |
| EN54 standard | EN 54-7 : 2006 |
| VdS approval | G 204060 |
| CE certificate | 0786 - CPD - 20104 |
| Ex-protection | Ex ib IIC T4 Gb |
Specifications sourced from manufacturer documentation.
Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know
Optional accessories
Optional additions — this product works without them.
Z-System Zener barrier for AV device (Drives one sounder or two strobes)
Listed in the Intrinsically Safe and relay products table alongside Z969 Zener Barrier for
Heat Sensor Rate Of Rise
Part of the same IS detector family as 803271.EX Rate-of-rise heat detector and 803374.EX
Dual Optical Heat Smoke sensor
Part of the same IS detector family as 803271.EX Rate-of-rise heat detector and 803374.EX
Relay 24V DC Base & Diode
compatible / works with: Relay 24V DC Base & Diode
Compare variants
Alternatives in the same range — pick the variant that fits your install.
Datasheets & documents
Reference downloads.
- 447 KB