Skip to content

Trade prices shown ex VAT. Order by 3pm for same-day dispatch on stocked lines, UK mainland. Free UK delivery on orders over £250 ex VAT.

Part Number or the Week S3EP-V-VAD-HPR-R

Gent Relay 24V DC Base & Diode

Part no.19104-52
BrandGent
RangeConventional Modules & Relays
Sub-rangeRelay
Gent 19104-52 Relay 24V DC Base & Diode — beige terminal block with black terminal block

Image for illustration; item supplied may differ

At a glance

  • Large alarm load driverDrives high-powered sounders fed from a separate 24 V battery and charger power supply from a panel or interface sounder circuit.
  • Four relays per interfaceA maximum of four relays with diode units can be fitted on the DIN rail inside the S4-34440 mains-powered interface unit.
  • DIN rail mountingUses an octal base holder that is TS35 DIN rail mountable within the interface unit.
  • 10 A contact ratingThe relay contacts are rated at 10 A, so the sounder load is set by the power supply and this rating together.
  • Two changeover contactsProvides two changeover sets of contacts, COM, NO and NC, on the octal base.

Description

The 19104-52 is the 24 V dc power relay that fits on the DIN rail inside the Gent mains-powered interface unit. It has an octal base and is used to drive a larger alarm load, such as high-powered sounders fed from a separate 24 V battery and charger power supply, from a panel or interface sounder circuit. The relay is rated at 10 A, and the load it can switch is limited by both the power supply and the relay contacts. Up to four relays can be fitted with diode units on the DIN rail inside the interface unit.

The 19104-52 power relay fits an octal base holder that is TS35 DIN rail mountable and installs inside the S4-34440 mains-powered interface unit. A maximum of four relays with their diode units can be fitted on the DIN rail inside the interface unit.

Read the full technical description

The 19104-52 power relay fits an octal base holder that is TS35 DIN rail mountable and installs inside the S4-34440 mains-powered interface unit. A maximum of four relays with their diode units can be fitted on the DIN rail inside the interface unit.

Where a 24 V alarm circuit at a control panel or interface unit output is required to drive a large alarm load, the relay is used as a driver. The monitored sounder circuit is wired across the relay coil through the diode unit, so the coil energises on the alarm polarity. A separate 24 V dc battery and charger power supply unit on its own mains feed supplies the alarm load, and its positive and negative rails run through the relay contacts to the chain of sounders, which ends in an end of line resistor so the load circuit stays monitored. The power supply fault contacts are taken to a suitable interface input. The total alarm load must be within the switching and power limits of both the power supply and the relay.

The relay has a 24 V coil with a 470 ohm coil resistance, a 10 A contact rating, a current consumption of 50 mA, and two changeover contact sets.

Specifications

Device type24 V dc power relay for the Gent mains-powered interface unit
MountingOctal base holder, TS35 DIN rail mountable, inside the S4-34440 interface
Maximum fittedFour relays with diode units on the DIN rail inside the interface unit
Relay voltage24 V
Relay coil resistance470 ohms
Relay contact rating10 A
Relay current consumption50 mA
ContactsTwo changeover sets, COM, NO and NC
Companion partDiode unit, TS35 DIN rail mountable, wired across the coil

Specifications per manufacturer documentation, subject to change. E&OE.

Documents

DocumentTypeSizeDownload
S4 mains-powered interface, data and installation (4188-968 issue 11)Installation2.5 MBDownload PDF

Optional accessories

+ 4 more