Wireless Conventional ES Detect
Gent 803374.EX O2T Intrinsically Safe Multisensor
- Sensor type
- Dual Optical Smoke Heat detector
- Ambient temperature
- -20 °C to +65 °C
- Specification
- EN 54-7 : 2006 / -5 B : 2000 / A1 : 2002, CEA 4021
- VdS approval
- G 204061
- Operating voltage
- 8 V DC to 42 V DC
- IP rating
- IP 43 (with base + optional base gasket)
- Max. input current (Ii)
- 252 mA
You will also need
Needed to install, power or certify this product.
Intrinsically Safe Dual Angle Optical Heat Detector - Please use base 805590.
Listed in the Intrinsically Safe and relay products order codes (803374.EX O2T-multisensor
Detector Base. Can be used for ES Conventional and Intrinsically safe detection.
Listed in the Intrinsically Safe and relay products order codes (803374.EX O2T-multisensor
Replacement Battery Pack for 805593 & 805601
Dual Optical Smoke Heat detector used in the wireless adapter base must be operated with battery pack 805597
Overview
What it is and how it fits the system.
The Gent 803374 is the 803374.EX O2T-multisensor detector, listed among Gent's Intrinsically Safe and relay products. It combines multisensor detection in an intrinsically safe form for hazardous-area applications.
Technical overview
803374 is a wired, intrinsically-safe dual optical/heat smoke detector designed for ATEX zone-1 environments. The unit fits directly into detector base 805590 and works in both ES conventional and intrinsically-safe detection systems.
Operating on 8 V DC to 42 V DC, the detector is certified to EN 54-7 : 2006 / -5 B : 2000 / A1 : 2002 and CEA 4021, with VdS approval G 204061 and CE certificate 0786 - CPD - 20105/20106. Explosion protection is rated Ex ib IIC T4 Gb, validated by ATEX examination certificate TÜV 09 ATEX 554910, and the assembly achieves ATEX category II 2G when used with safety barrier 764744/804744. A flashing red LED provides the alarm indication.
For hazardous areas the detector must be operated exclusively with its Ex safety barriers, part number 764744/804744, and it is commissioned, tested and maintained only with the 8000 service and programming software.
Constructed from ABS and finished in white, similar to RAL 9010, the detector weighs approximately 110 g and measures Ø 117 mm with a height of 62 mm on base 805590, reaching IP 43 with the base and an optional gasket. Ambient operation spans -20 °C to +65 °C, storage is rated between -25 °C and +75 °C, and the unit tolerates up to 95% relative humidity, non-condensing, while staying stable in moving air up to 25.4 m/s. Physical connections and wiring details are set out in the installation documentation.
Specifications
Full technical data for this part.
| Sensor type | Dual Optical Smoke Heat detector |
|---|---|
| Ambient temperature | -20 °C to +65 °C |
| Specification | EN 54-7 : 2006 / -5 B : 2000 / A1 : 2002, CEA 4021 |
| VdS approval | G 204061 |
| CE certificate | 0786 - CPD - 20105/20106 |
| Operating voltage | 8 V DC to 42 V DC |
| Alarm indicator | red LED, flashing |
| Air velocity range | 0 to 5.000 ft/min. ft/min |
| Storage temperature | -25 °C to +75 °C |
| Ambient humidity | ≤ 95% relative,(non-condensing) % |
| IP rating | IP 43 (with base + optional base gasket) |
| Housing material | ABS |
| Colour | White (similar to RAL 9010) |
| Weight | approx. 110 g |
| Dimensions (with base) | Ø 117 mm, H = 62 mm |
| Ex protection | Ex ib IIC T4 Gb |
| ATEX examination certificate | TÜV 09 ATEX 554910 |
| ATEX category | II 2G (with safety barrier Part No. 764744) |
| Max. input voltage (Ui) | 21 V DC |
| Max. input current (Ii) | 252 mA |
| Max. output current (Io) | 10 mA |
| Max. internal capacity (Ci) | 1 nF |
Specifications sourced from manufacturer documentation.
Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know
Optional accessories
Optional additions — this product works without them.
Z-System Zener barrier for AV device (Drives one sounder or two strobes)
Listed in the Intrinsically Safe and relay products order codes (803374.EX O2T-multisensor
Z-System Zener barrier for intrinsically safe detectors
Listed in the Intrinsically Safe and relay products order codes (803374.EX O2T-multisensor
Datasheets & documents
Reference downloads.
- 447 KB