Skip to content

Trade prices shown ex VAT. Order by 3pm for same-day dispatch on stocked lines, UK mainland. Free UK delivery on orders over £250 ex VAT.

Part Number or the Week S3EP-V-VAD-HPR-R

Gent 1.5m Venturi Tube

Part no.S4-34760-15
BrandGent
RangeS4 Duct & Accessories
Sub-rangeVenturi Tubes
Gent by Honeywell S4-34760-15 1.5m Venturi Tube — metallic cylindrical tube with a shaped inlet and outlet

Image for illustration; item supplied may differ

At a glance

  • 1.5 m tube length1500 mm Venturi tube for the Gent S4-34760 duct housing.
  • 600 to 1400 mm duct diameterSized for this duct diameter band, with the tube trimmed during installation.
  • 0.6 kg tube weightThe S4-34760-15 tube weighs 0.6 kg.
  • Support at the opposite wallThe fitted tube passes through the far side of the duct for support.
  • Cut to the installation lengthAllow for about 30 mm projection beyond the far wall, never more than 30 mm, and any mounting bracket spacing.
  • Gasket and screw connectionFits the housing’s oval opening with a rubber gasket and the housing kit’s short retaining screw.

Description

The Gent S4-34760-15 is a 1.5 m Venturi tube for the S4-34760 duct housing. It suits duct diameters from 600 to 1400 mm and weighs 0.6 kg. The tube takes air from the duct to the detector housed outside it. Cut the tube to suit the duct, with support at the far wall and an end cap in place. The entry hole is 38 mm and the far wall hole is 50 mm. Allow for the spacing of a mounting bracket when setting the length. The S4-34760-99 bracket is required on round or insulated ducts. A short screw secures the tube at the housing. The housing connection uses a rubber gasket at its oval opening.

The S4-34760-15 is the 1500 mm Venturi tube for the S4-34760 duct housing. Its duct diameter band is 600 to 1400 mm, and its weight is 0.6 kg. Air passes through the tube to the detector inside the externally mounted housing.

Read the full technical description

The S4-34760-15 is the 1500 mm Venturi tube for the S4-34760 duct housing. Its duct diameter band is 600 to 1400 mm, and its weight is 0.6 kg. Air passes through the tube to the detector inside the externally mounted housing.

Trim the tube to the installed duct size. It passes through the opposite duct wall, where it needs support, and projects about 30 mm beyond that wall, without exceeding 30 mm. The cut length must also allow for the spacing between the housing and duct when a mounting bracket is fitted.

The housing-side duct opening is 38 mm in diameter; the opposite-wall opening is 50 mm. Deburr the 38 mm opening and fit the seals at the duct penetration. At the housing, fit the rubber gasket around the tube, insert it into the oval opening and secure it with the housing kit's short screw. Close the free end with the end cap.

Use the S4-34760-99 mounting bracket for circular or insulated ducts. The bracket bends to the duct shape and has pre-punched fixing holes. The housing arrow must follow the air flow, with the tube positioned centrally across the duct.

Specifications

Product typeVenturi sampling tube
Compatible housingS4-34760
Tube length1500 mm / 1.5 m
Suitable duct diameter600 to 1400 mm
Tube weight0.6 kg
Length adjustmentCut to suit duct and mounting arrangement
Far-wall supportRequired at opposite duct wall
Housing-side duct bore38 mm diameter
Opposite-wall duct bore50 mm diameter
Tube end projectionAbout 30 mm beyond opposite wall; maximum 30 mm. Allow for bracket spacing when cutting
Housing connectionRubber gasket, oval entry and short retaining screw
End terminationEnd cap fitted
Circular or insulated duct installationS4-34760-99 bracket required

Specifications per manufacturer documentation, subject to change. E&OE.

Documents

DocumentTypeSizeDownload
Datasheet (S4-34760-15, S4-34760-28, S4-34760-99)Datasheet152 KBDownload PDF
Installation manual (S4-34760-15, S4-34760-28, S4-34760-99)Installation1.3 MBDownload PDF

Optional accessories

FAQs

Which ducts suit the S4-34760-15 tube?

The S4-34760-15 suits duct diameters from 600 to 1400 mm and has a supplied length of 1500 mm. It works with the S4-34760 housing, which sits outside the duct while the tube extends across the air stream. Trim the tube to suit the installation and support it at the opposite wall. For duct diameters from 1400 to 2700 mm, the corresponding longer option is the 2800 mm S4-34760-28, fitted to the same housing.

How should the S4-34760-15 be cut to length?

Cut the tube to suit the duct diameter and the housing's mounting position. The fitted tube passes through the far duct wall and projects about 30 mm beyond it, without exceeding 30 mm. When a bracket holds the housing away from the duct, allow for that spacing in the overall cut length. Fit the cap to the free end once the tube is trimmed, and support the tube at the opposite wall. The housing end is retained by a short screw.

What duct openings does the S4-34760-15 need?

The long-tube installation uses two duct openings: a 38 mm hole on the housing side and a 50 mm hole in the opposite wall. Deburr the 38 mm opening before fitting. The far-wall opening supports the tube as it crosses the duct, and the penetration needs its seal. The tube end is capped beyond that wall. At the housing, a separate rubber gasket sits around the tube where it enters the oval opening and is secured with the short screw.

How does the S4-34760-15 connect to the housing?

Fit the rubber gasket at the tube's housing end, insert that end into the oval opening in the S4-34760 and secure it with the housing kit's short screw. The tube carries duct air into the chamber containing the separate detector. Position the tube centrally across the duct and align the housing arrow with the airflow. The 1500 mm tube also needs support at the opposite wall, with its free end capped after it has been cut to length.

Does the S4-34760-15 installation need a bracket?

Circular or insulated ducts require the S4-34760-99 bracket for the S4-34760 housing. The bracket bends to follow the duct shape and has pre-punched mounting holes. Its spacing between the housing and duct must be included when setting the tube's cut length. The S4-34760-15 still needs support at the opposite wall and an end cap. Use its 600 to 1400 mm duct diameter band when sizing the installation, with the housing arrow aligned to the airflow.