Skip to content

Trade prices shown ex VAT. Order by 3pm for same-day dispatch on stocked lines, UK mainland. Free UK delivery on orders over £250 ex VAT.

Part Number or the Week S3EP-V-VAD-HPR-R

Gent S3 red Body Voice Sounder High Power White VAD

Part no.S3-V-VAD-HPW-R
BrandGent
RangeS3 Sounders & VADs
Sub-rangeWall Voice Sounders with VAD
Gent by Honeywell S3-V-VAD-HPW-R red body voice sounder — red housing clear lens visible LED

Image for illustration; item supplied may differ

At a glance

  • High Power white visual alarm with speechThis red bodied model combines three alarm tones, four spoken messages and a bell tone with a High Power white VAD.
  • Three EN 54-23 coverage settingsHigh: W-5-12.5, 781 cubic metres; Medium: W-4.5-11.3, 574 cubic metres; Low: W-3-8.5, 216 cubic metres. Coverage requires compliant operation, compatible panel software, installation within the category's maximum mounting height and minimum effective illuminance of 0.4 lux. For EN Vigilon 4-loop and 4-6-loop panels, EN 54-23 coverage requires MCC V4.52 or later and LPC V4.48 or later. For EN Vigilon Compact, it requires MCB V4.52 or later and LPC V4.48 or later. On Nano, MCB V3.12 or later and LP V1.08 or later support Low Power coverage only.
  • Maximum VAD current and powerMaximum VAD loop current and power are 18mA and 630mW at High Power, 14mA and 490mW at Medium Power, and 8mA and 280mW at Low Power. Combined sounder/VAD maxima at High, Medium and Low are 23mA, 19mA and 13mA for Turbo, or 21mA, 17mA and 11mA for Non Turbo.
  • Loop powered with an integral isolatorThe S3-V-VAD-HPW-R has an integral short circuit isolator meeting EN 54-17. The indoor S-Cubed range uses a 35V to 48V loop supply and loop in/out connections.
  • Indoor S-Cubed housing and base optionsThe indoor S-Cubed range is rated IP 21, with a 112mm square face and wall projection of 90mm on the standard base or 75mm on the optional shallow base. The S3-BASE-SR shallow base is red and comes in packs of five.
  • S-Cubed tone and volume adjustmentFor S-Cubed voice sounders, the S3-CONTROL infrared remote selects tone, speech message and volume from up to 3m away while the panel is in test mode. Hold the remote's power button to store the device settings. After a volume adjustment, save the new level at the panel.

Description

The Gent S3-V-VAD-HPW-R is a wall voice sounder with an integral High Power white visual alarm device and red body, for Gent Vigilon Plus, Compact Plus and Nano systems. It provides three alarm tones, four spoken messages and a bell tone. The High Power VAD has three coverage settings. Certified coverage requires compliant operation and compatible panel software. The indoor S-Cubed range is rated IP 21 for internal walls. The device is loop powered, with an integral short circuit isolator. The indoor range has a 112mm square face and projects 90mm on the standard base or 75mm on the optional shallow base. Supplied with a matching red standard base and one screw fitted in the base.

The S3-V-VAD-HPW-R is the red bodied voice sounder with a High Power white visual alarm device in Gent's S-Cubed Mark 3 range. It is loop powered and compatible with Gent Vigilon Plus, Compact Plus and Nano systems. It combines tone, speech and visual alarms.

Read the full technical description

The S3-V-VAD-HPW-R is the red bodied voice sounder with a High Power white visual alarm device in Gent's S-Cubed Mark 3 range. It is loop powered and compatible with Gent Vigilon Plus, Compact Plus and Nano systems. It combines tone, speech and visual alarms.

S-Cubed sounders provide three LPCB approved signals: an intermittent 970Hz tone at 1Hz, alternating 730Hz and 970Hz tones at 2Hz, and a continuous 970Hz tone. Each tone frequency has a tolerance of +/-10%. The range sounder rating is 103dB(A) +/-3dB, measured at 90 degrees and 1m. S-Cubed voice sounders store four spoken messages and a bell tone. The female announcements cover emergency evacuation, awaiting instructions and a test; the male announcement is for fire alarm evacuation. Message 3 with Signal 1 and Message 5 with Signal 2 are approved to EN 54-3 Annex C. The message and attention tone period defaults to 10 seconds and can be set up to 30 seconds; audio and bell-tone storage is up to 20 seconds.

The High Power white VAD coverage is High: W-5-12.5, 781 cubic metres; Medium: W-4.5-11.3, 574 cubic metres; Low: W-3-8.5, 216 cubic metres. Coverage requires compliant operation, compatible panel software, installation within the category's maximum mounting height and minimum effective illuminance of 0.4 lux. For EN Vigilon 4-loop and 4-6-loop panels, EN 54-23 coverage requires MCC V4.52 or later and LPC V4.48 or later. For EN Vigilon Compact, it requires MCB V4.52 or later and LPC V4.48 or later. On Nano, MCB V3.12 or later and LP V1.08 or later support Low Power coverage only. The S-Cubed VAD flash interval is two seconds. Maximum VAD loop current and power are 18mA and 630mW at High Power, 14mA and 490mW at Medium Power, and 8mA and 280mW at Low Power. Combined sounder/VAD maxima at High, Medium and Low are 23mA, 19mA and 13mA for Turbo, or 21mA, 17mA and 11mA for Non Turbo.

The indoor S-Cubed range uses a 35V to 48V loop supply and loop in/out terminals 01, L1, 02 and L2; the loop screen connects to the metal box earth. The S3-V-VAD-HPW-R has an integral short circuit isolator meeting EN 54-17. The indoor range is rated IP 21 for internal wall positions. Its body and lens are polycarbonate and the base is ABS. The indoor S-Cubed range has a 112mm square face and projects 90mm on the standard base or 75mm on an optional shallow base. The S3-BASE-SR shallow base matches this red body and comes in packs of five. Allow at least 10cm below the ceiling when fitting a shallow base so that the locking screw remains accessible. Keep the TOP mark facing upwards and the cable tails within 10cm. The base must remain surface mounted and the enclosure unpainted.

Changes to VAD settings on site use the Vigilon Commissioning Tool V1.32 or later with compatible loop software. For EN Vigilon 4-loop and 4-6-loop panels, EN 54-23 coverage requires MCC V4.52 or later and LPC V4.48 or later. For EN Vigilon Compact, it requires MCB V4.52 or later and LPC V4.48 or later. On Nano, MCB V3.12 or later and LP V1.08 or later support Low Power coverage only. The Nano Commissioning Tool is V3.0 or later. The device remains compatible with earlier panel software; certified coverage depends on the panel and loop versions above. For S-Cubed voice sounders, the S3-CONTROL infrared remote selects tone, speech message and volume from up to 3m away while the panel is in test mode. Hold the remote's power button to store the device settings. After a volume adjustment, save the new level at the panel. S-Cubed sounders and visual alarm devices synchronise across all loops of one panel; synchronisation does not extend across a network of panels.

Specifications

Manufacturer's designationS3 Voice Sounder/High Perf. White VAD/Red Body
Device typeWall mounted voice sounder with integral visual alarm device, from the Gent S-Cubed Mark 3 range. For internal applications, mounted on the internal walls of a building
Sound outputS-Cubed sounder range rating: 103dB(A) +/-3dB at 90 degrees and 1m.
TonesS-Cubed sounder signals: 1, intermittent 970Hz at 1Hz; 2, alternating 730Hz and 970Hz at 2Hz; 3, continuous 970Hz. Tone frequencies have a +/-10% tolerance. All three signals are LPCB approved.
Voice messagesS-Cubed voice sounder message set: 1, bell tone; 2, female emergency evacuation with Signal 3; 3, female announcement to await instructions with Signal 1; 4, female test announcement; 5, male fire alarm evacuation with Signal 2.
EN 54-3 Annex CThe await further instructions message (with Signal 1) and the male fire alarm evacuation message (with Signal 2) are approved to EN 54-3 Annex C
Message and attention tone periodS-Cubed voice sounders: default period 10 seconds, adjustable up to 30 seconds with the commissioning tool. Audio and bell-tone storage is up to 20 seconds.
Volume and message selectionFor S-Cubed voice sounders, the S3-CONTROL infrared remote selects tone, speech message and volume from up to 3m away while the panel is in test mode. Hold the remote's power button to store the device settings. After a volume adjustment, save the new level at the panel.
VAD category and coverage, high powerEN 54-23 category W-5-12.5; coverage volume 781 cubic metres
VAD category and coverage, medium powerEN 54-23 category W-4.5-11.3; coverage volume 574 cubic metres
VAD category and coverage, low powerEN 54-23 category W-3-8.5; coverage volume 216 cubic metres
VAD coverage conditionsCoverage requires compliant operation, compatible panel software, installation within the category's maximum mounting height and minimum effective illuminance of 0.4 lux. For EN Vigilon 4-loop and 4-6-loop panels, EN 54-23 coverage requires MCC V4.52 or later and LPC V4.48 or later. For EN Vigilon Compact, it requires MCB V4.52 or later and LPC V4.48 or later. On Nano, MCB V3.12 or later and LP V1.08 or later support Low Power coverage only.
Coverage notationFor wall category W-x-y, x is the maximum mounting height and y is the maximum width and length, in metres. The minimum category value of x is 2.4m. Coverage uses a minimum effective illuminance of 0.4 lux.
VAD flash rateS-Cubed VAD range: one flash every two seconds (0.5Hz).
Lens and body colourClear lens, white flash (High Power white VAD, HPW); red body, RAL 3020
Material and flammabilityS-Cubed indoor range: polycarbonate body and lens, ABS base; V2 flammability rating.
Ingress protectionS-Cubed indoor range: IP 21.
Loop operating voltageS-Cubed indoor range: 35V to 48V.
Power sourceLoop powered
Maximum loop current and powerMaximum values: VAD only: 18mA (630mW) high, 14mA (490mW) medium, 8mA (280mW) low. Maximum total for VAD and sounder: Turbo 23mA (805mW) / 19mA (665mW) / 13mA (455mW); Non Turbo 21mA (735mW) / 17mA (595mW) / 11mA (385mW) at high / medium / low
Approximate quantity per loop - Gent range datasheetApproximate maximum quantities for S-Cubed High Power sounder/VAD devices are 38 at High Power, 47 at Medium Power and 72 at Low Power (dependent on loop load).
Short circuit isolator, EN 54-17 dataIntegral isolator. S-Cubed indoor range limits: Vmax 48V; Vnom 40V; Vmin 24V; VSOmax 16V; VSOmin 8V; ICmax 0.8A; ISmax 1.25A; ILmax 50uA; ZCmax 0.13 ohm.
TerminalsS-Cubed indoor range: loop in/out terminals 01, L1, 02 and L2; connect the loop screen to the metal box earth.
Temperature and humidityS-Cubed indoor range: operating temperature -10C to +50C; storage -20C to +70C; relative humidity up to 95% without condensation between +5C and +45C.
Dimensions and weightS-Cubed indoor range: 112mm square face; projection 90mm with the standard base or 75mm with the optional shallow base. Indoor S-Cubed VADs weigh 293g with the deep base or 271g with the shallow base.
Mounting and baseSupplied with a matching red standard base and one screw fitted in the base. For indoor S-Cubed installation, secure the base to a flat wall or metal box, with TOP facing upwards and the VAD level. Keep shallow bases at least 10cm below the ceiling for screw access and limit cable tails to 10cm. Keep the enclosure unpainted and the base surface mounted.
Panel compatibilityFor EN Vigilon 4-loop and 4-6-loop panels, EN 54-23 coverage requires MCC V4.52 or later and LPC V4.48 or later. For EN Vigilon Compact, it requires MCB V4.52 or later and LPC V4.48 or later. On Nano, MCB V3.12 or later and LP V1.08 or later support Low Power coverage only.

Specifications per manufacturer documentation, subject to change. E&OE.

Standards and approvals

StandardWhat it covers
LPCB approvedApproved by the Loss Prevention Certification Board for fire detection and alarm system products.
LPCB certificate 042bs / listing 042bs/04
EN 54-3:2001 + A1:2002 + A2:2006
EN 54-17:2005 + AC:2007
EN 54-23:2010
Declaration of Performance 089-CPR-2014 Issue 3

Approval body: Loss Prevention Certification Board (BRE Global Limited), System 1.

Documents

DocumentTypeSizeDownload
Installation manual (S3-BASE-SR, S3-BASE-SW, S3-S-VAD-HPR-R, S3-S-VAD-HPR-W, S3-S-VAD-LPR-R, S3-S-W, S3-V-R, S3-V-VAD-HPR-R, S3-V-VAD-HPW-R, S3-V-W, S3-VAD-HPR-R)Installation740 KBDownload PDF

Optional accessories

FAQs

What EN 54-23 coverage does the white VAD on the S3-V-VAD-HPW-R give, and how does it compare with the red flash version?

The white VAD gives W-5-12.5 and 781 cubic metres at High Power, W-4.5-11.3 and 574 cubic metres at Medium, or W-3-8.5 and 216 cubic metres at Low. The red S3-V-VAD-HPR-R gives W-6.7-14 and 1313 cubic metres at High Power. Coverage requires compliant operation, compatible panel software, installation within the category's maximum mounting height and minimum effective illuminance of 0.4 lux. Both models have red bodies and provide three tones, four spoken messages and a bell tone.

Which tones and spoken messages does the S3-V-VAD-HPW-R hold, and which of them meet EN 54-3 Annex C?

This model provides three tones, four spoken messages and a bell tone. The S-Cubed tones are intermittent 970Hz at 1Hz, alternating 730Hz and 970Hz at 2Hz, and continuous 970Hz. The female messages cover emergency evacuation, awaiting instructions and a test; the male message is fire alarm evacuation. Message 3, awaiting instructions with Signal 1, and Message 5, male evacuation with Signal 2, are approved to EN 54-3 Annex C. The female emergency evacuation message is paired with Signal 3.

How does the S3-V-VAD-HPW-R flash, and which alarm settings can be changed?

The S-Cubed VAD flash interval is two seconds, or 0.5Hz. S-Cubed voice sounders have a message and attention tone period of 10 seconds by default, adjustable up to 30 seconds using the commissioning tool. The S3-CONTROL infrared remote can adjust tone, speech message and volume within 3m while the panel is in test mode. Hold its power button to store device settings, and save any adjusted volume at the panel as well. This model has a white flash behind a clear lens and a red body.

What happens to the coverage on a Gent Nano panel, or on older panel software?

Nano requires MCB V3.12 or later and LP V1.08 or later, supporting Low Power coverage of W-3-8.5 and 216 cubic metres. EN Vigilon four-loop, Compact and four-to-six-loop panels require MCC or MCB V4.52 or later and LPC V4.48 or later for certified coverage. Coverage requires compliant operation, installation within the category's maximum mounting height and minimum effective illuminance of 0.4 lux. The device remains compatible with earlier panel software. The white VAD is limited to its Low Power setting on Nano.

Does the S3-V-VAD-HPW-R need a base, and which one should I order?

Supplied with a matching red standard base and one screw fitted in the base. The optional S3-BASE-SR shallow base is red, matching this red bodied model, and comes in packs of five. Indoor S-Cubed devices project 90mm from the wall on the standard deep base or 75mm on the shallow base. Indoor S-Cubed VADs weigh 293g with the deep base or 271g with the shallow base. Leave at least 10cm below the ceiling when fitting the shallow base so that the locking screw remains accessible. The indoor range has a 112mm square face.

Also in this range

  • S3-V-VAD-HPR-RS3 red Body Voice Sounder High Power red VADThe red flash version of the same voice sounder on the same red body, stocked at GBP 126.78 ex VAT. It covers considerably more: EN 54-23 W-6.7-14 and 1313 cubic metres at high power, against W-5-12.5 and 781 cubic metres here (verified first-hand in 4188-1082 issue 8 Table 1 and in LPCB certificate 042bs, appendix references 042bs/05 and 042bs/04). Cheaper as well, so the white flash is a specification or appearance choice, never a coverage upgrade.£126.78ex VAT£152.14 inc VATIn stock
  • S3EP-V-VAD-HPW-RS3 EP (IP66) red Body Voice Sounder High Power White VADThe Environmentally Protected version of this part, stocked at GBP 174.62 ex VAT, for outdoor positions and harsh internal areas. Same voice sounder and the same High Power white VAD with identical EN 54-23 categories (W-5-12.5 / 781, W-4.5-11.3 / 574, W-3-8.5 / 216, verified in both manuals), in the larger EP enclosure at 125 x 125 x 95mm rather than 112mm square by 90mm. This part is IP 21 and its instructions warn against mounting it on an external wall surface, so the EP unit is the one for anything outside.£174.62ex VAT£209.54 inc VATIn stock