Gent S3 red Body Voice Sounder High Power red VAD
| Part no. | S3-V-VAD-HPR-R |
|---|---|
| Brand | Gent |
| Range | S3 Sounders & VADs |
| Sub-range | Wall Voice Sounders with VAD |

Image for illustration; item supplied may differ
At a glance
- High Power red visual alarm with speechThis red bodied model combines three alarm tones, four spoken messages and a bell tone with a High Power red VAD.
- Three EN 54-23 coverage settingsHigh: W-6.7-14, 1313 cubic metres; Medium: W-6.5-12.5, 1015 cubic metres; Low: W-5-9.5, 451 cubic metres. Coverage requires compliant operation, compatible panel software, installation within the category's maximum mounting height and minimum effective illuminance of 0.4 lux. For EN Vigilon 4-loop and 4-6-loop panels, EN 54-23 coverage requires MCC V4.52 or later and LPC V4.48 or later. For EN Vigilon Compact, it requires MCB V4.52 or later and LPC V4.48 or later. On Nano, MCB V3.12 or later and LP V1.08 or later support Low Power coverage only.
- Maximum VAD current and powerMaximum VAD loop current and power are 18mA and 630mW at High Power, 14mA and 490mW at Medium Power, and 8mA and 280mW at Low Power. Combined sounder/VAD maxima at High, Medium and Low are 23mA, 19mA and 13mA for Turbo, or 21mA, 17mA and 11mA for Non Turbo.
- Loop powered with an integral isolatorThe S3-V-VAD-HPR-R has an integral short circuit isolator meeting EN 54-17. The indoor S-Cubed range uses a 35V to 48V loop supply and loop in/out connections.
- Indoor S-Cubed housing and base optionsThe indoor S-Cubed range is rated IP 21, with a 112mm square face and wall projection of 90mm on the standard base or 75mm on the optional shallow base. The S3-BASE-SR shallow base is red and comes in packs of five.
- S-Cubed tone and volume adjustmentFor S-Cubed voice sounders, the S3-CONTROL infrared remote selects tone, speech message and volume from up to 3m away while the panel is in test mode. Hold the remote's power button to store the device settings. After a volume adjustment, save the new level at the panel.
Description
The Gent S3-V-VAD-HPR-R is a wall voice sounder with an integral High Power red visual alarm device and red body, for Gent Vigilon Plus, Compact Plus and Nano systems. It provides three alarm tones, four spoken messages and a bell tone. The High Power VAD has three coverage settings. Certified coverage requires compliant operation and compatible panel software. The indoor S-Cubed range is rated IP 21 for internal walls. The device is loop powered, with an integral short circuit isolator. The indoor range has a 112mm square face and projects 90mm on the standard base or 75mm on the optional shallow base. Supplied with a matching red standard base and one screw fitted in the base.
The S3-V-VAD-HPR-R is the red bodied voice sounder with a High Power red visual alarm device in Gent's S-Cubed Mark 3 range. It is loop powered and compatible with Gent Vigilon Plus, Compact Plus and Nano systems. It combines tone, speech and visual alarms.
Read the full technical description
The S3-V-VAD-HPR-R is the red bodied voice sounder with a High Power red visual alarm device in Gent's S-Cubed Mark 3 range. It is loop powered and compatible with Gent Vigilon Plus, Compact Plus and Nano systems. It combines tone, speech and visual alarms.
S-Cubed sounders provide three LPCB approved signals: an intermittent 970Hz tone at 1Hz, alternating 730Hz and 970Hz tones at 2Hz, and a continuous 970Hz tone. Each tone frequency has a tolerance of +/-10%. The range sounder rating is 103dB(A) +/-3dB, measured at 90 degrees and 1m. S-Cubed voice sounders store four spoken messages and a bell tone. The female announcements cover emergency evacuation, awaiting instructions and a test; the male announcement is for fire alarm evacuation. Message 3 with Signal 1 and Message 5 with Signal 2 are approved to EN 54-3 Annex C. The message and attention tone period defaults to 10 seconds and can be set up to 30 seconds; audio and bell-tone storage is up to 20 seconds.
The High Power red VAD coverage is High: W-6.7-14, 1313 cubic metres; Medium: W-6.5-12.5, 1015 cubic metres; Low: W-5-9.5, 451 cubic metres. Coverage requires compliant operation, compatible panel software, installation within the category's maximum mounting height and minimum effective illuminance of 0.4 lux. For EN Vigilon 4-loop and 4-6-loop panels, EN 54-23 coverage requires MCC V4.52 or later and LPC V4.48 or later. For EN Vigilon Compact, it requires MCB V4.52 or later and LPC V4.48 or later. On Nano, MCB V3.12 or later and LP V1.08 or later support Low Power coverage only. The S-Cubed VAD flash interval is two seconds. Maximum VAD loop current and power are 18mA and 630mW at High Power, 14mA and 490mW at Medium Power, and 8mA and 280mW at Low Power. Combined sounder/VAD maxima at High, Medium and Low are 23mA, 19mA and 13mA for Turbo, or 21mA, 17mA and 11mA for Non Turbo.
The indoor S-Cubed range uses a 35V to 48V loop supply and loop in/out terminals 01, L1, 02 and L2; the loop screen connects to the metal box earth. The S3-V-VAD-HPR-R has an integral short circuit isolator meeting EN 54-17. The indoor range is rated IP 21 for internal wall positions. Its body and lens are polycarbonate and the base is ABS. The indoor S-Cubed range has a 112mm square face and projects 90mm on the standard base or 75mm on an optional shallow base. The S3-BASE-SR shallow base matches this red body and comes in packs of five. Allow at least 10cm below the ceiling when fitting a shallow base so that the locking screw remains accessible. Keep the TOP mark facing upwards and the cable tails within 10cm. The base must remain surface mounted and the enclosure unpainted.
Changes to VAD settings on site use the Vigilon Commissioning Tool V1.32 or later with compatible loop software. For EN Vigilon 4-loop and 4-6-loop panels, EN 54-23 coverage requires MCC V4.52 or later and LPC V4.48 or later. For EN Vigilon Compact, it requires MCB V4.52 or later and LPC V4.48 or later. On Nano, MCB V3.12 or later and LP V1.08 or later support Low Power coverage only. The Nano Commissioning Tool is V3.0 or later. The device remains compatible with earlier panel software; certified coverage depends on the panel and loop versions above. For S-Cubed voice sounders, the S3-CONTROL infrared remote selects tone, speech message and volume from up to 3m away while the panel is in test mode. Hold the remote's power button to store the device settings. After a volume adjustment, save the new level at the panel. S-Cubed sounders and visual alarm devices synchronise across all loops of one panel; synchronisation does not extend across a network of panels.
Specifications
| Manufacturer's designation | S3 Voice Sounder/High Perf. Red VAD/Red Body |
|---|---|
| Device type | Wall mounted voice sounder with an integral High Power red visual alarm device, Gent S-Cubed Mark 3 range, for indoor positions |
| Sound output | S-Cubed sounder range rating: 103dB(A) +/-3dB at 90 degrees and 1m. |
| Tones | S-Cubed sounder signals: 1, intermittent 970Hz at 1Hz; 2, alternating 730Hz and 970Hz at 2Hz; 3, continuous 970Hz. Tone frequencies have a +/-10% tolerance. All three signals are LPCB approved. |
| Voice messages | S-Cubed voice sounder message set: 1, bell tone; 2, female emergency evacuation with Signal 3; 3, female announcement to await instructions with Signal 1; 4, female test announcement; 5, male fire alarm evacuation with Signal 2. |
| EN 54-3 Annex C | Message 3 with Signal 1 and Message 5 with Signal 2 are approved to EN 54-3 Annex C |
| Message and attention tone period | S-Cubed voice sounders: default period 10 seconds, adjustable up to 30 seconds with the commissioning tool. Audio and bell-tone storage is up to 20 seconds. |
| Volume and message selection | For S-Cubed voice sounders, the S3-CONTROL infrared remote selects tone, speech message and volume from up to 3m away while the panel is in test mode. Hold the remote's power button to store the device settings. After a volume adjustment, save the new level at the panel. |
| VAD category and coverage, high power | EN 54-23 category W-6.7-14; coverage volume 1313 cubic metres |
| VAD category and coverage, medium power | EN 54-23 category W-6.5-12.5; coverage volume 1015 cubic metres |
| VAD category and coverage, low power | EN 54-23 category W-5-9.5; coverage volume 451 cubic metres |
| VAD coverage conditions | Coverage requires compliant operation, compatible panel software, installation within the category's maximum mounting height and minimum effective illuminance of 0.4 lux. For EN Vigilon 4-loop and 4-6-loop panels, EN 54-23 coverage requires MCC V4.52 or later and LPC V4.48 or later. For EN Vigilon Compact, it requires MCB V4.52 or later and LPC V4.48 or later. On Nano, MCB V3.12 or later and LP V1.08 or later support Low Power coverage only. |
| Coverage notation | For wall category W-x-y, x is the maximum mounting height and y is the maximum width and length, in metres. The minimum category value of x is 2.4m. Coverage uses a minimum effective illuminance of 0.4 lux. |
| VAD flash rate | S-Cubed VAD range: one flash every two seconds (0.5Hz). |
| Synchronisation | S-Cubed sounders and VADs synchronise across all loops of one panel, without synchronisation across a network of panels. |
|---|---|
| Lens and body colour | Clear lens, red flash (High Power red VAD, HPR); red body, RAL 3020 |
| Material and flammability | S-Cubed indoor range: polycarbonate body and lens, ABS base; V2 flammability rating. |
| Ingress protection | S-Cubed indoor range: IP 21. |
| Loop operating voltage | S-Cubed indoor range: 35V to 48V. |
| Power source | Loop powered |
| Maximum loop current and power | Maximum values: VAD only: 18mA (630mW) high, 14mA (490mW) medium, 8mA (280mW) low. VAD and sounder total: Turbo 23mA (805mW) / 19mA (665mW) / 13mA (455mW); Non Turbo 21mA (735mW) / 17mA (595mW) / 11mA (385mW) at high / medium / low |
| Approximate quantity per loop - Gent range datasheet | Approximate maximum quantities for S-Cubed High Power sounder/VAD devices are 38 at High Power, 47 at Medium Power and 72 at Low Power (dependent on loop load). |
| Short circuit isolator, EN 54-17 data | Integral isolator. S-Cubed indoor range limits: Vmax 48V; Vnom 40V; Vmin 24V; VSOmax 16V; VSOmin 8V; ICmax 0.8A; ISmax 1.25A; ILmax 50uA; ZCmax 0.13 ohm. |
| Terminals | S-Cubed indoor range: loop in/out terminals 01, L1, 02 and L2; connect the loop screen to the metal box earth. |
| Temperature and humidity | S-Cubed indoor range: operating temperature -10C to +50C; storage -20C to +70C; relative humidity up to 95% without condensation between +5C and +45C. |
| Dimensions and weight | S-Cubed indoor range: 112mm square face; projection 90mm with the standard base or 75mm with the optional shallow base. Indoor S-Cubed VADs weigh 293g with the deep base or 271g with the shallow base. |
| Mounting and base | Supplied with a matching red standard base and one screw fitted in the base. For indoor S-Cubed installation, secure the base to a flat wall or metal box, with TOP facing upwards and the VAD level. Keep shallow bases at least 10cm below the ceiling for screw access and limit cable tails to 10cm. Keep the enclosure unpainted and the base surface mounted. |
| Panel compatibility | For EN Vigilon 4-loop and 4-6-loop panels, EN 54-23 coverage requires MCC V4.52 or later and LPC V4.48 or later. For EN Vigilon Compact, it requires MCB V4.52 or later and LPC V4.48 or later. On Nano, MCB V3.12 or later and LP V1.08 or later support Low Power coverage only. |
Specifications per manufacturer documentation, subject to change. E&OE.
Standards and approvals
| Standard | What it covers |
|---|---|
| LPCB approved | Approved by the Loss Prevention Certification Board for fire detection and alarm system products. |
| LPCB certificate 042bs / listing 042bs/05 | |
| EN 54-3:2001 + A1:2002 + A2:2006 | |
| EN 54-17:2005 + AC:2007 | |
| EN 54-23:2010 | |
| Declaration of Performance 090-CPR-2014 Issue 4 |
Approval body: Loss Prevention Certification Board (BRE Global Limited), System 1.
Documents
| Document | Type | Size | Download |
|---|---|---|---|
| Installation manual (S3-BASE-SR, S3-BASE-SW, S3-S-VAD-HPR-R, S3-S-VAD-HPR-W, S3-S-VAD-LPR-R, S3-S-W, S3-V-R, S3-V-VAD-HPR-R, S3-V-VAD-HPW-R, S3-V-W, S3-VAD-HPR-R) | Installation | 740 KB | Download PDF |
Optional accessories
- S3-CONTROLHandiLink IR Remote Control for the S-Cubed Range of SoundersRemote Control (S3-CONTROL) for volume control£107.64ex VAT£129.17 inc VATIn stock
FAQs
How does the S3-V-VAD-HPR-R flash, and how are the alarm settings changed?
The S-Cubed VAD flash interval is two seconds, or 0.5Hz. On S-Cubed voice sounders, tone, speech message and volume can be adjusted with the commissioning tool or the S3-CONTROL infrared remote. Use the remote within 3m while the panel is in test mode. Hold its power button to store device settings, and save any adjusted volume at the panel as well. The S3-V-VAD-HPR-R combines a High Power red beacon with three alarm tones, four spoken messages and a bell tone.
Do I need to order a base with the S3-V-VAD-HPR-R, and what is the S3-BASE-SR for?
Supplied with a matching red standard base and one screw fitted in the base. The red S3-BASE-SR shallow base is optional and comes in packs of five. It provides a lower profile for this red bodied model. Indoor S-Cubed devices project 90mm from the wall on the standard base or 75mm on the shallow base. Indoor S-Cubed VADs weigh 293g with the deep base or 271g with the shallow base. Leave at least 10cm below the ceiling when fitting a shallow base so that the locking screw remains accessible. The face is 112mm square.
What is the difference between the S3-V-VAD-HPR-R and the S3-V-VAD-HPW-R?
Both models provide three tones, four spoken messages and a bell tone, with a red body. The S3-V-VAD-HPR-R has a red flash behind a clear lens; the S3-V-VAD-HPW-R has a white flash behind a clear lens. Their High Power coverage is W-6.7-14 and 1313 cubic metres for red, or W-5-12.5 and 781 cubic metres for white. Coverage requires compliant operation, compatible panel software, installation within the category's maximum mounting height and minimum effective illuminance of 0.4 lux. Both offer High, Medium and Low VAD settings.
Does the S3-V-VAD-HPR-R work on a Gent Nano panel, and does the coverage change?
Nano supports this device from MCB V3.12 and LP V1.08, with Low Power VAD coverage of W-5-9.5 and 451 cubic metres. EN Vigilon four-loop, Compact and four-to-six-loop panels require MCC or MCB V4.52 or later and LPC V4.48 or later for certified coverage. Coverage requires compliant operation, installation within the category's maximum mounting height and minimum effective illuminance of 0.4 lux. The device remains compatible with earlier panel software. Nano limits the VAD to its Low Power setting.
How many S3-V-VAD-HPR-R can go on one loop?
The approximate maximum quantities for S-Cubed High Power sounder and VAD devices are 38 per loop at High Power, 47 at Medium Power and 72 at Low Power, dependent on loop load. Combined sounder and VAD maximum currents at High Power are 23mA for Turbo or 21mA for Non Turbo. The VAD maximum currents are 18mA at High, 14mA at Medium and 8mA at Low. Use the Gent Battery Standby and Loop Load Calculator for system design.
Also in this range
- S3EP-V-VAD-HPR-RS3 EP (IP66) red Body Voice Sounder High Power red VADThe Environmentally Protected twin: the same voice sounder and the same High Power red VAD, with identical EN 54-23 categories, in the EP enclosure at 125 x 125 x 95mm for outdoor positions and harsh internal areas. This part is the indoor unit and Gent tells you not to mount it on an external wall surface. Dearer, and the right part where the position is outside.£162.06ex VAT£194.47 inc VATIn stock
- S3-V-VAD-HPW-RS3 red Body Voice Sounder High Power White VADSame voice sounder, same red body, white VAD lens instead of red. Different EN 54-23 coverage: W-5-12.5 and 781 cubic metres at high power against this part's W-6.7-14 and 1313 cubic metres, and W-3-8.5 / 216 cubic metres at low. The coverage difference is the point of the note - a bare link would imply equivalence.£136.34ex VAT£163.61 inc VATIn stock