Skip to content

Trade prices shown ex VAT. Order by 3pm for same-day dispatch on stocked lines, UK mainland. Free UK delivery on orders over £250 ex VAT.

Part Number or the Week S3EP-V-VAD-HPR-R

Gent S3 Sounder White Body

Part no.S3-S-W
BrandGent
RangeS3 Sounders & VADs
Sub-rangeWall Sounders
Gent by Honeywell S3-S-W Wall Sounder — white circular unit with domed cover

Image for illustration; item supplied may differ

At a glance

  • S-Cubed Mark 3 tone sounderA white bodied wall tone sounder for Gent Vigilon Plus, Compact Plus and Nano addressable systems. This model has no visual alarm device.
  • Three S-Cubed alarm tonesS-Cubed sounders provide three LPCB approved signals: an intermittent 970Hz tone at 1Hz, alternating 730Hz and 970Hz tones at 2Hz, and a continuous 970Hz tone. Each tone frequency has a tolerance of +/-10%. The range sounder rating is 103dB(A) +/-3dB, measured at 90 degrees and 1m.
  • Loop powered with an integral isolatorThe S3-S-W has an integral short circuit isolator meeting EN 54-17. The indoor S-Cubed range uses a 35V to 48V loop supply and loop in/out connections.
  • S-Cubed tone and volume adjustmentFor S-Cubed sounders, the S3-CONTROL infrared remote selects tone and volume from up to 3m away while the panel is in test mode. Hold the remote's power button to store the device settings. After a volume adjustment, save the new level at the panel.
  • Indoor S-Cubed housing and base optionsThe indoor S-Cubed range is rated IP 21, with a 112mm square face and wall projection of 90mm on the standard base or 75mm on the optional shallow base. The S3-BASE-SW shallow base is white and comes in packs of five.
  • EN 54-3 sounder and EN 54-17 isolatorThis tone sounder meets EN 54-3 and has a short circuit isolator meeting EN 54-17. It provides tone alarms without spoken messages.

Description

The Gent S3-S-W is a white bodied wall tone sounder in the S-Cubed Mark 3 range, for Gent Vigilon Plus, Compact Plus and Nano addressable systems. It provides three alarm tones: intermittent, alternating and continuous. This model has no spoken messages or visual alarm device. It is loop powered and has an integral short circuit isolator. The indoor S-Cubed range is rated IP 21 for internal walls. Tone and volume can be set with the commissioning tool or S3-CONTROL infrared remote. The matching S3-BASE-SW shallow base is optional. The indoor range has a 112mm square face and projects 90mm on the standard base or 75mm on the optional shallow base. Supplied with a matching white standard base and one screw fitted in the base.

The S3-S-W is the white bodied tone sounder in Gent's S-Cubed Mark 3 range. It is loop powered and compatible with Gent Vigilon Plus, Compact Plus and Nano systems. It provides tone alarms without spoken messages.

Read the full technical description

The S3-S-W is the white bodied tone sounder in Gent's S-Cubed Mark 3 range. It is loop powered and compatible with Gent Vigilon Plus, Compact Plus and Nano systems. It provides tone alarms without spoken messages.

S-Cubed sounders provide three LPCB approved signals: an intermittent 970Hz tone at 1Hz, alternating 730Hz and 970Hz tones at 2Hz, and a continuous 970Hz tone. Each tone frequency has a tolerance of +/-10%. The range sounder rating is 103dB(A) +/-3dB, measured at 90 degrees and 1m.

The indoor S-Cubed range uses a 35V to 48V loop supply and loop in/out terminals 01, L1, 02 and L2; the loop screen connects to the metal box earth. The S3-S-W has an integral short circuit isolator meeting EN 54-17. The indoor range is rated IP 21 for internal wall positions. Its body is polycarbonate and the base is ABS. The indoor S-Cubed range has a 112mm square face and projects 90mm on the standard base or 75mm on an optional shallow base. The S3-BASE-SW shallow base matches this white body and comes in packs of five. Allow at least 10cm below the ceiling when fitting a shallow base so that the locking screw remains accessible. Keep the TOP mark facing upwards and the cable tails within 10cm. The base must remain surface mounted and the enclosure unpainted.

Vigilon commissioning uses the Vigilon Commissioning Tool V1.30 or later. For S-Cubed sounders, the S3-CONTROL infrared remote selects tone and volume from up to 3m away while the panel is in test mode. Hold the remote's power button to store the device settings. After a volume adjustment, save the new level at the panel. S-Cubed sounders and visual alarm devices synchronise across all loops of one panel; synchronisation does not extend across a network of panels.

Specifications

Manufacturer's designationS3 Sounder/White Body
Device typeWall mounted addressable sounder for internal use, part of the Gent S-Cubed Mark 3 range
Sound levelS-Cubed sounder range rating: 103dB(A) +/-3dB at 90 degrees and 1m.
TonesS-Cubed sounder signals: 1, intermittent 970Hz at 1Hz; 2, alternating 730Hz and 970Hz at 2Hz; 3, continuous 970Hz. Tone frequencies have a +/-10% tolerance. All three signals are LPCB approved.
Speech messagesNo spoken messages.
Visual alarm deviceNone fitted
Volume and tone selectionFor S-Cubed sounders, the S3-CONTROL infrared remote selects tone and volume from up to 3m away while the panel is in test mode. Hold the remote's power button to store the device settings. After a volume adjustment, save the new level at the panel.
Power sourceLoop powered
Loop operating voltageS-Cubed indoor range: 35V to 48V.
TerminalsS-Cubed indoor range: loop in/out terminals 01, L1, 02 and L2; connect the loop screen to the metal box earth.
Short circuit isolator, EN 54-17 dataIntegral isolator. S-Cubed indoor range limits: Vmax 48V; Vnom 40V; Vmin 24V; VSOmax 16V; VSOmin 8V; ICmax 0.8A; ISmax 1.25A; ILmax 50uA; ZCmax 0.13 ohm.
Approximate quantity per loop - Gent range datasheetThe approximate maximum quantity for S-Cubed standard tone sounders is 200 per loop (dependent on loop load).
Ingress protectionS-Cubed indoor range: IP 21.
ApplicationS-Cubed indoor range: internal wall positions.
ColourWhite body RAL 9010
MaterialS-Cubed indoor range: polycarbonate body; ABS base.
FlammabilityS-Cubed indoor range: V2.
Ambient operating temperatureS-Cubed indoor range: -10C to +50C
Storage temperatureS-Cubed indoor range: -20C to +70C
Relative humidityS-Cubed indoor range: 95% non condensing (+5C to +45C)
DimensionsS-Cubed indoor range: 112mm square face; projection 90mm with the standard base or 75mm with the optional shallow base.
Optional shallow baseS3-BASE-SW is the optional white shallow base, supplied in packs of five. Indoor S-Cubed wall projection is 90mm with the standard base or 75mm with the shallow base.
MountingSupplied with a matching white standard base and one screw fitted in the base. For indoor S-Cubed installation, secure the base to a flat wall or metal box, with TOP facing upwards. Keep shallow bases at least 10cm below the ceiling for screw access and limit cable tails to 10cm. Keep the enclosure unpainted and the base surface mounted.
Commissioning toolS-Cubed commissioning on Vigilon: Vigilon Commissioning Tool V1.30 or later.
Panel softwareGent Vigilon Plus, Compact Plus and Nano addressable systems.
Siting guidanceTest S-Cubed sound levels in the protected areas against the site requirements.

Specifications per manufacturer documentation, subject to change. E&OE.

Standards and approvals

StandardWhat it covers
LPCB approvedApproved by the Loss Prevention Certification Board for fire detection and alarm system products.
EN 54-3:2001 + A1:2002 + A2:2006
EN 54-17:2005 + AC:2007
Declaration of Performance 083-CPR-2014 Issue 3

Approval body: Loss Prevention Certification Board (BRE Global Limited), System 1.

Documents

DocumentTypeSizeDownload
Installation manual (S3-BASE-SR, S3-BASE-SW, S3-S-VAD-HPR-R, S3-S-VAD-HPR-W, S3-S-VAD-LPR-R, S3-S-W, S3-V-R, S3-V-VAD-HPR-R, S3-V-VAD-HPW-R, S3-V-W, S3-VAD-HPR-R)Installation740 KBDownload PDF

Optional accessories

FAQs

Does the S3-S-W have a beacon or spoken messages?

The S3-S-W provides tone alarms without a beacon or spoken messages. Its sounder meets EN 54-3 and its integral short circuit isolator meets EN 54-17. The S3-S-VAD-HPR-W combines a tone sounder with a High Power red beacon on a white body. The S3-V-W is a white bodied voice sounder with four spoken messages and a bell tone. The S3-S-W provides three alarm tones in a white enclosure, RAL 9010, for indoor positions on internal walls.

Do I need the S3-BASE-SW shallow base with the S3-S-W?

Supplied with a matching white standard base and one screw fitted in the base. The S3-BASE-SW is an optional white shallow base, supplied in packs of five, that matches the S3-S-W body. Indoor S-Cubed devices project 90mm from the wall on the standard base or 75mm with the shallow base. Mount the shallow base on a flat wall or metal box, leaving at least 10cm below the ceiling for access to the locking screw. Keep the TOP mark facing upwards and limit the cable tails to 10cm. The shallow base provides a lower profile.

How are the tone and the volume set on the S3-S-W?

Across the S-Cubed sounder range, tone and volume can be set using the commissioning tool or the S3-CONTROL infrared remote. Use the remote within 3m while the panel is in test mode. Its function button switches between volume adjustment and tone selection; the plus and minus buttons change the selected value. Hold the power button to store the device settings, and save an adjusted volume at the panel as well. The S3-S-W provides intermittent, alternating and continuous tones.

What is the difference between the S3-S-W and the S3-S-R?

The S3-S-W has a white body, RAL 9010, while the S3-S-R has a red body, RAL 3020. Both provide three alarm tones without speech or a beacon, and both have integral short circuit isolators. Each meets EN 54-3 and EN 54-17. Their indoor S-Cubed housing has a 112mm square face and projects 90mm on the standard base or 75mm on a shallow base. The optional S3-BASE-SW shallow base matches the white S3-S-W and comes in packs of five.

How many S3-S-W sounders can go on one loop?

The approximate maximum for S-Cubed standard tone sounders is 200 per loop, dependent on loop load. Use the Gent Battery Standby and Loop Load Calculator for system design. The indoor S-Cubed range uses a 35V to 48V loop supply, with loop in and loop out connections and the loop screen connected to the metal box earth. The S3-S-W has an integral short circuit isolator meeting EN 54-17. This model provides three tones, without speech or a beacon.

Also in this range

  • S3-S-RS3 Sounder red BodyThe identical tone sounder in a red body, RAL 3020 rather than RAL 9010. Same three signals, same 103dB(A) sounder-only level, same 35V-48V loop supply, same integral isolator; declared on the same DoP (083-CPR-2014 Issue 3) with its own identification code and its own certificate number. Choose on the finish the specification calls for.£70.56ex VAT£84.67 inc VATIn stock
  • S3EP-S-RS3 EP (IP66) Sounder red BodyThe Environmentally Protected sounder, for an outdoor position or a harsh internal area, where this IP 21 unit is indoor only ('Don't mount a Type A device onto an external wall surface', 4188-1082 issue 8 p1 Don'ts). Gent builds the EP sounder in a RED body only - there is no white-bodied EP sounder in any source held - so it is a like-for-like function swap, not a like-for-like finish swap. Its authority is a different manual (4188-1083).£114.22ex VAT£137.06 inc VATIn stock