Compact Plus
Gent COMPACT-NODE Compact Plus Terminal Node, Vigilon

- Dimensions
- height 403 x width 338 x depth 101 mm
- Weight
- 8.6Kg approximately without batteries Kg
- Operating temperature
- 0ºC to +45ºC
- Ingress Protection
- IP31
- Mains supply voltage
- 230V -15% +10% 50Hz/60Hz V
- Input current
- 0.6A
- EN54 standard
- EN54-4:1997 + A1:2002 and A2:2006
Overview
What it is and how it fits the system.
The Gent COMPACT-NODE is a Compact Plus terminal node for Vigilon panel networks, supplied in black. It provides the network termination point for connecting Vigilon panels into a networked fire system.
Technical overview
The Gent COMPACT-NODE terminates a Vigilon panel network, giving a group of networked fire panels the single point at which the network is brought together. Part of the Gent by Honeywell Compact Plus range, it lets multiple Vigilon panels work as one coordinated fire detection system rather than as isolated controllers, extending detection and control across a larger site.
Networking runs over a copper network card, and a single network can reach as many as 31 panels, with distances of up to 1.2km permitted between them. The node is approved to the EN54-4 fire standard and is offered in the EN version only. It is housed in a black enclosure rated to IP31 and draws from a 230V mains supply.
Standby is around 24 hours plus 30 minutes in alarm when fitted with two 12V 12Ah batteries. For terminal wiring and connection detail, refer to the installation manual.
Specifications
Full technical data for this part.
| Order code | COMPACT-NODE |
|---|---|
| Description | COMPACT PLUS TERMINAL NODE FOR VIGILON PANEL NETWORKS (SUPPLIED IN BLACK) |
| Colour | SUPPLIED IN BLACK |
| Dimensions | height 403 x width 338 x depth 101 mm |
| Weight | 8.6Kg approximately without batteries Kg |
| Storage temperature | -10ºC to +55ºC |
| Operating temperature | 0ºC to +45ºC |
| Ingress Protection | IP31 |
| Mains supply voltage | 230V -15% +10% 50Hz/60Hz V |
| Input current | 0.6A |
| EN54 standard | EN54-4:1997 + A1:2002 and A2:2006 |
| Clean contacts rating | 1A @ 24Vdc, active with master alarms |
| Auxiliary relay contact rating | 1A @ 24Vdc |
| Master alarm circuits | 2 - (24 V nominal) 250 mA max. per circuit |
| Batteries | 2 x Powersonic 12V 12Ahr, Model number: PS-12120 F1 |
| Standby duration | 24 hours standby power and 30 minutes alarm |
| Network capacity | up to 31 panels, 1.2Km maximum between panels |
| Network card | copper network card |
| Version | EN version only |
Specifications sourced from manufacturer documentation.
Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know
Enhancements (optional)
Optional additions — this product works without them.

Vigilon Plus Terminal Node (EN54 version) for use with multiple IO cards and Fibre networks. Supplied in black. Batteries not included - requires 2 x 4015-602-YFR (Power Sonic Flame Retardant 12V 21Ah) to meet compliance regulations.
Listed in the Vigilon Plus Control Panels order codes table (alongside VIGPLUS-NODE, the E

Compact Plus Outer Door Assembly (supplied in Black)
compatible / works with: Compact Plus Outer Door Assembly (supplied in Black)