Replacement MRC (Mark 4) with Protective Cover · Vigilon Plus Mimics & Repeats
Gent VSRPT-MRC-72 Replacement Master Repeat Card Mk4

- Product type
- Replacement MRC (Mark 4) with Protective Cover
- Mains fuse
- 3.15A(T) mains fuse
- Fuse fs3
- FS3 2A(QB)
- Battery
- 12V 7Ah battery
- Rotary switch setting
- Set the rotary switch SW3 to position 4 (located below the 40-way ribbon cable header P2)
- Rotary switch position 0
- 0 A2/A3/A4 Mimic Panel only
- Rotary switch positions unused
- 1 to 3 Unused; 5 to F Unused
Overview
What it is and how it fits the system.
The Gent VSRPT-MRC-72 is the replacement Master Repeat Card (MRC) Mark-4, supplied with a protective cover for installation into an EN/BS Repeat panel or A3 Mimic panel wired onto a loop of an EN or BS fire alarm control panel. It uses a 3.15A(T) mains fuse, an FS3 2A(QB) fuse and a 12V 7Ah battery, with rotary switch SW3 set to position 4 and a factory write-protected, buzzer-disable default configuration.
Technical overview
The VSRPT-MRC-72 is the Gent by Honeywell replacement Master Repeat Card (MRC) Mark-4, part of the Vigilon Plus Mimics and Repeats range. As a Repeat Panel spare, it restores master repeat capability within a Gent Vigilon installation. It is intended for installation into an EN/BS Repeat panel or an A3 Mimic panel that is wired onto a loop of an EN or BS fire alarm control panel.
Compatibility is limited to system control panels fitted with the newer shorter Loop Processor Card, and the host panel must run software of V4.19 or higher, or 3.90 or higher. In a Repeat panel application the ribbon connections route through to the DKC, while the Mimic panel configuration supports lamp test. The card is designed to the EN54 and BS5839 standards and supersedes the earlier 2534-115.
Specifications
Full technical data for this part.
| Product type | Replacement MRC (Mark 4) with Protective Cover |
|---|---|
| Mains fuse | 3.15A(T) mains fuse |
| Fuse fs3 | FS3 2A(QB) |
| Battery | 12V 7Ah battery |
| Rotary switch setting | Set the rotary switch SW3 to position 4 (located below the 40-way ribbon cable header P2) |
| Rotary switch position 0 | 0 A2/A3/A4 Mimic Panel only |
| Rotary switch positions unused | 1 to 3 Unused; 5 to F Unused |
| Interface connection | + RS485 0V 24V - |
| Write protect default | Write Protected (Factory setting) |
| Buzzer disable | BUZZER DISABLE |
| Lamp test | Lamp test (Mimic panel only) |
| Ribbon cables | 40-Way Ribbon to DKC (Repeat panel only); 20-Way Ribbon to DKC (Repeat panel only) |
| Supplied with | Protective Cover |
| Document reference | 4188-943_issue 3_08/12_MRC |
Specifications sourced from manufacturer documentation.
Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know
Enhancements (optional)
Optional additions — this product works without them.
A3 Zonal and Graphic Mimic BS & EN compatible supplied in grey. Batteries not included - requires 2 x 4015-603-YFR (Power Sonic Flame Retardant 6V 7Ah) to meet compliance regulations.
installs into an A3 Mimic panel

Vigilon Plus Repeat Panel supplied in black. Batteries not included - requires 2 x 4015-501-YFR (Power Sonic Flame Retardant 12V 7Ah) to meet compliance regulations.
installs into an EN/BS Vigilon Repeat panel