Gent Vigilon Plus Repeat Panel supplied in black. Batteries not included - requires 1 x 4015-501-YFR (Power Sonic Flame Retardant 12V 7Ah) to meet compliance regulations.
| Part no. | VIGPLUS-RPT |
|---|---|
| Brand | Gent |
| Range | Vigilon Plus Mimics & Repeats |
| Sub-range | Repeat Panels |

Image for illustration; item supplied may differ
At a glance
- Eight-line event screenBacklit LCD with forty characters on each of its eight lines.
- 32 fire-zone LEDsDedicated zone indicators sit alongside the event display.
- Essential system controlsProvides Sound Alarms, Silence Alarms, Reset and Cancel Buzzer behind the outer door.
- Locked control accessThe door leaves indications visible and restricts access to controls.
- Surface or semi-flush mountingTop and rear cable entry supports the panel installation.
- Vigilon Plus system connectionConnects to the device loop of compatible Vigilon Plus and Compact Plus systems.
Description
The Gent VIGPLUS-RPT is a Vigilon Plus repeat panel that displays fire-system events and provides essential controls at a second location. It connects to the device loop and has its own mains supply with battery standby. The backlit screen has eight lines of forty characters, alongside 32 fire-zone LEDs and system status indicators. A lockable door keeps the controls behind a key while leaving the indications visible. With the door shut, Next and Previous let users move through fire events. The panel is supplied in black and can be surface or semi-flush mounted, with cable entry at the top and rear. One 12V 7Ah battery is ordered separately.
The VIGPLUS-RPT provides a second location for reading fire-system events and operating essential controls. It connects to the Vigilon device loop, with a separate mains-derived supply and standby from one 12V 7Ah battery, ordered separately. It is compatible with Vigilon Plus and Compact Plus systems at the required host-card software versions.
Read the full technical description
The VIGPLUS-RPT provides a second location for reading fire-system events and operating essential controls. It connects to the Vigilon device loop, with a separate mains-derived supply and standby from one 12V 7Ah battery, ordered separately. It is compatible with Vigilon Plus and Compact Plus systems at the required host-card software versions.
The backlit LCD has eight lines with forty characters on each line. Alongside it are 32 fire-zone LEDs and indications for fire, verify, sounder, power, fault, power fault, system fault, delay, test and disablement. Fire-routing active and fault or disablement indications operate with the compatible fire-routing host system. Delay-block countdown is displayed at the main panel running the delay and is not shown on the repeat display.
The outer door locks over the controls while leaving the indicators visible. With the door closed, Next and Previous operate during a fire condition. Opening the door gives access to Sound Alarms, Silence Alarms, Reset, Cancel Buzzer, Verify, F1 to F4, Menu On/Off and U1 to U4. The user-function and Verify controls depend on their configuration at the main control panel.
The enclosure is designed for surface or semi-flush mounting. Semi-flush installation uses an optional surround and a wall opening 380mm high by 320mm wide, at least 59mm deep. Four top and four rear cable entry points are available, with three earth points inside the backbox. Cable tails are left at 400mm. The panel measures 403mm high, 338mm wide and 101mm deep.
For a Plus host using short cards with fire routing, MCC or MCB software must be V4.54 or later and LPC software V4.48 or later. For legacy hosts using short cards without fire routing, the minimum versions are MCC V4.11, MCB V4.21 and LPC V4.19. The repeat display uses SW3 position 4. The local buzzer is enabled when commissioning is complete, and the configured indications and controls are tested.
Specifications
| Product type | Vigilon Plus repeat panel |
|---|---|
| Compatible systems | Vigilon Plus and Compact Plus at required host-card software |
| System connection | 3-way connection to the device loop |
| Power source | Mains-derived supply with battery standby |
| Battery supply | 1 × 12V 7Ah battery; ordered separately |
| Mains input | 230V −15% / +10%, 50/60Hz |
| Rated mains current | 0.2A |
| LCD | Backlit; 8 lines × 40 characters |
| Fire-zone LEDs | 32 |
| Fire-routing indications | Active and fault/disablement with compatible host |
| Other status indicators | Fire, verify, sounder, power, fault, power fault, system fault, delay, test and disablement |
| Door-closed controls | Next and Previous during a fire condition |
| Door-open essential controls | Sound Alarms, Silence Alarms, Reset, Cancel Buzzer and Verify |
| Menu and function controls | F1-F4, Menu On/Off and U1-U4 |
| Control access | Lockable outer door |
|---|---|
| Mounting | Surface or semi-flush with optional surround |
| Dimensions H × W × D | 403 × 338 × 101mm |
| Weight without battery | 6.75kg |
| Supplied colour | Black |
| Operating temperature | 0°C to +45°C |
| Storage temperature | −10°C to +55°C |
| Relative humidity | Up to 90% at +5°C to +45°C, noncondensing |
| Cable entries | 4 top and 4 rear |
| Semi-flush wall opening | 380mm high × 320mm wide; at least 59mm deep |
| Cable tails | 400mm |
| Plus host: short cards with fire routing | MCC/MCB V4.54 or later; LPC V4.48 or later |
| Legacy host: short cards without fire routing | Minimum versions: MCC V4.11; MCB V4.21; LPC V4.19 |
| Display selection | SW3 position 4 for the 8-line repeat display |
Specifications per manufacturer documentation, subject to change. E&OE.
Optional accessories
- VIG-DOOR-SSStainless Steel Door for Vigilon Main Control PanelStainless steel options: Stainless Steel Door for Vigilon Main Control Panel (VIG-DOOR-SS)£1,227.05ex VAT£1,472.46 inc VATIn stock
- VIG-FLUSH-SSVigilon Main Control Panel Flush Mounting Kit (Stainless Steel)Stainless steel options: Stainless Steel Flush Mounting Kit for Vigilon Main Control Panel£666.17ex VAT£799.40 inc VATIn stock
- VSRPT-MRC-72Replacement MRC for new repeat, A3 & A2 mimic (BS & EN)compatible / works with: Replacement MRC for new repeat, A3 & A2 mimic (BS & EN)£473.62ex VAT£568.34 inc VATIn stock
- VIG-RPT-FLUSHRepeat Panel Flush SurroundFlush surround option for the Vigilon repeat panel£157.87ex VAT£189.44 inc VATIn stock
FAQs
What can be operated from the VIGPLUS-RPT?
With the outer door open, the repeat provides Sound Alarms, Silence Alarms, Reset, Cancel Buzzer and Verify controls, plus the menu and function keys. U1 to U4 and Verify need configuration at the main control panel. With the door closed, Next and Previous remain available during a fire condition to move through the displayed fire events. The lockable door restricts access to the controls while keeping the event display and status indications visible.
How does the repeat connect to a Plus system?
It connects to the device loop and has its own mains-derived supply with battery standby. A Plus host using short cards with fire-routing capability needs MCC or MCB software V4.54 or later and LPC software V4.48 or later. The panel is compatible with Vigilon Plus and Compact Plus systems at those required software levels. The loop connection terminates at P16 on the Master Repeat Card, with the separate mains connection at P9. One 12V 7Ah battery is ordered separately from the repeat panel.
Can the VIGPLUS-RPT be semi-flush mounted?
Yes. It can be surface mounted or semi-flush mounted using an optional surround. The semi-flush wall opening is 380mm high and 320mm wide, with a depth of at least 59mm. The backbox has four top and four rear cable entry points and three earth points. Cable tails are left at 400mm. The panel enclosure measures 403mm high, 338mm wide and 101mm deep, and the door keeps the indicators visible while restricting access to the controls.
Does the repeat show a delay-block countdown?
No. The delay-block countdown appears at the main panel where that delay is running; it is not shown on the repeat display. The VIGPLUS-RPT has a delay status indicator alongside its other system indications. Its backlit LCD presents event information across eight lines of forty characters, with 32 separate fire-zone LEDs. During a fire condition, the Next and Previous buttons let users move through fire events with the outer door closed and the controls behind it.
What is checked during commissioning?
The host-card firmware is checked against the applicable Plus or legacy shorter-card configuration, and SW3 is set to position 4 for the eight-line repeat display. The display test checks the LEDs. Fire indications, Sound Alarms, Silence Alarms and Reset are tested, along with configured Verify and U1 to U4 functions. The local buzzer is enabled when commissioning is complete. Local mains and battery failure tests also check that the repeat gives the associated fault indications.