Part Number or the Week S3EP-V-VAD-HPR-R

Gent SAFE 2 button Stainless Steel plus inter

Part no.SAFE-SS-D-KIT
BrandGent
RangeSAFE Button
Sub-rangeButton + Interface Module
Gent by Honeywell SAFE 2 button stainless steel plus interface — main product photograph

Image for illustration; item supplied may differ

At a glance

  • Switch and interface kitSAFE-SS-D-KIT includes a switch, S4-34450 interface and wiring loom.
  • Separate test and silence positionsThe upper position operates the alarm test; the lower position operates alarm silence.
  • Red and green indicationRed indicates silence control activation; green indicates the alarm test.
  • S4-34450 connectionThe switch uses channels 1 and 2 for silence and test, with channels 3 and 4 driving the LEDs.
  • Local alarm testHold the button upwards until the green LED lights; alarms stop five seconds after release.
  • 30m switch cable limitThe cable run between the SAFE button and its S4-34450 interface can be up to 30m.

Description

The Gent SAFE-SS-D-KIT is a stainless steel double SAFE button kit for local alarm control. Its two positions test local alarms in normal conditions and silence them during the initial smoke-alert delay. A red LED marks the silence function and a green LED marks the test function. The kit includes the switch, an S4-34450 interface and wiring loom, with the interface enclosure supplied separately. The cable run from switch to interface is limited to 30m. Area delays are set during commissioning. The switch is 85mm high and 85mm wide, with a depth of 25mm plus the terminal block. Test the local alarms each month in normal conditions.

The SAFE-SS-D-KIT combines the stainless steel double SAFE switch with an S4-34450 four-channel interface and wiring loom. The interface connects to the fire alarm loop. An interface enclosure is required separately.

Read the full technical description

The SAFE-SS-D-KIT combines the stainless steel double SAFE switch with an S4-34450 four-channel interface and wiring loom. The interface connects to the fire alarm loop. An interface enclosure is required separately.

In normal conditions, hold the switch upwards until the green LED lights to test the local alarms. During the initial smoke-alert delay, hold it downwards until the red LED lights to silence the area alarms. Interface channel 1 handles silence, channel 2 handles test, channel 3 drives the red LED and channel 4 drives the green LED. During normal conditions, the silence control can also disable area smoke detection for a default period of 15 minutes.

The SAFE range works with Vigilon Plus and Vigilon Compact Plus panels with MCC or MCB software V4.57 minimum and LPC software V4.52 minimum. Configure the area and interface with Commissioning Tool V1.34. Where a printer connects through an IOC, that card needs V4.16 minimum; loop repeat and mimic panels require MRC software V1.09 minimum. Area delays and extensions are set as part of commissioning.

Keep the switch-to-interface cable run within 30m. The button measures 85mm high by 85mm wide, with a depth of 25mm plus the terminal block. Allow enough backbox depth for the assembly and secure all terminal connections. Tighten the fixing screws without a powered screwdriver and do not apply an insulation tester to the switch. Test the area alarms monthly and clean the switch with a dry, soft, lint-free cloth.

Specifications

ProductSAFE switch and interface kit
Switch arrangementDouble button, two positions
FinishStainless steel
Supplied itemsSAFE switch, S4-34450 interface and wiring loom
Power sourceLoop powered through the S4-34450 interface
Control interfaceS4-34450
Switch-to-interface cable30m maximum
Button dimensions85mm H x 85mm W x 25mm D, plus terminal block
SAFE range switch terminals2.5mm² terminal capacity
Silence controlDownward press; hold until red LED lights
Test controlUpward press; hold until green LED lights
IndicatorsRed silence LED; green test LED
Test run-on5 seconds after releasing the test control
Interface enclosureSeparate from kit
SAFE range panel compatibilityVigilon Plus and Vigilon Compact Plus
MCC/MCB softwareV4.57 minimum for SAFE operation
LPC softwareV4.52 minimum for SAFE operation
Commissioning toolV1.34 for SAFE area and interface configuration
Channel 1Silence input
Channel 2Test input
Channel 3Red LED output
Channel 4Green LED output
Area alarm test intervalMonthly
CleaningDry, soft, lint-free cloth

Specifications per manufacturer documentation, subject to change. E&OE.

Optional accessories

Spares & replacement parts

FAQs

What is supplied with SAFE-SS-D-KIT?

SAFE-SS-D-KIT includes a switch, S4-34450 interface and wiring loom. The interface enclosure is a separate item. The switch operates the alarms assigned to its area, while the interface connects the controls to the fire alarm loop. Its two positions provide local test and silence control. Keep the cable run between switch and interface within 30m. The SAFE range uses Vigilon Plus or Vigilon Compact Plus panels with the required card software and area configuration.

How does SAFE-SS-D-KIT silence local alarms?

During the initial smoke-alert delay, hold the switch down until the red LED lights, then release it. This silences alarms in its assigned area. Delay periods and permitted extensions depend on the commissioned area settings. Near the end of the delay, the red LED flashes and the alert sounds; another press can extend the delay where configured. If smoke remains when the allowed delay expires, evacuation alarms follow the system cause and effect.

How do I test the alarms with SAFE-SS-D-KIT?

Test SAFE-SS-D-KIT while the system is in its normal condition. Press the upper test position and hold it until the green LED lights and the area alarms sound. Release the button when the test is complete; the alarms continue for five seconds before stopping and the green LED turns off. Carry out this area alarm test monthly. The lower position operates the silence function, using the red LED, so the two positions have separate controls and indications.

How is SAFE-SS-D-KIT connected and mounted?

The switch in SAFE-SS-D-KIT connects to its S4-34450 interface over a cable run of up to 30m. Channels 1 and 2 handle silence and test, while channels 3 and 4 drive the red and green LEDs. The switch is 85mm high and 85mm wide, with a depth of 25mm plus its terminal block. Allow sufficient backbox depth, secure the wire connections and tighten the fixing screws without a powered screwdriver. Do not apply an insulation tester to the switch.

Can SAFE-SS-D-KIT disable area smoke detection before an alarm?

In normal conditions, SAFE-SS-D-KIT can disable area smoke detection using its lower silence position. Hold that position until the red LED lights, then release it. The default disablement period is 15 minutes, with the duration set during commissioning. Before the red LED starts flashing, press and hold the silence control until the LED goes out to restore smoke detection. Near the end of the period, the flashing red LED warns that detection is about to resume; a further extension depends on the configured settings.