Gent SAFE 2 button Stainless Steel plus inter
| Part no. | SAFE-SS-D-KIT |
|---|---|
| Brand | Gent |
| Range | SAFE Button |
| Sub-range | Button + Interface Module |

Image for illustration; item supplied may differ
At a glance
- Switch and interface kitSAFE-SS-D-KIT includes a switch, S4-34450 interface and wiring loom.
- Separate test and silence positionsThe upper position operates the alarm test; the lower position operates alarm silence.
- Red and green indicationRed indicates silence control activation; green indicates the alarm test.
- S4-34450 connectionThe switch uses channels 1 and 2 for silence and test, with channels 3 and 4 driving the LEDs.
- Local alarm testHold the button upwards until the green LED lights; alarms stop five seconds after release.
- 30m switch cable limitThe cable run between the SAFE button and its S4-34450 interface can be up to 30m.
Description
The Gent SAFE-SS-D-KIT is a stainless steel double SAFE button kit for local alarm control. Its two positions test local alarms in normal conditions and silence them during the initial smoke-alert delay. A red LED marks the silence function and a green LED marks the test function. The kit includes the switch, an S4-34450 interface and wiring loom, with the interface enclosure supplied separately. The cable run from switch to interface is limited to 30m. Area delays are set during commissioning. The switch is 85mm high and 85mm wide, with a depth of 25mm plus the terminal block. Test the local alarms each month in normal conditions.
The SAFE-SS-D-KIT combines the stainless steel double SAFE switch with an S4-34450 four-channel interface and wiring loom. The interface connects to the fire alarm loop. An interface enclosure is required separately.
Read the full technical description
The SAFE-SS-D-KIT combines the stainless steel double SAFE switch with an S4-34450 four-channel interface and wiring loom. The interface connects to the fire alarm loop. An interface enclosure is required separately.
In normal conditions, hold the switch upwards until the green LED lights to test the local alarms. During the initial smoke-alert delay, hold it downwards until the red LED lights to silence the area alarms. Interface channel 1 handles silence, channel 2 handles test, channel 3 drives the red LED and channel 4 drives the green LED. During normal conditions, the silence control can also disable area smoke detection for a default period of 15 minutes.
The SAFE range works with Vigilon Plus and Vigilon Compact Plus panels with MCC or MCB software V4.57 minimum and LPC software V4.52 minimum. Configure the area and interface with Commissioning Tool V1.34. Where a printer connects through an IOC, that card needs V4.16 minimum; loop repeat and mimic panels require MRC software V1.09 minimum. Area delays and extensions are set as part of commissioning.
Keep the switch-to-interface cable run within 30m. The button measures 85mm high by 85mm wide, with a depth of 25mm plus the terminal block. Allow enough backbox depth for the assembly and secure all terminal connections. Tighten the fixing screws without a powered screwdriver and do not apply an insulation tester to the switch. Test the area alarms monthly and clean the switch with a dry, soft, lint-free cloth.
Specifications
| Product | SAFE switch and interface kit |
|---|---|
| Switch arrangement | Double button, two positions |
| Finish | Stainless steel |
| Supplied items | SAFE switch, S4-34450 interface and wiring loom |
| Power source | Loop powered through the S4-34450 interface |
| Control interface | S4-34450 |
| Switch-to-interface cable | 30m maximum |
| Button dimensions | 85mm H x 85mm W x 25mm D, plus terminal block |
| SAFE range switch terminals | 2.5mm² terminal capacity |
| Silence control | Downward press; hold until red LED lights |
| Test control | Upward press; hold until green LED lights |
| Indicators | Red silence LED; green test LED |
| Test run-on | 5 seconds after releasing the test control |
|---|---|
| Interface enclosure | Separate from kit |
| SAFE range panel compatibility | Vigilon Plus and Vigilon Compact Plus |
| MCC/MCB software | V4.57 minimum for SAFE operation |
| LPC software | V4.52 minimum for SAFE operation |
| Commissioning tool | V1.34 for SAFE area and interface configuration |
| Channel 1 | Silence input |
| Channel 2 | Test input |
| Channel 3 | Red LED output |
| Channel 4 | Green LED output |
| Area alarm test interval | Monthly |
| Cleaning | Dry, soft, lint-free cloth |
Specifications per manufacturer documentation, subject to change. E&OE.
Optional accessories
- SAFE-WHITE-D-KITSAFE 2 button White plus interfaceAlternative - same SAFE Double Button kit in White finish£234.03ex VAT£280.84 inc VATIn stock
- SAFE-RED-D-KITSAFE 2 button Red plus interfaceAlternative - same SAFE Double Button kit in Red finish£257.03ex VAT£308.44 inc VATIn stock
Spares & replacement parts
- SAFE-SS-D-SPARESAFE 2 button Stainless Steel plus loomReplacement switch for the 2-position Stainless Steel SAFE kit.£152.38ex VAT£182.86 inc VATIn stock
FAQs
What is supplied with SAFE-SS-D-KIT?
SAFE-SS-D-KIT includes a switch, S4-34450 interface and wiring loom. The interface enclosure is a separate item. The switch operates the alarms assigned to its area, while the interface connects the controls to the fire alarm loop. Its two positions provide local test and silence control. Keep the cable run between switch and interface within 30m. The SAFE range uses Vigilon Plus or Vigilon Compact Plus panels with the required card software and area configuration.
How does SAFE-SS-D-KIT silence local alarms?
During the initial smoke-alert delay, hold the switch down until the red LED lights, then release it. This silences alarms in its assigned area. Delay periods and permitted extensions depend on the commissioned area settings. Near the end of the delay, the red LED flashes and the alert sounds; another press can extend the delay where configured. If smoke remains when the allowed delay expires, evacuation alarms follow the system cause and effect.
How do I test the alarms with SAFE-SS-D-KIT?
Test SAFE-SS-D-KIT while the system is in its normal condition. Press the upper test position and hold it until the green LED lights and the area alarms sound. Release the button when the test is complete; the alarms continue for five seconds before stopping and the green LED turns off. Carry out this area alarm test monthly. The lower position operates the silence function, using the red LED, so the two positions have separate controls and indications.
How is SAFE-SS-D-KIT connected and mounted?
The switch in SAFE-SS-D-KIT connects to its S4-34450 interface over a cable run of up to 30m. Channels 1 and 2 handle silence and test, while channels 3 and 4 drive the red and green LEDs. The switch is 85mm high and 85mm wide, with a depth of 25mm plus its terminal block. Allow sufficient backbox depth, secure the wire connections and tighten the fixing screws without a powered screwdriver. Do not apply an insulation tester to the switch.
Can SAFE-SS-D-KIT disable area smoke detection before an alarm?
In normal conditions, SAFE-SS-D-KIT can disable area smoke detection using its lower silence position. Hold that position until the red LED lights, then release it. The default disablement period is 15 minutes, with the duration set during commissioning. Before the red LED starts flashing, press and hold the silence control until the LED goes out to restore smoke detection. Near the end of the period, the flashing red LED warns that detection is about to resume; a further extension depends on the configured settings.