SAFE Button
Gent SAFE-RED-D-KIT Red Double SAFE Switch Kit

- Kit contents
- SAFE 2 position, Red, switch kit containing - SAFE Switch, 4 Channel Interface and wiring loom (Does not include interface enclosure)
- Button type
- Double Button (2 position)
- Operating temperature
- 1OC to 50OC
- Loop loading
- 200 Alarm Areas per loop
- Weight
- 200g
- Dimensions
- 85 mm (H) x 85 mm (W) x 25mm (D)
- Approvals
- EN54 Part 2 Type B Dependency Approved
Overview
What it is and how it fits the system.
The Gent SAFE-RED-D-KIT is a red double-position SAFE switch kit used to manage Area Alarms in a Vigilon Plus Fire System, supplied with a SAFE Switch, 4 Channel Interface and wiring loom (interface enclosure not included). Pressing and holding for 5 seconds disables area smoke detection for 15 minutes, and the device is EN54 Part 2 Type B Dependency approved with up to 200 Alarm Areas per loop. It measures 85mm (H) x 85mm (W) x 25mm (D).
Technical overview
SAFE-RED-D-KIT is a Gent by Honeywell red double-position switch kit used to manage Area Alarms in a Vigilon Plus Fire System. The kit comprises a SAFE Switch, 4 Channel Interface and wiring loom, with the interface enclosure supplied separately. Activation requires pressing and holding the switch for five seconds to disable area smoke detection for fifteen minutes, indicated by confirmation LEDs.
Operating within 1OC to 50OC, the device supports up to 200 Alarm Areas per loop and holds EN54 Part 2 Type B Dependency approval. Physical dimensions are 85mm (H) x 85mm (W) x 25mm (D), with a weight of 200g and a finish combining white, red and stainless steel elements. Channel functions assign silence alarms and test operations to Channels 1 and 2, while Channels 3 and 4 drive red and green indicator LEDs respectively. A spare switch variant, SAFE-RED-D-SPARE, is available for replacement purposes.
Specifications
Full technical data for this part.
| Kit contents | SAFE 2 position, Red, switch kit containing - SAFE Switch, 4 Channel Interface and wiring loom (Does not include interface enclosure) |
|---|---|
| Button type | Double Button (2 position) |
| Operating temperature | 1OC to 50OC |
| Loop loading | 200 Alarm Areas per loop |
| Weight | 200g |
| Dimensions | 85 mm (H) x 85 mm (W) x 25mm (D) |
| Finish | White / Red / Stainless steel |
| Approvals | EN54 Part 2 Type B Dependency Approved |
| Activation | To Activate Press And Hold For 5 Seconds |
| Smoke disablement period | Area smoke detection being disabled for 15 minutes |
| Indicators | Confirmation LED to visually inform occupants that action has taken place; red LED (Channel 3) and green LED (Channel 4) |
| Channel functions | Channel 1 (Silence alarms) & Channel 3 (red led); Channel 2 (Test) & Channel 4 (green led) |
| Spare part code | SAFE-RED-D-SPARE (SAFE 2 position, Red, Spare switch complete with - SAFE Switch and wiring loom) |
Specifications sourced from manufacturer documentation.
Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know
Enhancements (optional)
Optional additions — this product works without them.

SAFE 2 button Stainless Steel plus inter
Alternative — same SAFE Double Button kit in Stainless Steel finish

SAFE 2 button White plus interface
Alternative — same SAFE Double Button kit in White finish
Spares & replacement parts
Replacement parts for units already in service.

SAFE 2 button Red plus loom
Replacement switch for the 2-position Red SAFE kit.