System Sensor DUAL INPUT MODULE - SYSTEM SENSOR

Part no.M220EA
BrandSystem Sensor
RangeAddressable Interface modules
Sub-rangeInput Module
System Sensor M220EA Dual Channel Input Module — white module with green terminal block and two input ports

Image for illustration; item supplied may differ

At a glance

  • Dual Channel Input ModuleM220EA monitors normally open contact fire alarm and supervisory devices on two channels.
  • Declared Performance DOP-IOD071Performance is declared under DOP-IOD071 to EN 54-17: 2005 and EN 54-18: 2005.
  • Operating Voltage RangeThe module works on 15 to 32 VDC, with a minimum of 16.5VDC for LED operation.
  • Low Standby CurrentMaximum standby current is 140 µA @24 V with no communication.
  • Tri-colour Channel IndicatorsTwo tri-colour LEDs give one indicator per channel, drawing 1.5 mA on red and 5.5 mA on yellow.
  • Integral Loop IsolatorsAll M200 series modules are provided with short circuit monitoring and isolators on the intelligent loop.
  • Rotary Decade AddressingThe module address is selected on rotary decade switches reached from the front or the top of the module.
  • Surface Or DIN MountingMounting is either in the M200E-SMB surface-mounting box or on standard 35 mm x 7.5 mm Top Hat DIN rail.

Description

Every M200 series module carries short circuit monitoring and isolators on the intelligent loop, and those isolators may be wired out of the loop to suit high current loaded loops, for example where sounders are used.

Where the control panel is compatible, short circuit fault monitoring of the input circuit may be possible, with an 18kΩ resistor wired in series with each device switch being monitored. Plug in type terminals take conductors up to 2.5 mm², and the working humidity range is 5% to 95% relative humidity, non-condensing.

M220EA is the dual channel input module of the M200 series, a family of microprocessor controlled interface devices permitting the monitoring and control of auxiliary devices. Its two channels monitor normally open contact fire alarm and supervisory devices, and the module may only be connected to control panels using compatible proprietary analogue addressable communication protocols. Performance is declared under DOP-IOD071 to EN 54-17: 2005 and EN 54-18: 2005.

The module runs on 15 to 32 VDC, with a minimum of 16.5VDC needed for LED operation, and its maximum standby current is 140 µA @24 V with no communication. Two tri-colour LEDs give one indicator per channel, drawing 1.5 mA on red and 5.5 mA on yellow. Panel command can set an LED to pulse green each time its channel is polled and to switch the red indicator on continuously in an alarm, while the yellow LED is controlled by the module itself and blinks to indicate an open circuit on the input circuit.

Read the full technical description

Two mounting routes are open to the installer. An M200E-SMB custom low profile surface-mounting box is fixed to the surface first, with the module and cover screwed onto that base, and the box measures 132 mm (H) x 137 mm (W) x 40 mm (D). Alternatively the DIN bracket on top allows mounting onto standard 35 mm x 7.5 mm Top Hat DIN rail inside a control panel or other suitable enclosure. Loop power must be disconnected before modules or sensors are installed, and the module is an electrostatic sensitive device, so handling precautions apply throughout. M220EA is made by Honeywell Products and Solutions Sàrl, trading as System Sensor Europe.

M220EA is the dual channel input module of the M200 series, a family of microprocessor controlled interface devices permitting the monitoring and control of auxiliary devices. Its two channels monitor normally open contact fire alarm and supervisory devices, and the module may only be connected to control panels using compatible proprietary analogue addressable communication protocols. Performance is declared under DOP-IOD071 to EN 54-17: 2005 and EN 54-18: 2005.

The module runs on 15 to 32 VDC, with a minimum of 16.5VDC needed for LED operation, and its maximum standby current is 140 µA @24 V with no communication. Two tri-colour LEDs give one indicator per channel, drawing 1.5 mA on red and 5.5 mA on yellow. Panel command can set an LED to pulse green each time its channel is polled and to switch the red indicator on continuously in an alarm, while the yellow LED is controlled by the module itself and blinks to indicate an open circuit on the input circuit.

Addresses are set on rotary decade switches, turned with a screwdriver from the front or the top of the module, and the address chosen refers to the first input channel with the next address assigned automatically to the second channel. Address 159 is invalid for dual channel modules, and where a control panel can use only 99 addresses, 99 is invalid too, a restriction that falls away on Advanced Protocol.

Specifications

Series descriptionThe M200 series of modules are a family of microprocessor controlled interface devices permitting the monitoring and/or control of auxiliary devices.
IndicatorsIt has two tri-colour LED's, one referring to each channel. Each LED can be set by panel command to pulse green each time the module channel is polled. In case of an alarm the panel can switch the red indicator on continuously. The Yellow LED is controlled by the module and blinks to indicate an open circuit on the input circuit.
Operating Voltage Range15 to 32 VDC (Min 16.5VDC for LED operation)
Maximum standby current140 µA @24 V and 25 o C (no communication)
LED current red1.5 mA
LED current yellow5.5 mA
Relative humidity5% to 95% relative humidity (non-condensing)
Maximum wire gauge2.5 mm²
Terminal typeplug in type terminals capable of supporting conductors up to 2.5 mm²
DimensionsBox dimensions: 132 mm (H) x 137 mm (W) x 40 mm (D)
AddressingThe module address is selected by means of rotary decade address switches. A screwdriver should be used to rotate the wheels to select the desired address, either from the front or the top of the module.
Address assignmentFor modules having more than one channel, the address selected will refer to the first input channel, the module will automatically assign the next one or two addresses as appropriate to the second input channel and output channel. As a result, address 159 will be invalid for dual channel modules
Address limit noteSome control panels are only able to use 99 addresses. If this is the case, 99 will be invalid for dual channel modules
Second channel terminalsThe dashed line circuit connected to terminals 8 and 9 should only be used with the M220EA. There are no connections to these terminals on the M210EA.
Short circuit input monitoringProvided the control panel is compatible, short circuit monitoring of the input circuit may be possible. An 18kΩ resistor should be wired in series with each device switch being monitored.
Short circuit isolatorsAll M200 series modules are provided with short circuit monitoring and isolators on the intelligent loop. If required, the isolators may be wired out of the loop to facilitate the use of the modules on high current loaded loops, for example if sounders are used.
EN54 Part / ClassEN 54-17: 2005, EN 54-18: 2005
Declaration of performanceM220EA: DOP-IOD071

Specifications per manufacturer documentation, subject to change. E&OE.