ex-VAT pricing shown

Now open for trade ordersGent, Morley-IAS & Xtralis stock added weekly — open to the trade.

Addressable Interface modules

Gent M201EA-240 Addressable Two-Pole Relay Module

Addressing
screwdriver-operated rotary address switches accessible from front and one side; uses one address on the intelligent add
Standards
Complies with EN 54-17:2005 and EN 54-18:2005; FPANZ listing pending
Nzs 4512 mains restriction
Per NZS 4512:2021 sections 2.3.4 and 4.2.5 (no mains cabling inside fire panels / ancillary control devices), the M201EA

Overview

What it is and how it fits the system.

The Gent M201EA-240 is an Intelligent Addressable two-pole relay module providing one two-pole voltage-free relay output, with one normally-open and one normally-closed contact, switched on or off by command from the fire panel. Individually loop-addressable across the range 1 to 99, it carries relay contacts rated 5 amps at 30 V dc, 5 amps at 100 V rms audio and 5 amps at 250 V ac power. It operates from 15 V dc to 32 V dc, draws a maximum standby current of 27 µA, measures 82 x 22 x 99 mm excluding terminal blocks and weighs 118 g.

Technical overview

M201EA-240, the Morley Intelligent Addressable two-pole relay module from the Addressable Interface modules range, provides one two-pole voltage-free relay output with one normally open and one normally closed contact, switched on or off by command from the fire panel. The relay contacts are rated 5 amps @ 30 V dc, 5 amps @ 100 V rms (audio) and 5 amps @ 250 V ac (power).

A built-in loop short-circuit isolator automatically detects shorts on the IA loop, and a tri-colour LED status indicator can be configured to switch green while the relay output is on or to pulse green each time the module is polled. Supply is 15 V dc to 32 V dc with a maximum standby current of 27 µA.

Rated IP 30 and operating from -20°C to 60°C, the 118 g module mounts by two holes or DIN rail clips in any type of enclosure, including the M200E-SMB surface-mount box; M200E-DIN clips suit M2xx series modules. The module complies with EN 54-17:2005 and EN 54-18:2005, and on NZS 4512:2021 systems must not be connected to 230 volt ac mains power circuits. M201EA-240 supersedes the M201E-240 and M201E-240-DIN.

Specifications

Full technical data for this part.

Addressingscrewdriver-operated rotary address switches accessible from front and one side; uses one address on the intelligent add
StandardsComplies with EN 54-17:2005 and EN 54-18:2005; FPANZ listing pending
Nzs 4512 mains restrictionPer NZS 4512:2021 sections 2.3.4 and 4.2.5 (no mains cabling inside fire panels / ancillary control devices), the M201EA

Specifications sourced from manufacturer documentation.

Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know

Optional accessories

Optional additions — this product works without them.

M200E-DIN

DIN rail mounting clip for M2xx series modules

compatible / works with: DIN rail mounting clip for M2xx series modules

£5.80
ex VAT
£6.96 inc VAT
Sold separately
M200E-SMB
Interface Enclosure (Small) Plastic Previously listed as S4-34493

Interface Enclosure (Small) Plastic Previously listed as S4-34493

Relay module mounts in the purpose-built M200E-SMB surface-mount box (optional enclosure)

£10.83
ex VAT
£13.00 inc VAT
Sold separately

Spares & replacement parts

Replacement parts for units already in service.

M201EA

SINGLE OUTPUT MODULE - SYSTEM SENSOR

Two mounting holes to suit the M200E-SMB surface-mount box; M201EA-240 is a suitable repla

£60.40
ex VAT
£72.48 inc VAT
Sold separately

Datasheets & documents

Reference downloads.