Skip to content

Trade prices shown ex VAT. Order by 3pm for same-day dispatch on stocked lines, UK mainland. Free UK delivery on orders over £250 ex VAT.

Part Number or the Week S3EP-V-VAD-HPR-R

System Sensor Agile Gateway. Loop-powered Gateway device for System Sensor Agile wireless system. Up to 8 Gateways may be used on the same loop. This requires a B501AP base. Compatible with DXc panels only

Part no.M200G-RF-26
BrandSystem Sensor
RangeSystem Sensor AGILE
Sub-rangeGateway
System Sensor M200G-RF-26 Agile Loop Powered Wireless Gateway — white domed enclosure with two dark screws on top

Image for illustration; item supplied may differ

Description

The System Sensor M200G-RF-26 is a Loop powered Gateway for the Agile wireless fire detection system: Up to 50 Wireless devices per Gateway. Mesh network technology providing up to two communication paths to each wireless device, over 18RF channels from 865MHz to 870MHz.

The M200G-RF-26 is the Loop powered Gateway for the System Sensor Agile wireless fire detection system.

Read the full technical description

The M200G-RF-26 is the Loop powered Gateway for the System Sensor Agile wireless fire detection system.

The manufacturer states Up to 8 Gateways per loop (in severe interference) and Up to 50 Wireless devices per Gateway (32 fire devices and 17 remote indicators as per EN54-25 Regulation).

The wireless platform uses mesh network technology providing up to two communication paths to each wireless device. It uses 18RF channels from 865MHz to 870MHz with Up to 400m free air communication range and 5 years average battery service life.

The Gateway is 94mm 42mm (with B501AP base). All System Sensor products are covered by our three year warranty.

Specifications

Product typeGateway and Repeater
PowerLoop powered Gateway
Communication line supply range24V
Standby current230uA
Radio frequency865-870 MHz
Transmitting power<25mW e.r.p.
Rf channels18RF channels from 865MHz to 870MHz
Free air communication rangeUp to 400m free air communication range
Communication pathsTwo communication paths to each wireless device
Wireless devices per gatewayUp to 50 Wireless devices per Gateway (32 fire devices and 17 remote indicators as per EN54-25 Regulation)
Gateways per loopUp to 8 Gateways per loop (in severe interference)
Operating temperature-30: 60 °C
Humidity10: 93 %RH (No condensation)
Fire standardEN54-25

Specifications per manufacturer documentation, subject to change. E&OE.

Documents

DocumentTypeSizeDownload
Datasheet (22051E-RF-26, 22051TLE-RF-26, M200G-RF-26, M200WC-RF-PRO)Datasheet823 KBDownload PDF

Optional accessories