V1 Voice Rack
VARIODYN ONE 585000.33 INC-A G2 Network Controller
- Model name
- INC-A G2
- Audio in out module
- Audio in/out module (6 in/out)
- Gpios
- 14 GPIOs
- Auxiliary audio input channels
- 6 (AUXILIARY AUDIO INPUT/OUTPUT (OPTIONAL))
- Operating modes
- "Direct Drive" or "Relay Matrix" operating modes provide flexibility
- Built in memory
- Built-in memory for configuration and audio files (0.9 GB/ 5 hrs.)
- Amplifier channel current
- maximum capacity of 5 A current per channel
You will also need
Needed to install, power or certify this product.
8 Speaker Line Module
INC has no speaker circuits by default; an 8 Speaker Line Module must be added to provide speaker circuits.
Overview
What it is and how it fits the system.
The INC-A G2 (585000.33) is a Gent VARIODYN ONE Intelligent Network Controller supplied with a 6 in/out audio module and 14 GPIOs, including six auxiliary audio input/output channels. It manages up to 8 amplifier channels at a maximum of 500 W and 5 A per channel, and up to 48 speaker circuits across six modules, with 0.9 GB built-in memory for configuration and audio. Direct Drive and Relay Matrix operating modes provide flexibility across PAVA installations.
Technical overview
585000.33, the INC-A G2 Intelligent Network Controller for the VARIODYN ONE PAVA system, integrates a 6-in/out audio module and acts as the main controller managing and monitoring power amplifiers, speaker lines and call stations. It manages up to 8 amplifier channels at a maximum of 500 W and 5 A per channel, and up to 48 speaker circuits across six modules, with 0.9 GB built-in memory for configuration and audio. The controller supports Direct Drive or Relay Matrix operating modes to suit different installation requirements.
The controller includes 14 GPIOs and six auxiliary audio input/output channels, supporting 8 simultaneous audio streams. Per-channel DSP processing can be adjusted and saved to fine-tune audio output across the system. An intuitive LED interface helps ensure clear system status monitoring, and Modbus over RS485 enables integration with third-party Modbus interfaces.
Specifications
Full technical data for this part.
| Model name | INC-A G2 |
|---|---|
| Audio in out module | Audio in/out module (6 in/out) |
| Gpios | 14 GPIOs |
| Auxiliary audio input channels | 6 (AUXILIARY AUDIO INPUT/OUTPUT (OPTIONAL)) |
| Operating modes | "Direct Drive" or "Relay Matrix" operating modes provide flexibility |
| Built in memory | Built-in memory for configuration and audio files (0.9 GB/ 5 hrs.) |
| Audio storage | 0.9 GB |
| Amplifier channels | Manages up to 8 amplifier channels (max. 500 W per channel) |
| Amplifier channel current | maximum capacity of 5 A current per channel |
| Speaker circuits | Up to 48 speaker circuits divided into 6 modules with 8 speaker circuits each |
| Simultaneous audio | Supports 8 simultaneous Audio per controller |
| Modbus protocol | Modbus protocol over Serial link (RS485) to integrate with 3rd Party Modbus interface |
| Dsp capability | Advance DSP capability to change and save: Volume, Dynamic Range Control, Delay, Parametric Equalizer, High Pass/Low pass filters per Amplifier channel |
| User interface | Intuitive LED interface ensuring you can easily understand the system status |
Specifications sourced from manufacturer documentation.
Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know
Datasheets & documents
Reference downloads.
- 510 KB