Gent Spare PCB for S4 Mains Powered Interface - 2.5A (S4-34440-12)
| Part no. | VSINTM-PCB12 |
|---|---|
| Brand | Gent |
| Range | S4 Interfaces & Accessories |
| Sub-range | Interface Spares |

Image for illustration; item supplied may differ
At a glance
- Spare circuit boardReplacement PCB for the Gent S4-34440-12 mains powered interface.
- For the 2.5 A parent interfaceThe S4-34440-12 has a maximum total output current of 2.5 A.
- Four-channel parent rangeThe S4 mains powered interfaces have four configurable input/output channels.
- Terminal blocks transferThe existing wired terminal blocks fit onto the replacement board.
- Original earthing fixingsReuse the board fixing screws as part of the case earth connection.
- Configuration after fittingAllocate the loop, then configure and test the installed interface for the site.
Description
The Gent VSINTM-PCB12 is a spare circuit board for the S4-34440-12 mains powered interface, the 2.5 A version. It replaces the original board inside the existing interface. The wired terminal blocks transfer to the new board, and the original fixing screws are reused as part of the case earth connection. Before removal, stop the loop at the fire panel, isolate the mains supply and disconnect the battery. After fitting, refit the protective cover and reconnect the mains and battery supplies, then allocate the loop. The interface must be configured and tested for the site after the board has been replaced.
The VSINTM-PCB12 fits the Gent S4-34440-12. The S4-34440-12 has a maximum total output current of 2.5 A. The S4 mains powered interface range has four channels that can be set for inputs, outputs or both.
Read the full technical description
The VSINTM-PCB12 fits the Gent S4-34440-12. The S4-34440-12 has a maximum total output current of 2.5 A. The S4 mains powered interface range has four channels that can be set for inputs, outputs or both.
During board replacement, the existing wired terminal blocks transfer to the new board. Reuse the original board fixing screws, which provide part of the case earth connection. Stop the loop, isolate the mains supply and disconnect the battery before removing the board.
Refit the protective cover before reconnecting mains at P3, followed by the battery lead at P7. Allocate the loop, close and lock the enclosure, then configure and test the interface. For the S4-34440-12, select the mains powered interface type and set its channels in the S4-MP configuration page.
Specifications
| Brand | Gent |
|---|---|
| Part number | VSINTM-PCB12 |
| Part type | Spare printed circuit board |
| Fits | S4-34440-12 |
| Parent interface type | S4 mains powered interface |
| Parent maximum total output current | 2.5 A |
| Parent range channel count | 4 configurable input/output channels |
| Replacement terminal connections | Transfer the existing wired terminal blocks |
| Board fixing screws | Original screws reused; part of case earthing |
Specifications per manufacturer documentation, subject to change. E&OE.
Documents
| Document | Type | Size | Download |
|---|---|---|---|
| Installation manual (VSINTM-PCB02, VSINTM-PCB12) | Installation | 81 KB | Download PDF |
Optional accessories
FAQs
Which interface does the VSINTM-PCB12 fit?
The VSINTM-PCB12 is the spare circuit board for the Gent S4-34440-12, which has a maximum total output current of 2.5 A. The S4 mains powered interface range has four channels for input and output functions, including using input and output circuits together on a channel. When configuring the S4-34440-12, select the mains powered interface type and set the required channel functions in the S4-MP page. These settings apply to the installed interface.
What is involved in replacing the VSINTM-PCB12?
Stop the loop at the fire panel, isolate the mains and disconnect the battery before removing the existing board. Retain the fixing screws and use them to secure the replacement; they form part of the case earthing. Transfer the wired terminal blocks and refit the protective cover. Reconnect the mains at P3, followed by the battery lead at P7, then allocate the loop. Close and lock the enclosure, and configure and test the interface for the site.