VESDA Multi-Function Control Card with MPO
| Part no. | VIC-030 |
|---|---|
| Brand | VESDA |
| Range | VESDA Programming and Connectivity |

Image for illustration; item supplied may differ
At a glance
- Monitored 24 V Powered OutputVIC-030 carries an MPO that provides power to devices such as sirens or strobes and monitors the line integrity.
- MPO Output CurrentMPO output current is 1 A (maximum) from a 24 VDC input drawing 100 mA more than the MPO output load.
- Third Relay Or MPOJumper configuration J9 J10 selects between a third relay and the 24 V MPO.
- Self-Configuring GPIThe GPI configures itself according to the MPO or Relay3 jumper selection, disabling the MPO on a short.
- Full LED IndicationLEDs show power to the MCC and MPO, relay and MPO activated states, internal communications, GPI state and GPI line fault.
- Field Wiring TerminalsTerminals accept 0.2 - 2.5 mm2 (30-12 AWG) with a 2.7K Ohm end of line resistor.
- Not UL Or ULC ApprovedVIC-030 is not approved by UL and is not approved by ULC.
Description
This is the version of the VLF Multifunction Control Card carrying the Monitored 24 V Powered Output, so a VESDA VLF detector can drive and supervise an external sounder or beacon circuit as well as switch its own relay contacts. The MPO is disabled if there is a short on the GPI.
The VLF MCC is specifically designed for installation in VESDA VLF smoke detectors and supports VLF-250 and VLF-500. It is quick and simple to install and runs out of the box, with minimal configuration needed for the extra features. Detector ambient temperature runs from 0 to 40°C (32 to 104°F), with humidity between 5% and 95%, non-condensing. Note that VIC-030 is not approved by UL and is not approved by ULC, so it must not be treated as a UL or ULC approved component.
Read the full technical description
VIC-030 is the VESDA VLF MCC with MPO, a Multifunction Control Card that installs in VESDA VLF smoke detectors and adds a Monitored 24 V Powered Output alongside its relays and monitored input. The MPO provides power to devices such as sirens or strobes and monitors the line integrity, taking a 24 VDC input, drawing 100 mA more than the MPO output load and delivering up to 1 A (maximum).
Jumper configuration J9 J10 selects either a third relay or the 24 V MPO. Where MPO is chosen, the output follows ALERT unless disabled, and the self-configuring GPI becomes a disable input - an end of line reading leaves the MPO enabled, a short disables it, and an open circuit leaves it enabled while raising Fault # 111/IFF8. Where Relay3 is chosen instead, the GPI is set to External Fault, for example to monitor a mains power supply, and Relay 3 follows the VLF DISABLED or STANDBY status. Onboard LEDs indicate power to the MCC, power to the MPO, relay and MPO activated states, MPO power and line fault, internal communications, GPI state and GPI line fault.
Field wiring is accepted on terminals of 0.2 - 2.5 mm2 (30-12 AWG), with a 2.7K Ohm end of line resistor, in a card of 110 mm x 70 mm x 20 mm. Approvals are CE (EMC & CPR) and AFNOR; VIC-030 is not approved by UL and is not approved by ULC.
Specifications
| Order code description | VIC-030 VESDA VLF MCC mit MPO |
|---|---|
| Dimensions | 110mm x 70mm x 20mm (Länge x Breite x Höhe) |
| Weight | 0,08 kg |
| Connections | 0,2 - 2,5 mm² (30-12 AWG) |
| Power consumption | 1 W vom Detektor bei 24 VDC (unter 42 mA) |
| Relay outputs | 2 A bei 30 VDC |
| Mpo input power | 24 VDC (nur bei der VIC-030) |
| Mpo input current | 100 mA höher als die MPO Ausgangslast (nur bei der VIC-030) |
|---|---|
| Mpo output current | 1 A (Maximum) (nur bei der VIC-030) |
| End of line resistor | Linienendwiderstand (MPO & GPI) 2,7 K Ohm |
| Tested temperature | Geprüft bei -10 bis 55°C |
| Detector ambient temperature | Umgebungstemperatur des Detektors 0 bis 40°C |
| Humidity | 5 % bis 95 % (nicht kondensierend) |
| Relays provided | Verfügt über zwei (2) zusätzliche Relais |
Specifications per manufacturer documentation, subject to change. E&OE.
Optional accessories
- VLF-250-00Small Area Detectorcompatible / works with: Small Area Detector£1,338.03ex VAT£1,605.64 inc VATIn stock
- VIC-020Multi-Function Control CardAlternative - same VESDA VLF multi-function control card without the MPO option.£262.78ex VAT£315.34 inc VATIn stock