VESDA Multi-function Control Card
| Part no. | VIC-020 |
|---|---|
| Brand | VESDA |
| Range | VESDA Programming and Connectivity |

Image for illustration; item supplied may differ
At a glance
- VLF Multi-function Control CardVIC-020 is the VESDA VLF Multi-function Control Card, an interface card for VESDA VLF smoke detectors.
- Two Additional RelaysThe card provides two additional relays, with Relay 1 output ALERT and Relay 2 output FIRE-2.
- Extra Monitored GPIIt provides an extra GPI with line monitoring, giving a VLF two (2) General Purpose Inputs in total.
- Four Alarm Levels ReportedThe MCC allows reporting of all four (4) alarm levels on dry relay outputs.
- Relay And Line RatingsRelay outputs are rated 2 A at 30 VDC and the end of line resistor is 2.7K Ohm.
- Detector-Powered CardPower consumption is 1 W at 24 VDC drawn from the detector, at less than 42 mA.
- VLF-250 And VLF-500 SupportThe card supports VLF-250 and VLF-500 and is fully compatible with VESDA VLF smoke detectors.
- Approved To EN 54-20Approval covers AFNOR, CE - EMC and CPR and EN 54-20.
Description
Installing a VLF MCC into a VLF detector gives an installer more connectivity, more fault detection and monitoring, and fuller annunciation of alarms and faults than the detector offers on its own. Improved connectivity to the fire alarm control panel comes from reporting all four (4) alarm levels on dry relay outputs.
The card is quick and simple to install and works out of the box, with only minimal configuration needed for the extra features. Field wiring is accepted on terminals sized 0.2 - 2.5 mm2 (30-12 AWG), and the card is fully compatible with VESDA VLF smoke detectors.
Read the full technical description
VIC-020 is the VESDA VLF Multi-function Control Card, an interface card that widens the input and output communications a VLF smoke detector can perform. It adds two relays and an extra General Purpose Input with line monitoring, so that a detector fitted with the card has two GPIs in total and can report all four (4) alarm levels on dry relay outputs to a fire alarm control panel.
Relay 1 is assigned to ALERT and Relay 2 to FIRE-2, each following the latching configuration of the matching VLF status, while the GPI input is assigned to FAULT. On that input an end of line condition reads as no fault, a short is reported as Fault # 115/IFF6 and an open circuit as Fault # 111/IFF8; the end of line resistor is 2.7K Ohm and the relay contacts are rated 2 A at 30 VDC.
Power consumption is 1 W at 24 VDC drawn from the detector, at less than 42 mA. The card weighs 0.08 kg (0.176 lb) and has been tested to -10 to 55°C (14 to 131°F), with relative humidity running from 5% to 95% (non-condensing). It carries AFNOR, CE - EMC and CPR and EN 54-20 approval, and supports VLF-250 and VLF-500.
Specifications
| Description | VESDA VLF MCC |
|---|---|
| Dimensions | 110mm x 70mm x 20mm (Länge x Breite x Höhe) |
| Weight | 0,08 kg |
| Connections | 0,2 - 2,5 mm2 (30-12 AWG) |
| Power consumption | 1 W vom Detektor bei 24 VDC (unter 42 mA) |
| Relay outputs | 2 A bei 30 VDC |
| End of line resistor | 2,7 K Ohm (Linienendwiderstand MPO & GPI) |
| Tested temperature | Geprüft bei -10 bis 55°C |
|---|---|
| Detector ambient temperature | Umgebungstemperatur des Detektors 0 bis 40°C |
| Humidity | 5 % bis 95 % (nicht kondensierend) |
| Number of relays | Verfügt über zwei (2) zusätzliche Relais |
| General purpose inputs | Verfügt über einen zusätzlichen GPI mit Leistungsüberwachung; ein VLF verfügt mit MCC über zwei (2) allgemeine Eingänge (GPIs) |
| Relay 1 output | VIC-020 Ausgang für Relais 1: Infoalarm (richtet sich nach der Sperrkonfiguration des VLF Infoalarmstatus) Ausgang für Relais 2: HAUPTALARM-2 (richtet sich nach der Sperrkonfiguration des VLF HAUPTALARM-2 Status) Input for GPI: FEHLER/STÖRUNG Der GPI gibt bei folgenden Bedingungen Statusberichte:; EOL > Kein Fehler; Short > Fehler# 115/IFF6; O/C > Fehler# 111/IFF8 |
| Relay 2 output | VIC-020 Ausgang für Relais 2: HAUPTALARM-2 (richtet sich nach der Sperrkonfiguration des VLF HAUPTALARM-2 Status) |
Specifications per manufacturer documentation, subject to change. E&OE.
Optional accessories