Skip to content

Trade prices shown ex VAT. Order by 3pm for same-day dispatch on stocked lines, UK mainland. Free UK delivery on orders over £250 ex VAT.

Part Number or the Week S3EP-V-VAD-HPR-R

Honeywell Transformer Rectifier 24VDC 4.0A

Part no.HLS-PSU-TR40
BrandHoneywell
RangeTransformer Rectifier

Image for illustration; item supplied may differ

At a glance

  • TR 4amp Door Hold SupplyHLS-PSU-TR40 is the TR 4amp door hold transformer-rectifier at 24V 4A.
  • 230Vac Mains InputMains input is 230Vac, 50Hz nominal at 500mA maximum.
  • Switched Output to MagnetsThe output is 22-30vdc dependent on load at 4A maximum, switched 24v to a door retainer magnet.
  • Fused Input and OutputThe mains input fuse is T1.0A 20mm, 250Vac HBC and the load output fuse is F4A 20mm, 250Vac glass.
  • Mains and Fault IndicatorsA green LED shows mains present and an amber LED shows an output fuse blown.
  • Control Contact SwitchingAn open circuit at the control contact leaves the output ON while a short circuit switches it OFF, and +24vdc from an external supply also switches the output OFF.
  • Steel CaseThe case is 1.2mm steel, white powder coated, at 200 x 230 x 80mm and 3.5Kg.
  • Operating and Storage TemperatureThe unit works from -10 to +40 °C and is stored between -20 to +80 °C.

Description

Rated 24V 4A, HLS-PSU-TR40 is the TR 4amp model in the door hold family. Mains at 230Vac, 50Hz nominal goes in; 22-30vdc dependent on load comes out, and a switched 24v feed reaches the door retainer magnet.

Two indicators report status, green for mains present and amber for an output fuse blown. Output control is by contact, open for output ON and short for output OFF, and +24vdc applied externally also drops the output.

HLS-PSU-TR40 is a door hold transformer-rectifier, the TR 4amp model, running from a 230Vac, 50Hz nominal mains supply and putting out switched 24v to door retainer magnets. Output sits at 22-30vdc dependent on load, with a load current of 4A maximum.

Mains input current is 500mA maximum, protected by a T1.0A 20mm, 250Vac HBC fuse, while the load output is guarded by an F4A 20mm, 250Vac glass fuse. A green LED shows mains present and an amber LED signals an output fuse blown.

Output switching answers to a control contact, where an open circuit leaves the output ON and a short circuit turns it OFF, and applying +24vdc from an external supply also switches the output OFF.

Read the full technical description

A white powder coated steel case of 1.2mm holds it all at 200 x 230 x 80mm and 3.5Kg. The 04390-31 and 04390-41 magnet door holders belong to the same Electromagnetic Door Holders range.

HLS-PSU-TR40 is a door hold transformer-rectifier, the TR 4amp model, running from a 230Vac, 50Hz nominal mains supply and putting out switched 24v to door retainer magnets. Output sits at 22-30vdc dependent on load, with a load current of 4A maximum.

Mains input current is 500mA maximum, protected by a T1.0A 20mm, 250Vac HBC fuse, while the load output is guarded by an F4A 20mm, 250Vac glass fuse. A green LED shows mains present and an amber LED signals an output fuse blown.

Output switching answers to a control contact, where an open circuit leaves the output ON and a short circuit turns it OFF, and applying +24vdc from an external supply also switches the output OFF.

The case is 1.2mm steel, white powder coated, at 200 x 230 x 80mm and 3.5Kg, working from -10 to +40 °C and stored between -20 to +80 °C. The switched output goes to a door retainer magnet. Within the Electromagnetic Door Holders range sit the 04390-31 magnet door holder, drawing 22mA at 24V DC, and the floor mounted 04390-41 at 45mA.

Specifications

DescriptionDoor Hold Transformer-Rectifier 24V 4A
Input voltage230Vac, 50Hz nominal
Input current500mA maximum
Mains input fuseT1.0A 20mm, 250Vac HBC
Output voltage22-30vdc dependent on load
Load current4A maximum
Load output fuseF4A 20mm, 250Vac glass
Dimensions200 x 230 x 80mm (HxWxD)
Weight3.5Kg
Case material1.2mm steel, white powder coated
Operating temperature-10 to +40 OC
Humidity95%
Storage temperature-20 to +80 OC

Specifications per manufacturer documentation, subject to change. E&OE.