FAAST-8100E
Fact-checked against 3 source sections — 11 facts verified, 0 conflicts resolved, 5 gaps flagged.
Complete the system
Recommended add-ons & expansion (1)
ASD Mains Powered Interface for FAAST LT. Batteries not included - requires 2 x 4015-604-YFR (Power Sonic Flame Retardant 12V 14Ah) to meet compliance regulations.
S4 ASD Interface Unit (S4-34440-ASD): the FAAST 8100E True aspirating unit wires to an ASD
Spares & consumables (1)
AIR FILTER FOR FAAST 7100E, 8100E & 9400X
Replacement air filter: F-A3384-000 (30 micron) for the FAAST 8100 series aspiration detec
The Xtralis FAAST-8100E is a true aspirating smoke detection unit built around two laser detectors for high-sensitivity early warning. Supplied with two 12V 14Ah Powersonic batteries and capable of 24-hour standby power via the ASD Interface Unit (S4-34440-ASD), it is commissioned using PipeIQ with configurable Fire and Fault relays. It is available as the pre-configured 8100-VIG-INT bundle (S4-34440-ASD plus 8100E plus EOL PCB) and selected as 'ASD 8100E' on the Vigilon panel.
Key features · 6
Technical data · 6 specs
| Batteries (supplied) | 2 x 12 V 14Ah Powersonic Ba |
|---|---|
| Standby power (via asd interface unit) | 24-hour standby power provided by an ASD Interface Unit (S4-34440-ASD) with 12V 14Ahr batteries |
| Eol terminal pcb terminal alignment | Align pins with terminals TB1 to TB10 on the FAAST unit |
| Bundle sku | 8100-VIG-INT (S4-34440-ASD + 8100E + EOL PCB) |
| Vigilon device setting | Select 'ASD 8100E' for a FAAST 8100E bundle (8100-VIG-INT) |
| Service note (filter replacement) | Turn off the system by removing the 24 Volt power connector from the unit |