Air Filter Assembly · FAAST

Xtralis F-A3384-000 FAAST 8100 Air Filter Assembly

Product type
Air Filter Assembly
Filter rating
30 micron filter
Supplied state
comes fully assembled and ready to use
Mounting
Secured to the unit with two Philips head screws (filter mounting screws), located behind the Display Door under the User Interface Card
Screw torque
6in-lb (0.7N-m) or ¼ turn past “lightly snug”. DO NOT OVER TIGHTEN.
Service mode behaviour
If power is not removed, the unit automatically enters Service Mode when the screws are removed from the filter; this removes power from the fan and the sensing chamber, the filter fault indicator is illuminated and the urgent relay is set.
Document reference
I56-3743-003

Overview

What it is and how it fits the system.

The Xtralis F-A3384-000 is a replacement air filter assembly for FAAST 8100 series aspiration detectors, supplied fully assembled and ready to use. It uses a 30-micron filter and secures to the unit with two Philips head screws torqued to 6in-lb (0.7N-m), or a quarter turn past lightly snug. If power is not removed during replacement, the unit automatically enters Service Mode.

Technical overview

F-A3384-000 is an air filter assembly from Xtralis, designed as a replacement component for the FAAST 8100 series aspiration detectors. It is supplied fully assembled and ready to use, featuring a 30-micron filter media for particulate capture in air sampling systems. The assembly secures to the detector unit using two Philips head screws located behind the Display Door, beneath the User Interface Card, with a specified torque of 6in-lb (0.7N-m) or a quarter turn past lightly snug to avoid over-tightening.

During filter replacement, if power remains connected, the FAAST 8100 series detector automatically enters Service Mode upon screw removal. This action disconnects power to the fan and sensing chamber, illuminates the filter fault indicator, and activates the urgent relay to signal maintenance status. The component is referenced in documentation I56-3743-003 and is intended exclusively for use with FAAST 8100 series systems, installed internally behind the display interface. Physical wiring details for the host unit are addressed in the associated installation and maintenance instructions.

Specifications

Full technical data for this part.

Product typeAir Filter Assembly
Filter rating30 micron filter
Supplied statecomes fully assembled and ready to use
MountingSecured to the unit with two Philips head screws (filter mounting screws), located behind the Display Door under the User Interface Card
Screw torque6in-lb (0.7N-m) or ¼ turn past “lightly snug”. DO NOT OVER TIGHTEN.
Service mode behaviourIf power is not removed, the unit automatically enters Service Mode when the screws are removed from the filter; this removes power from the fan and the sensing chamber, the filter fault indicator is illuminated and the urgent relay is set.
Document referenceI56-3743-003

Specifications sourced from manufacturer documentation.