Gent Evac Smart EACIE 2 BS8629 Panel (24 Zone) Loop based, requires FACP, excluding Gerda box. Includes Battery

Part no.EACIE2
BrandGent
RangeEACIE Panel
Sub-rangeEvac Smart Panel
Honeywell EACIE2 fire safety panel in grey metal casing, front view. — main product photo

Image for illustration; item supplied may differ

At a glance

  • 24 evacuation zonesTwo 12-zone fascia sections provide 24 separate zone controls in the EACIE2.
  • Individual zone switchesEach of the 24 zones has its own switch for the Fire and Rescue Service to activate or silence the alarms in that zone.
  • Separate evacuation and fault LEDsRed evacuation and yellow fault LEDs sit beside each EACIE2 zone switch, keeping the two indications distinct.
  • Panel status and buzzer controlsMains power, power fault and general fault indicators share the upper panel strip with a buzzer silence button operated by a four-second press.
  • Site zone labelsThe EvacSmart range supports engraved floor, flat or zone labels. The EACIE2 has building-name space below its two zone-control sections.
  • Battery includedThe EACIE2 includes its battery and requires a dedicated FACP. It fits inside a separately supplied GERDA enclosure.

Description

The Gent EACIE2 is a 24-zone EvacSmart evacuation alert panel for manual control by the Fire and Rescue Service. Its two 12-zone fascia sections have a switch for each zone, with red evacuation and yellow fault LEDs beside it. Labels can be engraved to match the floors, flats or zones on site. The panel requires a dedicated fire alarm control panel and fits inside a separate GERDA enclosure. It is supplied with a battery; the GERDA enclosure is excluded. Mains power, power fault and general fault indicators sit above the zone controls, alongside a button that silences the panel buzzer.

The EACIE2 provides 24 evacuation zones across two 12-zone fascia sections. The front layout has two sections in the left column, with zones 1-12 below zones 13-24. Each zone has its own evacuation switch and separate evacuation and fault LEDs. The EvacSmart range supports engraved zone descriptions to identify floors, flats or zones, with space below each section for the building name.

Read the full technical description

The EACIE2 provides 24 evacuation zones across two 12-zone fascia sections. The front layout has two sections in the left column, with zones 1-12 below zones 13-24. Each zone has its own evacuation switch and separate evacuation and fault LEDs. The EvacSmart range supports engraved zone descriptions to identify floors, flats or zones, with space below each section for the building name.

The EACIE2 requires a dedicated fire alarm control panel, or FACP. The EvacSmart system uses a Vigilon FACP with at least two loops: one connects the EACIE controls, while a separate loop serves the sounders and visual alarm devices through T-breaker runs. The evacuation system is separate from the building fire detection system. The FACP is located in a secure area near the EACIE for access by service personnel.

The 24 switches let the Fire and Rescue Service select the zones to evacuate. Moving a switch to the right activates the alarms in its zone; moving it left silences that zone. A flashing red LED indicates evacuation and a yellow LED indicates a zone fault. The common panel indicators show mains power, a mains or battery fault, and general system fault. Holding the buzzer button for four seconds silences the panel buzzer.

The EACIE2 is supplied with a battery and excludes the GERDA enclosure. EvacSmart panels install inside the separately supplied GERDA security enclosure, using the external panel brackets and the enclosure H-bracket studs. M6 nuts and washers secure the panel in place. The installer provides the cable, glands and associated installation accessories. The mains connection requires an unswitched 5 A fused spur and protective earthing.

The EvacSmart range operates from 230 V mains at 50 or 60 Hz, with a supply tolerance of -15% to +10% and a single 12 V, 7 Ah sealed lead acid backup battery. Its enclosure dimensions are 448 mm wide, 501 mm high and 181 mm deep, with a RAL 7035 finish. Range operating limits are -5 °C to +40 °C and up to 90% non-condensing relative humidity at +5 °C to +40 °C; storage limits are -10 °C to +55 °C.

Commissioning the EvacSmart system links each EACIE2 zone switch to its corresponding sector through a command build. Devices on a floor use matching zone and sector numbers. The EACIE MRC uses zone 128 without a sector assignment, sector links are removed, and a separate command build provides buzzer silencing. Individual sounder tests, detailed fault information and the event log are accessed at the dedicated FACP. A connected Honeywell CLSS Gateway also provides access through the CLSS App or Site Manager.

Specifications

Product rangeGent EvacSmart BS8629 evacuation alert system
Evacuation zones24
Fascia sections2 × 12 zones
Zone controls24 individual evacuation switches
Zone evacuation indication24 red LEDs
Zone fault indication24 yellow LEDs
Common indicatorsMains power on, power fault and general fault
Buzzer silencePress and hold for 4 seconds
Zone identificationEvacSmart range: engraved floor, flat or zone descriptions
Building identificationName space below each of the 2 fascia sections
System arrangementEvacSmart range: dedicated manual evacuation system
Control panel requirementDedicated FACP required
GERDA enclosureRequired separately; excluded from supply
Battery supplyIncluded
Power sourceEvacSmart range: mains supply with battery backup
Mains supplyEvacSmart range: 230 V, -15%/+10%, 50/60 Hz
Mains input currentEvacSmart range: 1.4 A
Mains connectionEvacSmart range: unswitched 5 A fused spur
PSU fuseEvacSmart range: FS3 T3.15AH250V, ceramic, 20 × 5 mm
Backup batteryEvacSmart range: one 12 V, 7 Ah sealed lead acid, fire-rated battery
Enclosure dimensionsEvacSmart range: 448 W × 501 H × 181 D mm
Enclosure finishEvacSmart range: RAL 7035
Operating temperatureEvacSmart range: -5 °C to +40 °C
Storage temperatureEvacSmart range: -10 °C to +55 °C
Relative humidityEvacSmart range: up to 90%, non-condensing, at +5 °C to +40 °C
MountingEvacSmart range: external brackets on GERDA H-bracket studs
Individual sounder testingEvacSmart system: at the dedicated FACP
Event logEvacSmart system: at the dedicated FACP
MRC configurationEvacSmart system: zone 128; no sector assignment

Specifications per manufacturer documentation, subject to change. E&OE.

Documents

DocumentTypeSizeDownload
Installation manual (EACIE1, EACIE2, EACIE3, EACIE4)Installation37.5 MBDownload PDF

Optional accessories

FAQs

How are the EACIE2 controls arranged?

The EACIE2 has 24 evacuation zones arranged across two 12-zone fascia sections. Its layout uses two sections in the left column, with zones 1-12 below zones 13-24. Every zone has an individual switch, a red evacuation LED and a yellow fault LED. The EvacSmart range supports engraved descriptions for the floors, flats or zones served by those controls. Building-name space sits below each fascia section, while the common power indicators and buzzer silence button sit above the zone controls.

Does the EACIE2 need a separate fire alarm control panel?

Yes. The EACIE2 requires a dedicated FACP as part of the EvacSmart evacuation system. The range uses a Vigilon control panel with at least two loops, separating the EACIE controls from the sounder and visual alarm device loop. The building fire detection system remains independent of the evacuation system. The FACP is positioned in a secure area close to the EACIE, where service personnel can access individual sounder tests, detailed fault information and the event log.

What comes with the EACIE2, and is GERDA included?

The EACIE2 includes a battery, while the GERDA security enclosure is supplied separately. EvacSmart panels fit inside that enclosure using the panel mounting brackets and the GERDA H-bracket studs, secured with M6 nuts and washers. A dedicated FACP is also required for the evacuation system. The installer supplies the cables, glands and associated installation accessories. Across the EvacSmart range, the electrical arrangement uses a mains supply and a single 12 V, 7 Ah sealed lead acid backup battery.

How does the Fire and Rescue Service operate the EACIE2?

The EACIE2 gives the Fire and Rescue Service an individual switch for each of its 24 zones. Moving a switch right activates the alarms in that zone; returning it left silences them. A flashing red LED indicates evacuation, while the separate yellow LED indicates a zone fault. Common indicators show mains power, power faults and general system faults. The panel buzzer can be silenced by pressing and holding its button for four seconds.

How are the EACIE2 zone switches configured?

Within the EvacSmart system, each EACIE2 switch is linked to the sector it controls through a command build. Devices serving a floor share matching zone and sector numbers. The EACIE MRC is assigned to zone 128 without a sector, and sector links are removed. A separate command build handles buzzer silencing. The dedicated FACP provides individual sounder testing and the event log, with additional access available through a connected Honeywell CLSS Gateway and the CLSS App or Site Manager.