Skip to content

Trade prices shown ex VAT. Order by 3pm for same-day dispatch on stocked lines, UK mainland. Free UK delivery on orders over £250 ex VAT.

Part Number or the Week S3EP-V-VAD-HPR-R

System Sensor Red Flash, Pure White Body, Clear Lens, c/w Isolator. Loop-powered EN54-23 C Category - Standard Performance Detector Base Sounder Strobe. EN54-23 certified. Coverage volume code: C-3-8.5 (Standard) / O-1-3 (Legacy)

Part no.BRS-PC-I00
BrandSystem Sensor
RangeAddressable Audio Visual Devices
Sub-rangeBase Sounder VAD

Image for illustration; item supplied may differ

At a glance

  • Standard Base Sounder StrobeBRS-PC-I00 is the standard product variant, a modular loop powered sounder and strobe device (VAD).
  • Standard Mode Coverage RatingStandard mode is rated C-3-8.5 to EN54-23, a cylinder Ø = 8.5m from 3m installation height covering 170 m3.
  • Loop Powered On Morley-IAS ProtocolThe device is loop powered, communicating on Morley-IAS Protocol, with standby demand of 150 uA maximum.
  • 18mA Alarm ConsumptionIn standard mode the device draws a typical maximum of 18mA at 24V with tone 3 at high volume.
  • 32 Tones And 96dB OutputThe 32 tone set is global and approved, selectable at the device or from the panel, and sound output is 96dB (A) ±3dB @ 1metre with tone 3 at high volume and 24V.
  • Red Flash At 0.5 HzIn standard mode the strobe gives a red flash at 0.5 Hz.
  • Environmental Operating RangeAmbient range is -10°C to 55°C with relative humidity to 93% ± 3%, non-condensing, and IP21C is reached with the low profile B501AP base and the IP seal in place.
  • Approved To EN54 PartsApproval is held to EN54-3, EN54-17 and EN54-23, with manufacture under the Construction Products Regulation (CPR).

Description

One ceiling point, two warnings: the device sounds the alarm and flashes it. BRS-PC-I00 is the standard product in this range, drawing everything it needs from the loop and answering on Morley-IAS Protocol. It goes up by twist fit onto the universal B501AP base, and the red flash B501 base is supported as well.

Coverage in standard mode is rated C-3-8.5 under EN54-23, which is a cylinder Ø = 8.5m seen from 3m installation height, or 170 m3 of protected volume, with the red strobe running at 0.5 Hz. Demand at 24V with tone 3 at high volume is a typical maximum of 18mA, against a standby figure of 150 uA maximum.

BRS-PC-I00 is the standard product in the Honeywell Morley-IAS range of intelligent detector base sounder strobes, a modular loop powered device whose purpose is to alert building occupants to a potential fire from one ceiling position. Communication with the panel is on Morley-IAS Protocol.

Standard mode gives an EN54-23 coverage code of C-3-8.5, taken at 3m installation height over a cylinder Ø = 8.5m for a volume of 170 m3. The strobe flashes red at 0.5 Hz in that mode. Sound output reaches 96dB (A) ±3dB @ 1metre, measured with tone 3 at high volume and 24V, and in those conditions the device draws a typical maximum of 18mA. The supply is 15 to 29 VDC (Isolation) and standby is 150 uA maximum.

Read the full technical description

Commissioning is helped along by rotary wheels and address tags for clear address indication, a 32 tone set that can be picked at the device or from the panel, and adjustable sound, light and tones to suit varying installation applications. A loop continuity spring supports first fix, cable entry is rear or surface with large cable access, and individual components can be replaced separately.

BRS-PC-I00 is the standard product in the Honeywell Morley-IAS range of intelligent detector base sounder strobes, a modular loop powered device whose purpose is to alert building occupants to a potential fire from one ceiling position. Communication with the panel is on Morley-IAS Protocol.

Standard mode gives an EN54-23 coverage code of C-3-8.5, taken at 3m installation height over a cylinder Ø = 8.5m for a volume of 170 m3. The strobe flashes red at 0.5 Hz in that mode. Sound output reaches 96dB (A) ±3dB @ 1metre, measured with tone 3 at high volume and 24V, and in those conditions the device draws a typical maximum of 18mA. The supply is 15 to 29 VDC (Isolation) and standby is 150 uA maximum.

The device is rated for ambient temperatures of -10°C to 55°C and humidity of 93% ± 3%, non-condensing. IP21C is reached where the base used is the low profile B501AP and the IP seal is in place. Manufacture falls under the Construction Products Regulation (CPR), and approval is held to EN54-3, EN54-17 and EN54-23.

Specifications

Product code (standard)BRS-PC-I00
Standard product (mi variant)MI-BRS-PC-I
Supply voltage15 to 29 VDC (Isolation)
Operating voltage range15 to 29V
Standby current150 uA maximum
Typical max current consumption @ 24v, tone 3 @ high volume (standard mode)18mA
Typical max current consumption @ 24v, tone 3 @ high volume (legacy mode)8mA
Sound output, typical96dB (A) ±3dB @ 1metre (Tone 3, high volume @ 24V)
Tone setGlobal & approved 32 tone set, selectable from device or from panel
Strobe flash rate0.5 Hz / 1 Hz (Legacy mode)
Flash rate (standard mode)0.5 Hz
Flash rate (legacy mode)1 Hz
Flash colourRed
En 54-23 coverage volume code (standard mode)C-3-8.5

Specifications per manufacturer documentation, subject to change. E&OE.

Optional accessories