Skip to content

Trade prices shown ex VAT. Order by 3pm for same-day dispatch on stocked lines, UK mainland. Free UK delivery on orders over £250 ex VAT.

Part Number or the Week S3EP-V-VAD-HPR-R

System Sensor Optical conventional detector

Part no.2020P
BrandSystem Sensor
RangeConventional Detection Vision Range
Sub-rangeDetector
System Sensor 2020P Optical Smoke Detector — white circular unit, VISION-embossed dome, LED at base

Image for illustration; item supplied may differ

At a glance

  • Photo-Electronic Optical Smoke DetectorThe 2020P uses an optical chamber together with an ASIC to detect fires quickly and accurately.
  • EN54 Part 7 ApprovalIt is approved to EN54-7:2000 (Amendment 1) and marked 0832 0832-CPD-0181.
  • Automatic Drift CompensationThe detector provides automatic drift compensation.
  • Low Current DrawQuiescent current is 45µA Typical, at 24VDC, 25°C, with a maximum standby current of 60μA @ 24VDC.
  • Latching Alarm With LEDThe integral LED gives a local alarm signal and latches until reset by momentary power interruption.
  • Low Profile HeadThe head is a low profile moulding, 102mm in diameter and 32.5mm tall, plus 9.5mm where a standard base is used.
  • Standard And Deep BasesIt mounts on the 2020B and 2020BSD standard bases or the 2020DB and 2020DBSD deep bases.
  • Remote Laser TriggerA hand held laser tool with a range of several metres can be used to remotely trigger the detector.

Description

Optical smoke sensing in the Vision conventional family is covered by the 2020P, an optical chamber and ASIC combination from System Sensor. Its approval is EN54-7:2000 (Amendment 1) against EN54 part 7, with LPCB and CE approval and the marking 0832 0832-CPD-0181.

Current demand is modest: 45µA Typical, at 24VDC, 25°C quiescent, no more than 60μA @ 24VDC in standby and 70mA @ 28VDC while in alarm, all on a 14 to 28VDC (Nominal 24VDC) line. An alarm latches until a momentary power interruption clears it, lit on the integral LED and repeatable at a remote LED. The detector features automatic drift compensation.

The 2020P is a conventional photo-electronic optical smoke detector in the Vision range, pairing an optical chamber with an ASIC to detect fires quickly and accurately. It is a System Sensor product, approved to EN54-7:2000 (Amendment 1), declared against EN54 part 7, LPCB Approved and CE Approved, and marked 0832 0832-CPD-0181.

The head works from 14 - 28 VDC, taking 45µA Typical, at 24VDC, 25°C when quiescent and a maximum standby current of 60μA @ 24VDC, with 70mA @ 28VDC drawn in alarm. Alarms latch and are reset by momentary power interruption, shown on the integral LED, and a remote LED annunciator can repeat that indication. Automatic drift compensation is provided.

The head is a low profile design, 102mm in diameter and standing 32.5mm high, with 9.5mm more for a standard base, moulded in ABS to approximate RAL9016 and weighing 75g before the 45g the base adds. Terminals accept 0.4mm² to 2.0mm² conductors, and the detector is rated for -30ºC to +70ºC across 5 to 95% Relative Humidity (non-condensing).

Read the full technical description

The body spans 102mm across, its height 32.5mm before a standard base adds 9.5mm, and it weighs 75g plus the 45g of that base, in ABS approximating RAL9016. It fits 2020B, 2020BSD, 2020DB or 2020DBSD bases and answers to the 2020LT laser tool for remote triggering.

The 2020P is a conventional photo-electronic optical smoke detector in the Vision range, pairing an optical chamber with an ASIC to detect fires quickly and accurately. It is a System Sensor product, approved to EN54-7:2000 (Amendment 1), declared against EN54 part 7, LPCB Approved and CE Approved, and marked 0832 0832-CPD-0181.

The head works from 14 - 28 VDC, taking 45µA Typical, at 24VDC, 25°C when quiescent and a maximum standby current of 60μA @ 24VDC, with 70mA @ 28VDC drawn in alarm. Alarms latch and are reset by momentary power interruption, shown on the integral LED, and a remote LED annunciator can repeat that indication. Automatic drift compensation is provided.

The head is a low profile design, 102mm in diameter and standing 32.5mm high, with 9.5mm more for a standard base, moulded in ABS to approximate RAL9016 and weighing 75g before the 45g the base adds. Terminals accept 0.4mm² to 2.0mm² conductors, and the detector is rated for -30ºC to +70ºC across 5 to 95% Relative Humidity (non-condensing).

Bases available run from 2020B and 2020BSD at standard height to 2020DB and 2020DBSD in deep form, giving application flexibility and compatibility with conventional fire alarm panels of many kinds. The 2020LT hand held laser tool, effective over several metres, provides the remote alarm trigger feature.

Specifications

Operating voltage range14 to 28VDC (Nominal 24VDC)
Supply voltage14 - 28 VDC
Quiescent current45µA Typical, at 24VDC, 25°C
Maximum standby current @ 25ºc60μA @ 24VDC
Maximum alarm current70mA @ 28VDC
Latching alarmReset by momentary power interruption
Diameter102mm
Height32.5mm (plus 9.5mm for standard base)
Weight75g (plus 45g for standard base)
MaterialABS
ColourApproximates RAL9016
Max wire gauge for terminals0.4mm² to 2.0mm²
Application temperature range-30ºC to +70ºC
Humidity5 to 95% Relative Humidity (non-condensing)

Specifications per manufacturer documentation, subject to change. E&OE.