Gas Detection XCL
VESDA Sensepoint XCL XCL-VEA-CO2VV-RM CO2 Modbus 5% v/v
- Ordering code description
- VESDA Sensepoint XCL CO 2 5% v/v Modbus Relay for VEA
- Gas detected
- Carbon Dioxide (CO 2 ): 5.0% v/v (adjustable 1.0 – 5.0% v/v)
- Product family
- VESDA Sensepoint XCL MICRO BORE — Aspirated Gas Detection for Micro Bore ASD System (VESDA-E VEA Addressable Aspirating Smoke Detection)
- Supply voltage
- 24 VDC nominal; 11 to 32V DC (Analog 4-20 mA); 9 to 32V DC (Modbus); 24V AC 50/60Hz Nominal (20 to 27 VAC)
- Maximum inrush current
- 850 mA (24V DC)
- Ingress protection
- IP65, Type 4 (NEMA 250)
- Operating temperature
- −20 to +50 °C (−4 to +122 °F)
Overview
What it is and how it fits the system.
The XCL-VEA-CO2VV-RM is a VESDA Sensepoint XCL Micro Bore aspirated carbon dioxide (CO2) gas detector that inserts in-line into a VESDA-E VEA tube network, set to 5.0% v/v and adjustable from 1.0 to 5.0% v/v. It provides Modbus RTU output plus relays, runs on 24V DC nominal and is rated IP65 (Type 4 / NEMA 250) in a 113 x 113 x 59 mm enclosure.
Technical overview
XCL-VEA-CO2VV-RM is the Xtralis VESDA Sensepoint XCL carbon dioxide detector ordered with Modbus RTU communications and relays, part of the Sensepoint XCL Micro Bore aspirated gas detection line for the VESDA-E VEA addressable aspirating smoke detection system. Carbon dioxide detection is set at 5.0% v/v, with the setting adjustable between 1.0 and 5.0% v/v.
Upkeep draws on a defined parts set: the XCL-SC-CO2VV replacement sensor and XCL-FILTER replacement filter are the listed spares, while the XCL-VEA-CAL calibration/flow cap, XCL-VEA-TUB tubing interface, XCL-M20-CG cable glands and XCL-COVER sensor cover are the recommended accessories. Field wiring lands on pluggable rising clamp terminals, and physical connection detail sits in the installation manual.
Network placement is in-line: the detector joins VEA micro bore tube of 6 mm (1/4 in) OD through flexible tubes, and VSC and VSM4 integration provides remote access to detectors. Configurable relays and interfaces to PLCs, HVAC, BMS and fire alarm control panels complete the system connections, with Bluetooth 4.0 (Bluetooth Low Energy) linking a compatible smart device running iOS 10 or Android 4.3 or above at up to 10 m (mobile device dependent).
Specifications
Full technical data for this part.
| Ordering code description | VESDA Sensepoint XCL CO 2 5% v/v Modbus Relay for VEA |
|---|---|
| Gas detected | Carbon Dioxide (CO 2 ): 5.0% v/v (adjustable 1.0 – 5.0% v/v) |
| Product family | VESDA Sensepoint XCL MICRO BORE — Aspirated Gas Detection for Micro Bore ASD System (VESDA-E VEA Addressable Aspirating Smoke Detection) |
| Supply voltage | 24 VDC nominal; 11 to 32V DC (Analog 4-20 mA); 9 to 32V DC (Modbus); 24V AC 50/60Hz Nominal (20 to 27 VAC) |
| Maximum power consumption | 1.2 W (Analog 4-20mA) (toxic), 1.7W (flammable and CO2); 0.7 W (Modbus) (toxic), 1.2W (flammable and CO2); Relay Version: additional 0.6W total |
| Maximum inrush current | 850 mA (24V DC) |
| Output | Analog Output: 0 to 22 mA; Digital Output: Modbus RTU; Relay Output: 2 relays (24 V DC / 250 V AC, 5 A) |
| Dimensions | 113 x 113 x 59 mm (4.4 x 4.4 x 2.3 in) (WxHxD) |
| Weight | 500 g (1.1 lb) |
| Ingress protection | IP65, Type 4 (NEMA 250) |
| Casing material | Polycarbonate (charcoal colour) |
| Operating temperature | −20 to +50 °C (−4 to +122 °F) |
| Storage temperature | 0 to +30 °C (+32 to +86 °F) |
| Humidity | 0 to 99% (non-condensing) |
Specifications sourced from manufacturer documentation.
Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know
Optional accessories
Optional additions — this product works without them.
VESDA Sensepoint XCL Calibration/Flow Cap for VEA
XCL-VEA-CAL — VESDA Sensepoint XCL Calibration/Flow Cap for VEA
VESDA Sensepoint XCL Tubing Interface for VEA
XCL-VEA-TUB — VESDA Sensepoint XCL Tubing Interface for VEA
VESDA Sensepoint XCL Cable Glands - Pack of 10
XCL-M20-CG — VESDA Sensepoint XCL Cable Glands - Pack of 10
VESDA Sensepoint XCL Sensor Cover with Gasket
XCL-COVER — VESDA Sensepoint XCL Sensor Cover with Gasket
Spares & replacement parts
Replacement parts for units already in service.
VESDA RPL SENS CO2 5% V/V SP XCL
XCL-SC-CO2VV — VESDA Sensepoint XCL Replacement Sensor - CO2 5% v/v
VESDA Sensepoint XCL Replacement Filter - Pack of 10
XCL-FILTER — VESDA Sensepoint XCL Replacement Filter - Pack of 10