ex-VAT pricing shown

Now open for trade ordersGent, Morley-IAS & Xtralis stock added weekly — open to the trade.

Gas Detection XCL

VESDA Sensepoint XCL XCL-VEA-CH4-RM CH4 Modbus Detector

Ordering code description
VESDA Sensepoint XCL CH 0-100% LEL Modbus 4 Relay for VEA
Gas detected
Combustible (CAT): 0 – 100% LEL (Methane, Hydrogen, Propane, Ethanol, Butane, Octane, etc.)
Factory calibration
CAT: Factory calibrated to CH 4
Supply voltage
24 VDC nominal; 11 to 32V DC (Analog 4-20 mA); 9 to 32V DC (Modbus); 24V AC 50/60Hz Nominal (20 to 27 VAC)
Maximum inrush current 24vdc
850 mA
Ingress protection
IP65, Type 4 (NEMA 250)
Operating temperature
−20 to +50 °C (−4 to +122 °F)

Overview

What it is and how it fits the system.

The XCL-VEA-CH4-RM is a VESDA Sensepoint XCL aspirated combustible (CAT) gas detector that inserts in-line into a VESDA-E VEA micro bore tube network, measuring 0-100% LEL and factory-calibrated to methane (CH4). It provides Modbus RTU digital output with two relays, runs on 24V DC nominal and is rated IP65 (Type 4 / NEMA 250) in a 113 x 113 x 59 mm enclosure.

Technical overview

XCL-VEA-CH4-RM is the Modbus RTU variant of the Xtralis VESDA Sensepoint XCL methane detector for VESDA-E VEA microbore tube networks, an addressable aspirated unit that pairs digital communication with two relays. RS 485 Modbus output sits alongside VSC and VSM4 integration for remote access to detectors, and the detector interfaces into PLCs, HVAC, building management systems and fire alarm control panels.

Within the tube network the detector samples from the VEA's 6 mm micro bore line, with flexible tube sections cut to 50 mm and tube clips securing the VEA and flexible tubing parts. For routine attention, the XCL-VEA-CAL calibration and flow cap inserts into the detector module and turns clockwise until locked; XCL-VEA-TUB provides a tubing interface, XCL-FILTER replacement filters are ordered in packs of ten, and XCL-M20-CG cable glands and the XCL-COVER sensor cover with gasket round out the accessory list. Sensor replacement uses the XCL-SC-CH4 cartridge.

Bluetooth Low Energy links a compatible smart device running iOS 10 / Android 4.3 or above at up to 10 m, additional approvals stand at EN 50270 and RED, FCC, BT SIG, and terminal wiring detail lives in the installation manual.

Specifications

Full technical data for this part.

Ordering code descriptionVESDA Sensepoint XCL CH 0-100% LEL Modbus 4 Relay for VEA
Gas detectedCombustible (CAT): 0 – 100% LEL (Methane, Hydrogen, Propane, Ethanol, Butane, Octane, etc.)
Factory calibrationCAT: Factory calibrated to CH 4
Supply voltage24 VDC nominal; 11 to 32V DC (Analog 4-20 mA); 9 to 32V DC (Modbus); 24V AC 50/60Hz Nominal (20 to 27 VAC)
Maximum power consumption 24vdc1.2 W (Analog 4-20mA) (toxic), 1.7W (flammable and CO 2); 0.7 W (Modbus) (toxic), 1.2W (flammable and CO 2); Relay Version: additional 0.6W total
Maximum inrush current 24vdc850 mA
OutputAnalog Output: 0 to 22 mA; Digital Output: Modbus RTU; Relay Output: 2 relays (24 V DC / 250 V AC, 5 A)
Dimensions113 x 113 x 59 mm (4.4 x 4.4 x 2.3 in) (WxHxD)
Weight500 g (1.1 lb)
Ingress protectionIP65, Type 4 (NEMA 250)
Casing materialPolycarbonate (charcoal colour)
Operating temperature−20 to +50 °C (−4 to +122 °F)
Storage temperature0 to +30 °C (+32 to +86 °F)
Humidity0 to 99% (non-condensing)

Specifications sourced from manufacturer documentation.

Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know

Spares & replacement parts

Replacement parts for units already in service.

XCL-SC-CH4

XCL Sensor-Flam Catalytic

Replacement CH4 catalytic sensor cartridge for the XCL CH4 detector.

£330.63
ex VAT
£396.76 inc VAT
Sold separately