Gent Intrinsically safe outdoor call point, 470 ohm.
| Part no. | W1A-R470SG-K013-81 |
|---|---|
| Brand | Gent |
| Range | MCP |
Image for illustration; item supplied may differ
Description
The W1A-R470SG-K013-81 is the Honeywell Morley-IAS intrinsically safe outdoor call point, 470 Ohm, IP67 (Old PN: WCP1A-R470SG-01IS). It is intended for outdoor use within Intrinsically Safe (I.S.) systems using suitable I.S. barriers.
The W1A-R470SG-K013-81 is the INTRINSICALLY SAFE OUTDOOR CALL POINT (IP67), 470 Ohm.
Read the full technical description
The W1A-R470SG-K013-81 is the INTRINSICALLY SAFE OUTDOOR CALL POINT (IP67), 470 Ohm.
An intrinsically safe version of the outdoor call point is available for installation in hazardous areas. These call points are manufactured to protect against other hazards, as defined in paragraph 1.2.7 of annex II of the ATEX Directive 94/9/EC.
They are intended for outdoor use within Intrinsically Safe systems using suitable I.S. barriers.
Dimensions (W x H x D) are 97.5 mm x 93 mm x 71 mm and the weight is 270g, with an operating voltage of 24VDC nominal and an operating temperature range of -25°C to +70°C.
Specifications
| Auxiliary output | Auxiliary Output: 0.25A |
|---|---|
| Combined sector aux current | The combined maximum total current load for sectors and auxiliary output is 0.5A. |
| Channel configuration | factory configured with all four channels as 'Sector' outputs |
| Auxiliary supply | 24V DC SUPPLY FUSED AT 250mA |
| Batteries | 2 x 12V 2.1Ahr BATTERIES |
| Battery voltage | 24V 2.1Ahr BATTERIES |
| Zone eol | 5K6 EOL IS Zone Input (Resistor 5K6K) |
| Sector eol | 10K EOL (Resistor 10K) |
|---|---|
| End of line capacitor | End-of-line units Capacitor 22uF |
| Field cable length | cable length max. 150m |
| Mains supply cable | The mains supply cable must be a standard fire resisting type and should meet PH30 classification, such as any of the standard and enhanced loop cable. Requires a minimum conductor cross sectional area of 0.75mm2. |
| Mains fuse | Fuse 3.15A QB Glass (20mm x 5mm) |
| Sector output loads | Sector Output with Sounders; Sector Output with Inductive load (eg Relay) with Flyback diode |
| Earth continuity | Ensure the board fixing screws are securely fitted as they form part of an earth continuity path to the metal enclosure, this is necessary for electrical safety and for EMC compliance. |
Specifications per manufacturer documentation, subject to change. E&OE.
Documents
| Document | Type | Size | Download |
|---|---|---|---|
| Installation manual (VSINTM-PCB-UPG, W1A-R470SG-K013-81) | Installation | 163 KB | Download PDF |
Optional accessories
- VSINTM-PCB-UPGReplacement Card for Mains Powered Interface (34440)Board product code VSINTM-PCB-UPG£1,030.36ex VAT£1,236.43 inc VATIn stock