Aspirating Smoke Detection
Xtralis VSP-877 Flush-Mount ASD Sampling Point (White)
- Material
- RoHS/REACH compliant
- Sampling hole
- Standard 2 mm (5/64”) pilot sampling hole which can be drilled out up to 5 mm (13/64”)
- Ceiling panel cutout
- 32 mm – 35 mm Ceiling Panel Cutout for mounting
- Capillary diameter
- 6, 8, 10 mm, 1/2”
- Design
- Flush mount design provides less obtrusive installation and improved aesthetics
- Ordering code
- VSP-877 — Flush Mount Sampling Point
- Ordering code black
- VSP-877-B — Flush Mount Sampling Point (Black)
Overview
What it is and how it fits the system.
The Xtralis VSP-877 is a Flush Mount Sampling Point, a functionally and aesthetically improved alternative to the conical sampling point for Xtralis aspirating smoke detection pipe networks. Its flush-mount design gives a less obtrusive installation, with a standard 2 mm (5/64") pilot sampling hole that can be drilled out and a 32-35 mm ceiling panel cutout for mounting. RoHS/REACH compliant and supplied in White 80258, it accepts 6, 8, 10 mm and 1/2" capillary and is marked "XTRALIS FIRE DETECTION SYSTEM - DO NOT PAINT."
Technical overview
VSP-877 gives Xtralis aspirating smoke detection pipe networks a flush-mounted alternative to the conical sampling point, suitable for all Xtralis aspirating smoke detectors as a standard solution. White 80258 is the colour of this base reference, while black and grey counterparts are ordered as VSP-877-B and VSP-877-G.
Fitting happens from one side of the ceiling only: the wing-lock arrangement allows the point to be installed from below, which suits fixed ceilings where the far side cannot be reached. Once in place the head sits flush against the ceiling for a less obtrusive appearance, and the small pilot sampling hole is drilled out on site where a larger opening is called for.
Capillary connections span metric and imperial sizes, and installations in the Americas running ½” capillary tubing can add the optional VSP-878 push-in connect adaptor kit. Wording incorporated into the point warns against painting, in line with code requirements, and the material is RoHS/REACH compliant.
Specifications
Full technical data for this part.
| Color | White 80258 |
|---|---|
| Material | RoHS/REACH compliant |
| Sampling hole | Standard 2 mm (5/64”) pilot sampling hole which can be drilled out up to 5 mm (13/64”) |
| Ceiling panel cutout | 32 mm – 35 mm Ceiling Panel Cutout for mounting |
| Capillary diameter | 6, 8, 10 mm, 1/2” |
| Design | Flush mount design provides less obtrusive installation and improved aesthetics |
| Ordering code | VSP-877 — Flush Mount Sampling Point |
| Ordering code black | VSP-877-B — Flush Mount Sampling Point (Black) |
| Ordering code grey | VSP-877-G — Flush Mount Sampling Point (Grey) |
| Marking | Incorporates text (XTRALIS FIRE DETECION SYSTEM – DO NOT PAINT) complying with codes |
Specifications sourced from manufacturer documentation.
Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know