ex-VAT pricing shown

Now open for trade ordersGent, Morley-IAS & Xtralis stock added weekly — open to the trade.

Replacement PSU · Vigilon Plus

Gent VS-PSU-72 Vigilon Replacement Power Supply

VS-PSU-72 — Hero
Product type
Replacement PSU
Battery capacity
2 x 12V 21Ah batteries
Battery float voltage
about: 27.5V @ 15 Deg C, 27.3V @ 20 Deg C, 27.1V @ 25 Deg C
Mains input
Live and Neutral wires connected to PSU module terminals P2 (L N)
Battery connection
For VIG-1-72: battery filter cable to socket P1
Communication indicator
LD5 Indicates Communication with MCC
Indicator leds
LD1 LD2 LD3 LD4 LD5

Overview

What it is and how it fits the system.

The Gent VS-PSU-72 is a replacement power supply unit for the VIG1-24/72, suitable for installation in VIG1-72 Vigilon 4/6 loop fire alarm control panels. It supports 2 x 12V 21Ah batteries with a float voltage of about 27.5V at 15 degC, drives mains via terminals P2 (L N) and battery via socket P1, and provides status LEDs LD1-LD5, including LD5 for MCC communication. Protected by FS2 (3A15 QB glass) and FS6 (3.15A AS ceramic) fuses, it supports battery and PSU disconnection/reconnection testing.

Technical overview

The VS-PSU-72 is a Gent by Honeywell replacement power supply unit for the Vigilon Plus range, specifically designed for VIG1-24/72 and VIG1-72 Vigilon 4/6 loop fire alarm control panels. It supports two 12V 21Ah batteries with a float voltage that varies from about 27.5V at 15°C to 27.1V at 25°C, and drives mains input via terminals P2 (Live and Neutral) while connecting the batteries through socket P1.

Status indication is provided by LEDs LD1 through LD5, with LD5 specifically indicating communication with the MCC. The unit is protected by FS2 (3A15 QB glass) and FS6 (3.15A AS ceramic) fuses, and supports disconnection and reconnection testing to verify fault monitoring. Safety warnings note that removal of the cover exposes live parts, and the PCB earth must be securely connected to the case via its fixing screw. The module mounts inside the back box and is retained by the original fixing screws.

Specifications

Full technical data for this part.

Product typeReplacement PSU
Battery capacity2 x 12V 21Ah batteries
Battery float voltageabout: 27.5V @ 15 Deg C, 27.3V @ 20 Deg C, 27.1V @ 25 Deg C
Mains inputLive and Neutral wires connected to PSU module terminals P2 (L N)
Battery connectionFor VIG-1-72: battery filter cable to socket P1
Communication indicatorLD5 Indicates Communication with MCC
Indicator ledsLD1 LD2 LD3 LD4 LD5
Fuse fs2FS2 3A15 QB glass
Fuse fs6FS6 3.15A AS ceramic
Fault monitoringCarry out battery and PSU tests, such as disconnection and reconnection of battery circuit(s) and mains supply to check for fault monitoring
Safety warningWARNING Removal of cover exposes live parts DANGER
EarthingPCB earth to Case; ensure fixing screw is securely fitted
MountingFit the PSU module in the back box and secure it using the original fixing screws (two screws located top right and bottom left of the PSU module)
DisposalWEEE Directive: at the end of their useful life, the packaging, product and batteries should be disposed of via a suitable recycling centre. Do not dispose of with normal household waste. Do not burn.

Specifications sourced from manufacturer documentation.

Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know