Replacement PSU · Vigilon Plus
Gent VS-PSU-72 Vigilon Replacement Power Supply

- Product type
- Replacement PSU
- Battery capacity
- 2 x 12V 21Ah batteries
- Battery float voltage
- about: 27.5V @ 15 Deg C, 27.3V @ 20 Deg C, 27.1V @ 25 Deg C
- Mains input
- Live and Neutral wires connected to PSU module terminals P2 (L N)
- Battery connection
- For VIG-1-72: battery filter cable to socket P1
- Communication indicator
- LD5 Indicates Communication with MCC
- Indicator leds
- LD1 LD2 LD3 LD4 LD5
Overview
What it is and how it fits the system.
The Gent VS-PSU-72 is a replacement power supply unit for the VIG1-24/72, suitable for installation in VIG1-72 Vigilon 4/6 loop fire alarm control panels. It supports 2 x 12V 21Ah batteries with a float voltage of about 27.5V at 15 degC, drives mains via terminals P2 (L N) and battery via socket P1, and provides status LEDs LD1-LD5, including LD5 for MCC communication. Protected by FS2 (3A15 QB glass) and FS6 (3.15A AS ceramic) fuses, it supports battery and PSU disconnection/reconnection testing.
Technical overview
The VS-PSU-72 is a Gent by Honeywell replacement power supply unit for the Vigilon Plus range, specifically designed for VIG1-24/72 and VIG1-72 Vigilon 4/6 loop fire alarm control panels. It supports two 12V 21Ah batteries with a float voltage that varies from about 27.5V at 15°C to 27.1V at 25°C, and drives mains input via terminals P2 (Live and Neutral) while connecting the batteries through socket P1.
Status indication is provided by LEDs LD1 through LD5, with LD5 specifically indicating communication with the MCC. The unit is protected by FS2 (3A15 QB glass) and FS6 (3.15A AS ceramic) fuses, and supports disconnection and reconnection testing to verify fault monitoring. Safety warnings note that removal of the cover exposes live parts, and the PCB earth must be securely connected to the case via its fixing screw. The module mounts inside the back box and is retained by the original fixing screws.
Specifications
Full technical data for this part.
| Product type | Replacement PSU |
|---|---|
| Battery capacity | 2 x 12V 21Ah batteries |
| Battery float voltage | about: 27.5V @ 15 Deg C, 27.3V @ 20 Deg C, 27.1V @ 25 Deg C |
| Mains input | Live and Neutral wires connected to PSU module terminals P2 (L N) |
| Battery connection | For VIG-1-72: battery filter cable to socket P1 |
| Communication indicator | LD5 Indicates Communication with MCC |
| Indicator leds | LD1 LD2 LD3 LD4 LD5 |
| Fuse fs2 | FS2 3A15 QB glass |
| Fuse fs6 | FS6 3.15A AS ceramic |
| Fault monitoring | Carry out battery and PSU tests, such as disconnection and reconnection of battery circuit(s) and mains supply to check for fault monitoring |
| Safety warning | WARNING Removal of cover exposes live parts DANGER |
| Earthing | PCB earth to Case; ensure fixing screw is securely fitted |
| Mounting | Fit the PSU module in the back box and secure it using the original fixing screws (two screws located top right and bottom left of the PSU module) |
| Disposal | WEEE Directive: at the end of their useful life, the packaging, product and batteries should be disposed of via a suitable recycling centre. Do not dispose of with normal household waste. Do not burn. |
Specifications sourced from manufacturer documentation.
Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know