Trade prices shown ex VAT. Order by 3pm for same-day dispatch on stocked lines, UK mainland. Free UK delivery on orders over £250 ex VAT.

Part Number or the Week S3EP-V-VAD-HPR-R

Gent Battery Box for VIGPLUS-72 & VIGPLUS-72-NP. Batteries not included - 72hr panels require 4 x 4015-602-YFR (Power Sonic Flame Retardant 12V 21Ah) to meet compliance regulations.

Part no.VS-BATTBOX-72
BrandGent
RangeVigilon Plus
Sub-rangeVigilon Plus Accessories
Honeywell Gent VS-BATTBOX-72 Battery Box — grey metal box with keyhole and Honeywell Gent logo

Image for illustration; item supplied may differ

At a glance

  • VIGPLUS-72Fits VIGPLUS-72 panels.
  • VIGPLUS-72-NPFits VIGPLUS-72-NP panels.
  • External battery enclosureHouses the batteries outside the control panel.
  • Separate batteriesBatteries are supplied separately; a pair of 550 door keys, battery wiring harnesses, a terminal block and four fuses are included.
  • Four batteries requiredThe 72-hour panel requires four 4015-602-YFR batteries.
  • Battery typePower Sonic flame retardant 12V 21Ah batteries.

Description

The Gent VS-BATTBOX-72 is an external battery box for VIGPLUS-72 and VIGPLUS-72-NP fire alarm panels, also used for the VIG72-UPGR Plus conversion. Supplied with a pair of 550 door keys, battery wiring harnesses, a terminal block and four fuses. Four 4015-602-YFR Power Sonic flame retardant 12V 21Ah batteries are required and supplied separately. The box has upper and lower shelves and a lockable door. It can sit beneath the panel or remotely, up to 10m away with 1.5mm² MICC or 15m with 2.5mm² MICC. An earth lead connects the panel and box.

VS-BATTBOX-72 is an external battery enclosure for VIGPLUS-72 and VIGPLUS-72-NP panels. The battery requirement for the 72-hour panel is four 4015-602-YFR Power Sonic flame retardant 12V 21Ah batteries, supplied separately.

Read the full technical description

VS-BATTBOX-72 is an external battery enclosure for VIGPLUS-72 and VIGPLUS-72-NP panels. The battery requirement for the 72-hour panel is four 4015-602-YFR Power Sonic flame retardant 12V 21Ah batteries, supplied separately.

In a Vigilon Plus installation, the battery box may occupy a position below the panel or be installed remotely. The maximum panel-to-box cable distance is 10m with 1.5mm² MICC or 15m with 2.5mm² MICC.

The Plus battery box has upper and lower shelves and a lockable door. Supplied with a pair of 550 door keys, battery wiring harnesses, a terminal block and four fuses. An earth lead is required between the panel and battery box.

VS-BATTBOX-72 is also used for the VIG72-UPGR Plus conversion.

Specifications

ManufacturerGent
Product typeExternal panel battery enclosure
Panel fitVIGPLUS-72; VIGPLUS-72-NP
Supplied withA pair of 550 door keys, battery wiring harnesses, one terminal block and four fuses; batteries supplied separately
Current battery order4 x 4015-602-YFR
Specified batteryPower Sonic flame retardant 12V 21Ah
Plus installation: box positionsBeneath the control panel or remote
Plus installation: 1.5mm² MICC10m maximum panel-to-box cable distance
Plus installation: 2.5mm² MICC15m maximum panel-to-box cable distance
Plus installation: earth continuityEarth lead between control panel and battery box

Specifications per manufacturer documentation, subject to change. E&OE.

Documents

DocumentTypeSizeDownload
Installation manual (VS-BATTBOX, VS-BATTBOX-72)Installation164 KBDownload PDF
Installation manual (VS-BATTBOX, VS-BATTBOX-72, VS-FILTER-72)Installation216 KBDownload PDF

FAQs

Which panels does VS-BATTBOX-72 fit?

VS-BATTBOX-72 is the external battery enclosure for VIGPLUS-72 and VIGPLUS-72-NP fire alarm panels. It is also used for the VIG72-UPGR Plus conversion. Four 4015-602-YFR Power Sonic flame retardant 12V 21Ah batteries are required for the 72-hour panel and are supplied separately. In a Plus installation, the battery box may occupy a position below the control panel or be installed remotely. An earth lead is required between the panel and the battery box.

Does VS-BATTBOX-72 include batteries?

The batteries are supplied separately from the box. The 72-hour panel requires four 4015-602-YFR Power Sonic flame retardant 12V 21Ah batteries. The box comes with a pair of 550 door keys, battery wiring harnesses, a terminal block and four fuses. VS-BATTBOX-72 houses the batteries outside the VIGPLUS-72 or VIGPLUS-72-NP control panel. It has upper and lower shelves and a lockable door, and can be fitted beneath the panel or at a remote location.

Can the battery box be installed away from the panel?

Yes. In a Vigilon Plus installation, the battery box may occupy a position below the control panel or be installed remotely. The maximum cable distance between the panel and box is 10m with 1.5mm² MICC or 15m with 2.5mm² MICC. An earth lead is required between the two enclosures. VS-BATTBOX-72 is the external panel battery box for VIGPLUS-72 and VIGPLUS-72-NP panels and is also used for the VIG72-UPGR Plus conversion.

What is the internal arrangement of the Plus battery box?

The Plus battery box has an upper shelf and a lower shelf, with a lockable door. An earth lead is required between the control panel and the box. The box can be fitted beneath the panel or at a remote location. For the VIGPLUS-72 and VIGPLUS-72-NP panels, the battery requirement is four 4015-602-YFR Power Sonic flame retardant 12V 21Ah batteries, supplied separately. The maximum remote cable distance is 10m with 1.5mm² MICC or 15m with 2.5mm² MICC.

Is this box used for a VIG72-UPGR Plus conversion?

Yes. VS-BATTBOX-72 is the external battery enclosure for the VIG72-UPGR Plus conversion. Four 4015-602-YFR Power Sonic flame retardant 12V 21Ah batteries are supplied separately. The Plus battery box can sit beneath the panel or at a remote location. The maximum panel-to-box cable distance is 10m with 1.5mm² MICC or 15m with 2.5mm² MICC, and an earth lead is required between the enclosures. The box has upper and lower shelves and a lockable door.