Gent Input/Output Card for Vigilon V3+
| Part no. | VIG-IOC-V3+ |
|---|---|
| Brand | Gent |
| Range | Gent Legacy |
| Sub-range | V3+ |

Image for illustration; item supplied may differ
At a glance
- New IO Card V3+ BSVIG-IOC-V3+ is the new IO Card V3+ (BS) and has version 3+ software.
- BS5839 Part 4 PanelsIt is designed for installation in fire panels to BS5839:Part 4, such as the Vigilon, 34000, 32000, 3400 and 3300 analogue addressable fire panels and Network (or Terminal) nodes.
- Backplane Plug In CardThe card plugs into the backplane in a Control Panel or Network Node, with associated terminals on terminal card RS232/RS485.
- Size And WeightOverall size is 148mm height x 100mm width with a weight of 72g (approximate).
- Environmental RangeOperating temperature is 0C to 45C, storage temperature -10C to 55C and relative humidity non condensing up to 90%.
- Simultaneous Port UseThere is no need to switch between the RS232 and RS485 ports as they are both available for simultaneous use.
- Addressing And BaudNode address range is 1 to 31 and baud when installed as an additional IO card can be 1200, 1800, 2400, 3600, 4800, 7200, 9600 and 19200.
- Replaces Existing IO CardsThe new IO card combine the functions of all the existing IO cards and will replace the existing IO cards.
Description
Version 3+ software is what marks out this Input Output card. Its place is a fire panel built to BS5839:Part 4 - the Vigilon, 34000, 32000, 3400 and 3300 analogue addressable fire panels and Network (or Terminal) nodes - where it plugs into the backplane of a Control Panel or Network Node.
Ensure all DIP switches of SW1 are set to the Off position before installing the IO card in the backplane of Vigilon or 34000 system Control panel or Network node. No dongle is required for the DIP switches to work, when used as a second or additional IO card. The SW1 switch settings apply for the new IO Card when installed as an additional IO card in the Vigilon or 34000 panel or node.
VIG-IOC-V3+ is the new IO Card V3+ (BS), an Input Output card that has version 3+ software and is designed for installation in fire panels to BS5839:Part 4, such as the Vigilon, 34000, 32000, 3400 and 3300 analogue addressable fire panels and Network (or Terminal) nodes. It is a backplane plug in card for a Control Panel or Network Node, with associated terminals on terminal card RS232/RS485.
Overall size is 148mm height x 100mm width and weight 72g (approximate). Operating temperature is 0C to 45C, storage temperature -10C to 55C and relative humidity non condensing up to 90%. There is no need to switch between the RS232 and RS485 ports as they are both available for simultaneous use.
Node address range is 1 to 31, and baud when installed as an additional IO card can be 1200, 1800, 2400, 3600, 4800, 7200, 9600 and 19200. DIP switches SW1 take the required baud rate and node address and rotary switch SW2 the required function, both before the card goes into a spare socket of the backplane.
Read the full technical description
The card is 148mm height x 100mm width, 72g (approximate), rated 0C to 45C operating and -10C to 55C in storage, with relative humidity up to 90%.
VIG-IOC-V3+ is the new IO Card V3+ (BS), an Input Output card that has version 3+ software and is designed for installation in fire panels to BS5839:Part 4, such as the Vigilon, 34000, 32000, 3400 and 3300 analogue addressable fire panels and Network (or Terminal) nodes. It is a backplane plug in card for a Control Panel or Network Node, with associated terminals on terminal card RS232/RS485.
Overall size is 148mm height x 100mm width and weight 72g (approximate). Operating temperature is 0C to 45C, storage temperature -10C to 55C and relative humidity non condensing up to 90%. There is no need to switch between the RS232 and RS485 ports as they are both available for simultaneous use.
Node address range is 1 to 31, and baud when installed as an additional IO card can be 1200, 1800, 2400, 3600, 4800, 7200, 9600 and 19200. DIP switches SW1 take the required baud rate and node address and rotary switch SW2 the required function, both before the card goes into a spare socket of the backplane.
One additional IO card can be fitted into the spare socket on the backplane of the Vigilon/34000/3400 control panels and up to four into the backplane sockets of the associated Network node. A 20 way ribbon cable connects between DKC connector P4 and the IO card socket P2. The new IO card combine the functions of all the existing IO cards and will replace the existing IO cards.
Specifications
| Product type | Input/Output card |
|---|---|
| Designation | BS Vigilon IOC (VIG-IOC-V3+) |
| Rotary switch setting not domain aware | SW2 Position 1 |
| Rotary switch setting domain aware | SW2 Position 5 |
| Configuration action | Set the Rotary Switch (SW2) to the Required position |
| Communications interface | RS232 Max 15m |
| Panel requirement | IOC Card is required for VIG1-24/72 Panels |
Specifications per manufacturer documentation, subject to change. E&OE.
Optional accessories
- VIG-IOC-DOMInput/Output Card for VIGPLUS-24 and VIGPLUS-72 Vigilon Panels (EN54)EN equivalent variant is the EN Vigilon IOC (VIG-IOC-DOM)£709.55ex VAT£851.46 inc VATIn stock