VESDA Modbus HLI for Darwish & Honeywell only
| Part no. | VHX-0410 |
|---|---|
| Brand | VESDA |
| Range | VESDA Programming and Connectivity |

Image for illustration; item supplied may differ
At a glance
- ModBus HLI Type 2VHX-0410 is the ModBus HLI - Type 2, which has the echoing function disabled.
- Quiescent PowerQuiescent power consumption is 1.68 W.
- Smoke Level ScalingSmoke Level is reported relative to the Fire Alarm threshold where the full scale is 20.
- Threshold Reporting ValuesThe Fire Alarm threshold is reported as the relative sensitivity to 1 %obs/m, so 2 %obs/m reports 50, 1 %obs/m reports 100, 0.1 %obs/m reports 1000 and 0.02 %obs/m reports 5000.
- Fault MappingAll VESDAnet faults are mapped on one or more of the Modbus HLI faults, namely Head Fault, Head Fault (Battery and Mains), Head Fault (Scanner) and Flow Fault.
- Zone Fault HandlingNetwork faults are mapped onto all zones, whereas zone faults are mapped onto that particular zone.
- Detector CommandsReset Detector, Isolate Detector and Start Scan Test can be issued across the interface.
Description
Type 2 is the ModBus HLI variant whose echoing function is disabled.
Detector alarm thresholds for Alert, Action and Fire can be read across the interface, and the commands Reset Detector, Isolate Detector and Start Scan Test can be issued to a detector. The unit is easily configured using Xtralis configuring and monitoring software packages.
VHX-0410 is the ModBus HLI - Type 2 within the Xtralis VESDA ModBus HLI family, and it is the variant which has the echoing function disabled. Quiescent power consumption is 1.68 W.
Smoke Level is reported relative to the Fire Alarm threshold where the full scale is 20, giving actual smoke level = (Reported smoke value * Fire1 Threshold) / 20. The Fire Alarm threshold itself is reported as the relative sensitivity to 1 %obs/m, so a detector set at 2 %obs/m reports 50, one at 1 %obs/m reports 100, one at 0.1 %obs/m reports 1000 and one at 0.02 %obs/m reports 5000.
Read the full technical description
Secondary monitoring is the recommended role; primary reporting to the fire panel or another primary reporting system is also suitable. Where primary reporting is the duty, the interface must first be integrated, then approved or listed with the serving fire panel or primary reporting system, under the relevant fire standards and codes.
VHX-0410 is the ModBus HLI - Type 2 within the Xtralis VESDA ModBus HLI family, and it is the variant which has the echoing function disabled. Quiescent power consumption is 1.68 W.
Smoke Level is reported relative to the Fire Alarm threshold where the full scale is 20, giving actual smoke level = (Reported smoke value * Fire1 Threshold) / 20. The Fire Alarm threshold itself is reported as the relative sensitivity to 1 %obs/m, so a detector set at 2 %obs/m reports 50, one at 1 %obs/m reports 100, one at 0.1 %obs/m reports 1000 and one at 0.02 %obs/m reports 5000.
All VESDAnet faults are mapped on one or more of the Modbus HLI faults, namely Head Fault, Head Fault (Battery and Mains), Head Fault (Scanner) and Flow Fault. Faults categorised as network faults are mapped onto all zones, whereas zone faults are mapped onto that particular zone. Information reaching the host takes in Fault Status (Head, Battery and Mains, Flow, Scanner), Detector Alarm State (Alert, Action, Fire), Smoke Level and Smoke Bargraph Level. Secondary monitoring is what a VESDA HLI is recommended for, taking in fire alarms as well as the other notifications a VESDAnet carries; used instead for primary reporting, it must be integrated and approved or listed with whichever fire panel or primary reporting system receives it, to the relevant fire standards and codes.
Specifications
| Type | ModBus HLI - Type 2 |
|---|---|
| Echo function | Echoing function disabled (Type 2) |
| Supply voltage | 24 VDC |
| Current consumption | 70 mA (Quiescent) |
| Power consumption | 1.68 W (Quiescent) |
| Dimensions | 188 mm x 98 mm x 40 mm (7.4 in. x 3.9 in. x 1.6 in. approx.) |
| Weight | 0.4 kg (0.9 lbs) |
| Number of detectors supported | Up to 200 VESDA Devices (includes max 40 detectors and remaining VESDA ancillary devices) |
|---|---|
| Max detectors per vesdanet | supports up to a maximum of 40 VESDA detectors on a VESDAnet |
| Detector zone number range | supports VESDAnet detector zone numbers between 1 to 200; divides the address range into 7 logical networks |
| Modem support | Modem support is not available |
| Product warranty | 2 years |
| Host interface | RS-232 |
| Vesdanet interface | RS-485 |
Specifications per manufacturer documentation, subject to change. E&OE.