Gent SAFE 1 button white plus interface
| Part no. | SAFE-WHITE-S-KIT |
|---|---|
| Brand | Gent |
| Range | SAFE Button |
| Sub-range | Button + Interface Module |

Image for illustration; item supplied may differ
At a glance
- Switch and interface kitSAFE-WHITE-S-KIT includes a switch, S4-34450 interface and wiring loom.
- Combined test and silence controlHold down until the red LED lights: test in normal conditions, or silence during the initial smoke-alert delay.
- Red status LEDThe red LED indicates activation of the test or silence control.
- S4-34450 connectionThe switch connects to channel 1 for silence and test, with channel 3 driving the red LED.
- Local alarm testHold the button down for about five seconds until the red LED lights; alarms stop five seconds after release.
- 30m switch cable limitThe cable run between the SAFE button and its S4-34450 interface can be up to 30m.
Description
The Gent SAFE-WHITE-S-KIT is a white single SAFE button kit for local alarm control. Its one position tests local alarms in normal conditions and silences them during the initial smoke-alert delay. A red LED shows when the control is active. The kit includes the switch, an S4-34450 interface and wiring loom, with the interface enclosure supplied separately. The cable run from switch to interface is limited to 30m. Area delays are set during commissioning. The switch is 85mm high and 85mm wide, with a depth of 25mm plus the terminal block. Test the local alarms each month in normal conditions.
The SAFE-WHITE-S-KIT combines the white single SAFE switch with an S4-34450 four-channel interface and wiring loom. The interface connects to the fire alarm loop. An interface enclosure is required separately.
Read the full technical description
The SAFE-WHITE-S-KIT combines the white single SAFE switch with an S4-34450 four-channel interface and wiring loom. The interface connects to the fire alarm loop. An interface enclosure is required separately.
The single button uses a downward hold for both functions. In normal conditions it starts a local alarm test; during the initial smoke-alert delay it silences the area alarms. Hold it until the red LED lights to activate either function. Interface channel 1 handles silence and test, and channel 3 drives the red LED. Channels 2 and 4 are unused in this configuration.
The SAFE range works with Vigilon Plus and Vigilon Compact Plus panels with MCC or MCB software V4.57 minimum and LPC software V4.52 minimum. Configure the area and interface with Commissioning Tool V1.34. Where a printer connects through an IOC, that card needs V4.16 minimum; loop repeat and mimic panels require MRC software V1.09 minimum. Area delays and extensions are set as part of commissioning.
Keep the switch-to-interface cable run within 30m. The button measures 85mm high by 85mm wide, with a depth of 25mm plus the terminal block. Allow enough backbox depth for the assembly and secure all terminal connections. Tighten the fixing screws without a powered screwdriver and do not apply an insulation tester to the switch. Test the area alarms monthly and clean the switch with a dry, soft, lint-free cloth.
Specifications
| Product | SAFE switch and interface kit |
|---|---|
| Switch arrangement | Single button, one position |
| Finish | White |
| Supplied items | SAFE switch, S4-34450 interface and wiring loom |
| Power source | Loop powered through the S4-34450 interface |
| Control interface | S4-34450 |
| Switch-to-interface cable | 30m maximum |
| Button dimensions | 85mm H x 85mm W x 25mm D, plus terminal block |
| SAFE range switch terminals | 2.5mm² terminal capacity |
| Silence control | Downward press; hold until red LED lights |
| Test control | Downward press for about 5 seconds, until red LED lights |
| Indicators | Red LED |
| Test run-on | 5 seconds after releasing the test control |
|---|---|
| Interface enclosure | Separate from kit |
| SAFE range panel compatibility | Vigilon Plus and Vigilon Compact Plus |
| MCC/MCB software | V4.57 minimum for SAFE operation |
| LPC software | V4.52 minimum for SAFE operation |
| Commissioning tool | V1.34 for SAFE area and interface configuration |
| Channel 1 | Silence and test input |
| Channel 2 | Unused in single-button configuration |
| Channel 3 | Red LED output |
| Channel 4 | Unused in single-button configuration |
| Area alarm test interval | Monthly |
| Cleaning | Dry, soft, lint-free cloth |
Specifications per manufacturer documentation, subject to change. E&OE.
Spares & replacement parts
- SAFE-WHITE-S-SPARESAFE 1 button white plus loomReplacement switch for the 1-position White SAFE kit.£145.48ex VAT£174.58 inc VATIn stock
FAQs
What is supplied with SAFE-WHITE-S-KIT?
SAFE-WHITE-S-KIT includes a switch, S4-34450 interface and wiring loom. The interface enclosure is a separate item. The switch operates the alarms assigned to its area, while the interface connects the controls to the fire alarm loop. Its single control provides local test and silence control. Keep the cable run between switch and interface within 30m. The SAFE range uses Vigilon Plus or Vigilon Compact Plus panels with the required card software and area configuration.
How does SAFE-WHITE-S-KIT silence local alarms?
During the initial smoke-alert delay, hold the switch down until the red LED lights, then release it. This silences alarms in its assigned area. Delay periods and permitted extensions depend on the commissioned area settings. Near the end of the delay, the red LED flashes and the alert sounds; another press can extend the delay where configured. If smoke remains when the allowed delay expires, evacuation alarms follow the system cause and effect.
How do I test the alarms with SAFE-WHITE-S-KIT?
Test SAFE-WHITE-S-KIT while the system is in its normal condition. Press the button downwards for about five seconds, until the red LED lights and the area alarms sound. Keep it pressed for the test, then release it; the alarms continue for five seconds before stopping and the LED turns off. Carry out the area alarm test monthly. The same button operates the silence function during the initial smoke-alert delay, so its action depends on the system condition.
How is SAFE-WHITE-S-KIT connected and mounted?
The switch in SAFE-WHITE-S-KIT connects to its S4-34450 interface over a cable run of up to 30m. Channel 1 handles silence and test, and channel 3 drives the red LED. The switch is 85mm high and 85mm wide, with a depth of 25mm plus its terminal block. Allow sufficient backbox depth, secure the wire connections and tighten the fixing screws without a powered screwdriver. Do not apply an insulation tester to the switch.
Does SAFE-WHITE-S-KIT provide the double button’s smoke-disable function?
SAFE-WHITE-S-KIT uses single-button SAFE operation. Its downward press starts an area alarm test in normal conditions and silences the local alarms during the initial smoke-alert delay. Pre-event smoke disablement belongs to double-button SAFE operation. The single button connects through interface channel 1 for test and silence, with channel 3 for its red LED; channels 2 and 4 are unused. On a double-button switch, the upper test position has a green LED and the lower silence position has a red LED.