Gas Detection
Li-ion Tamer LT-SEN-IM-UL Off-Gas Interface Module
- Ordering code description
- Li-ion Tamer Interface Module UL
- Dimensions
- 140 (L) x 85 (W) x 34 (H) [mm]
- Input power range
- 15 - 32VDC Typical 24VDC
- Max sensors per module
- 1
- System outputs
- 3 Relay outputs/MODBUS/CANBUS
- Power consumption interface module with sensors
- 65mA, Max 1.56W (@ 24VDC)
- Relay load
- Max. 30 VDC 2A Max. 125 VAC 0.5 A
Overview
What it is and how it fits the system.
The Li-ion Tamer Interface Module UL is the interface module of the Li-ion Tamer Sensor Multi Output Solution (MOS), monitoring the off-gas sensor and integrating its output signals for lithium-ion battery monitoring. It runs on a 15-32VDC input (typical 24VDC) and provides 3 relay outputs plus MODBUS and CANBUS communication. Measuring 140 x 85 x 34 mm, each module supports one sensor with MODBUS at 9600 baud and CANBUS at 500K.
Technical overview
LT-SEN-IM-UL carries the ordering description Li-ion Tamer Interface Module UL and forms the interface-module component of the Li-ion Tamer Sensor Multi Output Solution (MOS) for lithium-ion battery monitoring. The module belongs to both MOS assemblies: LT-SEN-MOS pairs it with the LT-SEN-M Gen 2+ off-gas sensor, and LT-SEN-MOS-C49 pairs it with the LT-SEN-M-C49 sensor variant. In either build, one module monitors one off-gas sensor installed at the battery racks or cabin, and integrates its output signals.
Three relays carry the alarm1, alarm2 and fault functions, with alarm outputs latching until reset or until a command is sent to release them. MODBUS and CANBUS communication is available alongside the relay outputs, and an RJ45 connection supplies operating power to the attached sensor. LED indication reports state: green blinking through initialisation, steady green in normal running, steady red in alarm and steady yellow on a sensor fault.
Certification as a fire alarm system module is to UL864 10th, joined by ULC S527, FM 6540, Safety UL61010-1, RoHS EN50581-2002, EMI EN55011-2010 and EMC EN61326-1-2021. Physical wiring for the RJ45 sensor connection, relay outputs and MODBUS/CANBUS terminals is detailed in the installation manual.
Specifications
Full technical data for this part.
| Ordering code description | Li-ion Tamer Interface Module UL |
|---|---|
| Dimensions | 140 (L) x 85 (W) x 34 (H) [mm] |
| Input power range | 15 - 32VDC Typical 24VDC |
| Max sensors per module | 1 |
| System outputs | 3 Relay outputs/MODBUS/CANBUS |
| Power consumption interface module with sensors | 65mA, Max 1.56W (@ 24VDC) |
| Relay load | Max. 30 VDC 2A Max. 125 VAC 0.5 A |
| Output rj45 | 0.25W (5VDC/ 0.5mA) power supply for sensor |
| Baud rate | MODBUS: 9600 CANBUS: 500K |
| Communication hardware | MODBUS: RS485, 2-wire (TX, RX) CANBUS: 2-wire (CANH, CANL) |
| Target lifetime | > 10 years |
| Fault detection | Single cell failure |
| Relays numbers | 3 (alarm1, alarm2, fault) |
| Alarm latch | Alarm output latch, reset or send command to release. |
Specifications sourced from manufacturer documentation.
Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know