ex-VAT pricing shown

Now open for trade ordersGent, Morley-IAS & Xtralis stock added weekly — open to the trade.

PSU

HLSPS25 24V 2.5A EN54-4 Power Supply, Steel Enclosure

Output current
PS25 2.5A (with battery charging disabled)
Output voltage
28V dc +/- 2%
Number of outputs
2
Input voltage
115-230V ac 50/60 Hz
Charger current
300mA (7.2Ah Batteries) or 600mA (17Ah)
Ingress protection
IP 30
Approval
EN54-4 / A2

Overview

What it is and how it fits the system.

The HLSPS25 is a 24VDC 2.5A EN54-4 power supply housed in a surface-mounting steel enclosure, providing monitoring and standby capability with a 2.5A alarm rating (battery charging disabled). It delivers a regulated 28Vdc (+/-2%) output across two outputs from a 115-230Vac 50/60Hz input, with selectable charger current of 300mA (7.2Ah) or 600mA (17Ah). Rated IP30, it provides a 1A 24Vdc fault relay and removable terminals for cable up to 2.5mm CSA.

Technical overview

The HLSPS25 is an Ancillaries PSU range 24VDC 2.5amp EN54-4 power supply in a surface-mounting steel enclosure, delivering a regulated 28Vdc (+/-2%) output across two outputs from a 115-230Vac 50/60Hz input. It provides monitoring and standby capability with a 2.5A alarm rating and battery charging disabled, featuring selectable charger current of 300mA (7.2Ah) or 600mA (17Ah) for external battery support.

Rated IP30, the unit includes a 1A 24Vdc fault relay and removable terminals accommodating cable up to 2.5mm CSA. It measures 377(w) x 408(h) x 92(d) mm with mounting hole centres at 337mm horizontal and 352mm vertical, and offers 24 or 72 hour standby capability. The HLSPS25 accepts up to two 17Ah batteries and is compatible with the Morley-IAS Max two loop system, superseding the HLS-PSU-20 model.

Specifications

Full technical data for this part.

Order codeHLSPS25
Output currentPS25 2.5A (with battery charging disabled)
Output voltage28V dc +/- 2%
Number of outputs2
Input voltage115-230V ac 50/60 Hz
Charger current300mA (7.2Ah Batteries) or 600mA (17Ah)
Fault relay1A 24Vdc
Cable capacity2.5mm CSA
Removable terminalsRemovable terminals for up to 2.5mm cable
Ingress protectionIP 30
Dimensions377(w) x 408(h) x 92(d) mm
Mounting hole centres337mm (horizontal), 352mm (vertical) (see diagram)
ApprovalEN54-4 / A2
Standby capability24 hour or 72 hour standby capability

Specifications sourced from manufacturer documentation.

Specifications per manufacturer documentation, subject to change — E&OE. Spotted an inaccuracy? Let us know

Optional accessories

Optional additions — this product works without them.

MA-2000-01

Morley-IAS Max two loop (networkable) For System Sensor & Apollo protocol

compatible / works with: Morley-IAS Max two loop (networkable) For System Sensor & Ap

£1,017.20
ex VAT
£1,220.64 inc VAT
Sold separately
HLSPS50

24VDC 5amp EN54-4 Power Supply

Alternative — sibling EN54-4 PSU in the same steel enclosure, 5A instead of 2.5A alarm capability.

£323.00
ex VAT
£387.60 inc VAT
Sold separately