VESDA FAAST-LT
| Part no. | FAAST-LT |
|---|---|
| Brand | VESDA |
Image for illustration; item supplied may differ
Description
The Xtralis FAAST LT is a Fire Alarm Aspiration Sensing Technology unit that connects to a Gent Vigilon fire panel through the S4 ASD Interface Unit (S4-34440-ASD). It ships in three laser-detector variants: the single-port FL0111E and FL0112E (1-channel, one laser detector) and the dual-port FL0122E (2-channel, two laser detectors), each available as a pre-configured -VIG-INT bundle with the ASD interface and EOL PCB. The interface delivers up to 48-hour standby on the FL0111E and 24-hour standby on the FL0112E and FL0122E, with port selection set per variant at commissioning.
Specifications
| Single-port variants (fl0111e / fl0112e) | FAAST LT (FL0111E or FL0112E) Single-Port (1-channel) & 1 laser detector |
|---|---|
| Dual-port variant (fl0122e) | FAAST LT (FL0122E) Dual-Port (2-channel) & 2 laser detectors |
| Pre-configured bundle skus (faast lt + asd interface + eol pcb) | FL0111E-VIG-INT (S4-34440-ASD + FL0111E + EOL PCB); FL0112E-VIG-INT (S4-34440-ASD + FL0112E + EOL PCB); FL0122E-VIG-INT (S4-34440-ASD + FL0122E + EOL PCB) |
| Standby power - fl0112e / fl0122e | 24-hour standby power to a FAAST LT FL0112E, FAAST LT FL0122E (and FAAST 8100E) from an ASD Interface Unit (S4-34440-ASD) with 12V 14Ahr batteries |
| Standby power - fl0111e | The ASD Interface unit is capable of delivering standby of up to 48-hour to a FAAST LT FL0111E |
| Factory interface setting - fl0112e | The S4 ASD interface unit is factory set to 'ASD 1 Port I/F' to connect to a FAAST LT FL0112E unit |
| Interface setting - fl0122e | If the ASD interface unit is connected to a FAAST LT FL0122E (or a FAAST 8100E) use Vigilon Commissioning tool V1.31 and select 'ASD 2 Port I/F' (or 'ASD 8100') in Device settings |
| Bundle interface selection | for FAAST LT bundles: FL0111E-VIG-INT select 'ASD 1 Port I/F'; FL0112E-VIG-INT select 'ASD 1 Port I/F'; FL0122E-VIG-INT select 'ASD 2 Port I/F' |
| Single-port wiring (fl0111e / fl0112e) | Wiring a FAAST LT Single Port (1-Channel) FL0111E or FL0112E to a ASD Interface Unit (S4-34440-ASD) |
| Dual-port wiring (fl0122e) | Wiring a FAAST LT Dual Port (2-Channel) FL0122E unit to a ASD Interface Unit (S4-34440-ASD) |
Specifications per manufacturer documentation, subject to change. E&OE.
Documents
| Document | Type | Size | Download |
|---|---|---|---|
| Installation manual (FAAST-8100E, FAAST-LT, FL0122E, S4-34440-ASD) | Installation | 4.4 MB | Download PDF |
Optional accessories
- S4-34440-ASDASD Mains Powered Interface for FAAST LT. Batteries not included - requires 2 x 4015-604-YFR (Power Sonic Flame Retardant 12V 14Ah) to meet compliance regulations.S4 ASD Interface Unit (S4-34440-ASD) - the FAAST LT unit connects to and is monitored by t£661.99ex VAT£794.39 inc VATIn stock