Skip to content

Trade prices shown ex VAT. Order by 3pm on a working day for same-day dispatch on stocked lines, Great Britain. Free UK delivery on orders over £250 ex VAT.

Part Number or the Week S3EP-V-VAD-HPR-R

VESDA FAAST Automatic Purging Unit- Freezer Applications

Part no.F-BO-AFE70-3
BrandVESDA
RangeFAAST
Sub-rangeAir Purging
F-BO F-BO-AFE70-3 Automatic Purging Unit — cream enclosure with red pipe and metal fitting, warning labels

Image for illustration; item supplied may differ

£2,865.20 ex VAT
£3,438.24 inc VAT
Available to order, ships 16th November
Dates are based on our supplier's lead times and may change.
Free UK delivery over £250 ex VAT, otherwise £9.95 ex VAT (£11.94 inc VAT).

Volume pricing

Bulk discount, applied automatically at checkout.

QuantityUnit price ex VAT
1+£2,865.20
5+£2,764.92
25+£2,664.64

At a glance

  • High Air Flow ValveThe solenoid valve gives a typical air flow rate of approx. 5,000 l/min (ANR) at 0.7MPa (7bar).
  • Low Temperature OperationThe DF designation covers refrigeration area down to -20°C and allows use in environments with low temperatures.
  • Ingress ProtectionThe unit is rated IP20D.
  • No Added Air ResistanceThe purging units do not represent an additional air resistance in the sampling pipe network and do not have to be included in the calculation of the sampling pipe network.
  • Panel Actuated PurgingStandard connection uses indirect actuation through the fire detection control panel and master-slave working uses direct actuation, both in accordance with EN 54-13.
  • Status LED And SettingsOperating conditions are indicated by the status LED, while the purging program, internal clock, time and device number are set at the unit.
  • Shared Series PlatformF-BO-AFE70-3 has outer dimensions and functionality in common with F-BO-AFE70-2 and differs in the built-in solenoid valve.
  • CE Marking BasisCE marking rests on the Electromagnetic Compatibility Directive 2014/30/EU with EN 55022:2010 and EN 50130-4:2011 + A1:2014, and expressly does not result from the guideline 2014/68/EU.

Description

F-BO-AFE70-3 is suitable for even larger and further-flung pipe systems. Its solenoid valve is rated at approx. 5,000 l/min (ANR) at 0.7MPa (7bar), and its DF build adds refrigeration area duty down to -20°C. Outer dimensions and functionality match F-BO-AFE70-2 of the same series; the built-in solenoid valve is what separates them.

The enclosure is rated IP20D. Connection is made to the sampling pipe, to the aspirating smoke detector and to a compressed-air supply, with filters and check valves used on the pipe connection. Actuation is indirect through the fire detection control panel as standard, or direct through the panel where units work in master-slave mode, in accordance with EN 54-13. The values specified in the project planning guidelines of the aspirating smoke detector must not be exceeded.

Read the full technical description

Under §8 of the DGVO these purging units are pressure equipment with low risk potential, designed and manufactured in accordance with the engineering practice of a Member State, and the CE labelling of the device expressly does not result from the guideline 2014/68/EU.

F-BO-AFE70-3 is an automatic purging unit of the Automatic Purging Units Series F-BO-AFE70, working on the sampling pipe network of an aspirating smoke detector. Its solenoid valve gives a typical air flow rate of approx. 5,000 l/min (ANR) at 0.7MPa (7bar), which suits even larger and further-flung pipe systems, while the DF designation covers refrigeration area down to -20°C and allows use in environments with low temperatures.

The purging unit does not represent an additional air resistance in the sampling pipe network and therefore does not have to be included in the calculation of that network, although the values specified in the project planning guidelines of the aspirating smoke detector must not be exceeded.

Operating conditions are shown on the status LED, and the purging program, the internal clock, the time and the device number are all set at the unit, by the user or by the installer. A Slave activation output supports master-slave working with direct actuation through the fire detection control panel, alongside the standard connection with indirect actuation through the panel, both in accordance with EN 54-13.

CE marking rests on the Electromagnetic Compatibility Directive 2014/30/EU with EN 55022:2010 and EN 50130-4:2011 + A1:2014, and expressly does not result from the guideline 2014/68/EU.

Specifications

Order namePurging Unit / AFE70-3
Ordering descriptionFAAST Purging System AFE70-3 (High Flow & sub-zero temperatures)
Supply voltage21.6 - 30 VDC
Current consumption normal8mA (normal condition) @ 24v
Current consumption solenoid energised300mA (solenoid valve energised)
Air delivery performance5000 lit/minute
Operating temperature-20°C to +40°C
Ingress protectionIP20D
Relative humidityMax. 95% at 40°C
Height68 mm
Width204 mm
Depth160 mm
Weight3.2kg (approx.)
Housing cover colourGrey White, RAL 9002

Specifications per manufacturer documentation, subject to change. E&OE.